Text |
2007-01-22 09:15:11 | *** DENIED *** |
| 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE CORRECT. |
| |
| 2) SEE ENERGY CALCULATIONS TOTAL COOLING BTU'S 264,000, |
| AND PLANS ARE SHOWING 8 UNITS AT 59,000 = 472,000 TOTAL |
| BTU'S, THE TWO MUST COINCIDE, PLEASE CORRECT. |
| |
| 3) PLEASE SUBMIT MANUAL J CALCULATIONS FOR MODEL "A" |
| ONE UNIT ONLY 2081 SQUARE FEET, AND MODEL "B" ONE UNIT |
| ONLY 2157 SQUARE FEET. |
| |
| 4) FORTH BEDROOM OPTION IS MISSING FROM MECHANICAL |
| PLANS PAGE M-2, PLEASE CORRECT. |
| |
| 5) SEE PAGE M-2 FIRST FLOOR PLAN POWER ROOM #102, |
| EXHAUST UP TO ATTIC, EXHAUST AIR MUST DISCHARGE TO THE |
| OUTDOORS, SEE 2004 FBC/M 501.2. PLEASE CORRECT. |
| |
| 6) SEE PAGE M-1 FIRST FLOOR PLAN, THE CLOTHES DRYER |
| VENT MAY NOT DISCHARGE ON TO THE A/C CONDENSER UNIT, |
| SEE 2004 FBC/M 401.5.2. PLEASE CORRECT. |
| |
| 7) RETURN AIR TRANSFER DUCTS TO ALL ROOM ARE |
| UNDER-SIZED, BALANCED RETURN AIR MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |