Plan Review Notes
Plan Review Notes For Permit 06120586
Permit Number 06120586
Review Stop M
Sequence Number 1
Notes
Date Text
2007-01-22 09:15:11*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE CORRECT.
  
 2) SEE ENERGY CALCULATIONS TOTAL COOLING BTU'S 264,000,
 AND PLANS ARE SHOWING 8 UNITS AT 59,000 = 472,000 TOTAL
 BTU'S, THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 3) PLEASE SUBMIT MANUAL J CALCULATIONS FOR MODEL "A"
 ONE UNIT ONLY 2081 SQUARE FEET, AND MODEL "B" ONE UNIT
 ONLY 2157 SQUARE FEET.
  
 4) FORTH BEDROOM OPTION IS MISSING FROM MECHANICAL
 PLANS PAGE M-2, PLEASE CORRECT.
  
 5) SEE PAGE M-2 FIRST FLOOR PLAN POWER ROOM #102,
 EXHAUST UP TO ATTIC, EXHAUST AIR MUST DISCHARGE TO THE
 OUTDOORS, SEE 2004 FBC/M 501.2. PLEASE CORRECT.
  
 6) SEE PAGE M-1 FIRST FLOOR PLAN, THE CLOTHES DRYER
 VENT MAY NOT DISCHARGE ON TO THE A/C CONDENSER UNIT,
 SEE 2004 FBC/M 401.5.2. PLEASE CORRECT.
  
 7) RETURN AIR TRANSFER DUCTS TO ALL ROOM ARE
 UNDER-SIZED, BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.