Date |
Text |
2007-02-06 10:30:31 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| 1. SHT P-1 UNIT A SANITARY RISER DIAGRAM. THE AUTOMATIC |
| CLOTHES WASHER FIXTURE SHALL CONNECT TO A BRANCH DRAIN |
| OR DRAINAGE STACK A MINIMUM OF 3" IN DIAMETER. SECTION |
| 406.3.--THE FITTING SHOWN AT THE TOP OF THE STACK |
| IS NOT APPROVED. THERE SHOULD BE A WYE DOWNSTREAM AND A |
| SWEEP ABOVE THE WYE TO CONNECT THE THREE BATHROOM |
| GROUPS. (SEE RED LINE EXAMPLE ON ONE SET OF PLANS). |
| |
| 2. SHT P-1 WATER HEATER DETAIL, IF A BACKFLOW PREVENTOR |
| IS REQUIRED, THEN THERMAL EXPANSION CONTROL WILL BE |
| REQUIRED PER SECTION 607.3.2. |
| |
| 3. SHT P-2 UNIT B SANITARY RISER DIAGRAM. THE AUTOMATIC |
| CLOTHES WASHER FIXTURE SHALL CONNECT TO A BRANCH DRAIN |
| A MINIMUM OF 3" IN DIAMETER. SECTION 406.3.--THE |
| TUB AND THE WATER CLOSET AT THE BASE OF THE STACK ARE |
| NOT VENTED. SECTION 901.2.1.--ONLY THE FIXTURES |
| WITHIN THE BATHROOM GROUP SHALL CONNECT TO THE |
| WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT. |
| SECTION 909.1. THE SECOND FLOOR MASTER BATH & BATH #2 |
| SHALL CONNECT DOWNSTREAM OF THE BATHROOM FIXTURES IN |
| OPTIONAL BATHROOM #4. THE AAV FOR OPTIONAL BATHROOM #4 |
| SHALL BE INSTALLED FOR THE BRANCH LINE FOR THE BATHROOM |
| ONLY. AS SHOWN IT IS VENTING ONLY THE LAV. (SEE RED |
| LINE EXAMPLES ON ONE SET OF PLANS). |
| |
| 4. MORE INFORMATION IS REQUIRED. ARE THE UNITS TO BE |
| INDIVIDUALLY METERED? IF THERE IS A SINGLE WATER METER, |
| AN RPZV BACKFLOW WILL BE REQUIRED. SECTION 608.13.2. |
| PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 5. SUBMIT WATER RISER DIAGRAMS FOR EACH UNIT TYPE. SHOW |
| ALL PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS |
| REQUIRED BY SECTION 604.9. (WASH MACHINES, DISH |
| WASHERS, & ICE MAKERS). WATER HAMMER ARRESTORS SHALL BE |
| LOCATED IN AN "EFFECTIVE RANGE", (NOT IN THE CEILING), |
| PER PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| SECTION 106.3.5.1.3(3)(13) |
| |
| 6. SUBMIT PLUMBING FLOOR PLANS FOR EACH UNIT SHOWING |
| THE SANITARY, WATER, P/T DISCHARGE LINE, EMERGENCY W/H |
| PAN DRAIN LINE, THE WATER SERVICE, AND SANITARY SEWER |
| LOCATIONS. SECTION 106.3.5.1.3(4)(10). |
| |
| 7. AN IRRIGATION PERMIT AND PLANS ARE REQUIRED. SECTION |
| 105.1. |
| |
| REVIEW BY KEN STEVENS |