2007-02-15 15:01:02 | *****DENIED***** |
| |
| |
| 01.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK |
| WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH |
| SUBMITTED PLAN SHEET. |
| |
| 02.PLEASE SUBMIT THE FOLLOWING INFORMATION: |
| *CONSTRUCTION TYPE* OCCUPANCY TYPE*BUILDING HEIGHT |
| * BUILDING SQUARE FOOTAGE *INTERIOR FINISH |
| CLASSIFICATIONS * ANY OTHER PERTINENT INFORMATION TO |
| ASSIST IN THE PLAN REVIEW. |
| |
| 03.WILL THE STRUCTURE HAVE A FIRE ALARM AND/OR FIRE |
| SPRINKLER SYSTEM?IF SO, PROVIDE A LAYOUT OF THE FIRE |
| PROTECTION SYSTEM(S) FOR REVIEW. |
| |
| 04.NFPA 101 - 2003 EDITION AND THE FORIDA FIRE |
| PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. |
| |
| 05.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 06.THE CONSTRUCTION OPERATION AND /OR THE STOCKING OF |
| NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE |
| OR HINDER EMERGENCY ACCESS RESPONSE TO THE SAID |
| PROPERTY OR THE VICINITY THEREOF. |
| |
| 07.THE SITE PLAN (SHEET A-1) DOES NOT SHOW ANY FIRE |
| HYDRANTS.INDICATE THE LOCATION OF FIRE HYDRANT(S) |
| WITHIN 300 FEET OF THE STRUCTURE.PLEASE BE ADVISED |
| THAT AN ADDITIONAL HYDRANT MAY BE REQUIRED IF THIS |
| DISTANCE IS GREATER THAN 500 FEET. |
| |
| 08IT APPEARS THAT THIS STRUCTURE WILL BE SETBACK |
| FROM EMBASSY DRIVE.IF THIS TRUE, AS PER WEST PALM |
| BEACH CODE, A MONUMENT SIGN OR MARQUEE SHALL POST THE |
| ADDRESS RANGE FOR THE DEVELOPMENT.THESE NUMBERS SHALL |
| BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN |
| WIDTH. |
| |
| 09.PLEASE INDICATE ON PLANS THAT ALL FIRE RATED DOORS |
| (103,108,111) SHALL BE EQUIPPED WITH SELF CLOSING |
| DEVICES AND SHALL POSTIVELY CLOSE UPON RELEASE. |
| |
| 10.ON THE APPROPIATE EXTERIOR ELEVATION SHEET, |
| DISPLAY THE ADDRESS FOR THE UNITS. |
| |
| 11.PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE |
| TIED INTO A FIRE ALARM SYSTEM.SMOKE ALARMS (SA), ON |
| THE OTHER HAND, RECEIVE THEIR OPERATING POWER FROM THE |
| BUILDING ELECTRICAL SYSTEM.SEE ELECTRICAL SHEETS. |
| |
| 12.SMOKE ALARMS ARE TO BE ARRANGED SO THAT THE |
| OPERATION OF ANY SMOKE ALARMSHALL CAUSE THE ALARM IN |
| ALL SMOKE ALARMS WITHIN THE DWELLING UNIT TO SOUND. |
| |
| 13.A FIRE HYDRANT IS SHOWN ON SHEET LP-1 BUT NOT ON |
| SHEET A-1.IS THIS AN EXISTING HYDRANT OR A PROPOSED |
| HYDRANT TO BE INSTALLED? |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |