2007-02-06 10:30:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P-1 UNIT A SANITARY RISER DIAGRAM. THE AUTOMATIC
 CLOTHES WASHER FIXTURE SHALL CONNECT TO A BRANCH DRAIN
 OR DRAINAGE STACK A MINIMUM OF 3" IN DIAMETER. SECTION
 406.3.--THE FITTING SHOWN AT THE TOP OF THE STACK
 IS NOT APPROVED. THERE SHOULD BE A WYE DOWNSTREAM AND A
 SWEEP ABOVE THE WYE TO CONNECT THE THREE BATHROOM
 GROUPS. (SEE RED LINE EXAMPLE ON ONE SET OF PLANS).
  
 2. SHT P-1 WATER HEATER DETAIL, IF A BACKFLOW PREVENTOR
 IS REQUIRED, THEN THERMAL EXPANSION CONTROL WILL BE
 REQUIRED PER SECTION 607.3.2.
  
 3. SHT P-2 UNIT B SANITARY RISER DIAGRAM. THE AUTOMATIC
 CLOTHES WASHER FIXTURE SHALL CONNECT TO A BRANCH DRAIN
 A MINIMUM OF 3" IN DIAMETER. SECTION 406.3.--THE
 TUB AND THE WATER CLOSET AT THE BASE OF THE STACK ARE
 NOT VENTED. SECTION 901.2.1.--ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUP SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT.
 SECTION 909.1. THE SECOND FLOOR MASTER BATH & BATH #2
 SHALL CONNECT DOWNSTREAM OF THE BATHROOM FIXTURES IN
 OPTIONAL BATHROOM #4. THE AAV FOR OPTIONAL BATHROOM #4
 SHALL BE INSTALLED FOR THE BRANCH LINE FOR THE BATHROOM
 ONLY. AS SHOWN IT IS VENTING ONLY THE LAV. (SEE RED
 LINE EXAMPLES ON ONE SET OF PLANS).
  
 4. MORE INFORMATION IS REQUIRED. ARE THE UNITS TO BE
 INDIVIDUALLY METERED? IF THERE IS A SINGLE WATER METER,
 AN RPZV BACKFLOW WILL BE REQUIRED. SECTION 608.13.2.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 5. SUBMIT WATER RISER DIAGRAMS FOR EACH UNIT TYPE. SHOW
 ALL PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. (WASH MACHINES, DISH
 WASHERS, & ICE MAKERS). WATER HAMMER ARRESTORS SHALL BE
 LOCATED IN AN "EFFECTIVE RANGE", (NOT IN THE CEILING),
 PER PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 SECTION 106.3.5.1.3(3)(13)
  
 6. SUBMIT PLUMBING FLOOR PLANS FOR EACH UNIT SHOWING
 THE SANITARY, WATER, P/T DISCHARGE LINE, EMERGENCY W/H
 PAN DRAIN LINE, THE WATER SERVICE, AND SANITARY SEWER
 LOCATIONS. SECTION 106.3.5.1.3(4)(10).
  
 7. AN IRRIGATION PERMIT AND PLANS ARE REQUIRED. SECTION
 105.1.
  