Plan Review Notes
Plan Review Notes For Permit 06120586
Permit Number 06120586
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-02-15 15:01:02*****DENIED*****
  
  
 01.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 02.PLEASE SUBMIT THE FOLLOWING INFORMATION:
 *CONSTRUCTION TYPE* OCCUPANCY TYPE*BUILDING HEIGHT
 * BUILDING SQUARE FOOTAGE *INTERIOR FINISH
 CLASSIFICATIONS * ANY OTHER PERTINENT INFORMATION TO
 ASSIST IN THE PLAN REVIEW.
  
 03.WILL THE STRUCTURE HAVE A FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEM?IF SO, PROVIDE A LAYOUT OF THE FIRE
 PROTECTION SYSTEM(S) FOR REVIEW.
  
 04.NFPA 101 - 2003 EDITION AND THE FORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 05.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 06.THE CONSTRUCTION OPERATION AND /OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER EMERGENCY ACCESS RESPONSE TO THE SAID
 PROPERTY OR THE VICINITY THEREOF.
  
 07.THE SITE PLAN (SHEET A-1) DOES NOT SHOW ANY FIRE
 HYDRANTS.INDICATE THE LOCATION OF FIRE HYDRANT(S)
 WITHIN 300 FEET OF THE STRUCTURE.PLEASE BE ADVISED
 THAT AN ADDITIONAL HYDRANT MAY BE REQUIRED IF THIS
 DISTANCE IS GREATER THAN 500 FEET.
  
 08IT APPEARS THAT THIS STRUCTURE WILL BE SETBACK
 FROM EMBASSY DRIVE.IF THIS TRUE, AS PER WEST PALM
 BEACH CODE, A MONUMENT SIGN OR MARQUEE SHALL POST THE
 ADDRESS RANGE FOR THE DEVELOPMENT.THESE NUMBERS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH.
  
 09.PLEASE INDICATE ON PLANS THAT ALL FIRE RATED DOORS
 (103,108,111) SHALL BE EQUIPPED WITH SELF CLOSING
 DEVICES AND SHALL POSTIVELY CLOSE UPON RELEASE.
  
 10.ON THE APPROPIATE EXTERIOR ELEVATION SHEET,
 DISPLAY THE ADDRESS FOR THE UNITS.
  
 11.PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE
 TIED INTO A FIRE ALARM SYSTEM.SMOKE ALARMS (SA), ON
 THE OTHER HAND, RECEIVE THEIR OPERATING POWER FROM THE
 BUILDING ELECTRICAL SYSTEM.SEE ELECTRICAL SHEETS.
  
 12.SMOKE ALARMS ARE TO BE ARRANGED SO THAT THE
 OPERATION OF ANY SMOKE ALARMSHALL CAUSE THE ALARM IN
 ALL SMOKE ALARMS WITHIN THE DWELLING UNIT TO SOUND.
  
 13.A FIRE HYDRANT IS SHOWN ON SHEET LP-1 BUT NOT ON
 SHEET A-1.IS THIS AN EXISTING HYDRANT OR A PROPOSED
 HYDRANT TO BE INSTALLED?
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  