Plan Review Notes
Plan Review Notes For Permit 06120586
Permit Number 06120586
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-12 18:52:49** UNSAT **
  
 ** PLEASE SEE THESE ARE COMMENTS BASED ON THE PLANS
 SUBMITTED. PLEASE SEE THAT THERE MAY BE COMMENTS ON THE
 NEXT REVIEW WHICH MAY BE NEW AS SOME INFORMATION AS
 SHOWN ON THESE PLANS WILL BE CHANGING SYSTEMS.
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC AS THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE PLANS ARE BEING SUBMITTED AND
 LABELED AS TOWNHOUSE UNITS, HOWEVER PLEASE SEE IF THESE
 ARE INDEED FEE SIMPLE "TOWNHOUSES" AS PER FBC
 DEFINITIONS, PLEASE SEE REQUIREMENTS OF THE FBC AND
 ELECTRICAL CODE WHICH WOULD CHANGE MANY ITEMS IN THE
 DESIGN AND PLEASE KNOW SEPARATE PERMIT APPLICATIONS,
 PLANS AND FEES WOULD BE REQUIRED ON EACH FEE SIMPLE
 TOWNHOUSE. PLEASE SEE AS ALL UNITS ARE CONNECTED BY A
 COMMON AREA AND ONE BUILDING THIS DOES NOT SEEM
 POSSIBLE.
 PLEASE KNOW THE PLANS AS SUBMITTED IS FOR ONE BUILDING
 AND PLEASE SEE COMMENTS FOR ELECTRICAL SERVICE(S) AS
 SUBMITTED.
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION.
  
 2) NOTE: PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES ALL
 SMOKE DEVICES TO BE A MINIMUM OF 3FT FROM BATH DOORS
 AND 20FT FROM COOKING APPLIANCES. THERE ARE EXCEPTIONS
 FOR COOKING APPLIANCES IF DEVICE IS OF AN PHOTOELECTRIC
 TYPE AND/OR RESETTING TYPE.
  
 3) NOTE: PLEASE SEE SOME RECEPTACLES SPACED ALONG
 KITCHEN COUNTER SPACE. IT APPEARS SOME NEED TO BE
 RELOCATED TO MEET 210.52C1
  
 4) NOTE: PLEASE SEE ALL RECEPTACLES SERVING KITCHEN
 COUNTER SPACE SHALL BE SHOWN AS GFI/GFI PROTECTED.
 210.8A6.
  
 5) NOTE: PLEASE SEE NO RECEPTACLE BEING SHOWN FOR THE
 DISPOSAL FOR DISCONNECTING MEANS.
 422.31
  
 6) NOTE: PLEASE CLARIFY THE TYPE FIRE PROTECTION BEING
 INSTALLED FOR BUILDING. PLEASE SEENFPA-72 11-5.1.1,
 11.8.3. PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL
 FOR SD FOR SMOKE DETECTORS THIS IS OK, HOWEVER PLEASE
 KNOW IF THESE ARE INDEED SMOKE DETECTORS AS DEFINED IN
 NFPA72, THESE WOULD BE DEVICES WHICH ONLY DETECT AND
 WOULD SIGNAL TO OTHER ALARM/HORN DEVICES. NO ALARM HORN
 DEVICES ARE SHOWN. PLEASE INDICATE IF PART OF A FUTURE
 LV FA SYSTEM.
 PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED
 DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY
 WOULD BE LABELED AS SA FOR SMOKE ALARMS.
 PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT
 THE SOUTHERN SECTION IAEI MEETING FROM NFPA THAT IF
 UNITS ARE INDEED DEVICES WHICH DETECT AND SOUND AN
 ALARM, PLANS SHOULD SHOW THEM AS SA'S AND THIS IS NOT
 NEW CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST
 TO SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06
 SHOULD BE CHANGING IF AND WHERE APPLICABLE. PLEASE SEE
 SECTIONS OF THE FBC AS STATED ON PLANS WHICH ACTUALLY
 CONTAIN THE WORDING OF SMOKE ALARMS IN THE FBC.
 IF PART OF A LV FIRE/SECURITY SYSTEM PLEASE INDICATE AS
 SUCH. PLEASE SHOW DEVICES THEN FOR SOUNDING. PLEASE
 ALSO SEE MISSING SMOKE DETECTION/ SMOKE ALARM DEVICE IN
 UNIT "C" FIRST FLOOR.
  
 7) NOTE: PLEASE SEE FBC 2004 13-103.1.1.1 WHICH
 REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED.
 PLEASE NOTE ON PLANS ACCORDINGLY AND INDICATE
 FIXTURES.
  
 8) NOTE: PLEASE BE SURE PLANS REFLECT THE CODES IN
 WHICH THE DESIGN IS UNDER AND PERMITTED UNDER. PLEASE
 LIST THE FOLLOWING AT A MINIMUM FOR ELECTRICAL SHEETS
 AND ARCHITECTURAL SHEETS.
 2005 NFPA-70 (NEC), 2002-NFPA-72 NATIONAL FIRE ALARM
 CODE
 ** PLEASE KNOW FOR INFORMATIONAL PURPOSE, AS OF
 DECEMBER 8TH, 2006 THE STATE OF FLORIDA ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70(
 NEC). AS THIS PROJECT WAS SUBMITTED FOR PERMIT BEFORE
 THIS DATE, THIS PROJECT IS UNDER THE PREVIOUS CODES AS
 STATED ABOVE. PLEASE SEE THAT THERE ARE STRUCTURAL
 DESIGN CHANGES ALSO DONE UNDER THE NEW 2006 REVISIONS
 TO THE FBC. PLEASE SEE BUILDING REVIEW NOTES FOR DESIGN
 PRESSURES ETC. (NOTED FOR INFORMATION ONLY)
  
 9) NOTE: PLEASE SEE THE HWH IS BEING SHOWN WITH
 RECEPTACLE FOR THE CONNECTION OF THIS UNIT WHICH IS NOT
 PERMITTED. PLAN NEEDS TO SHOW A DISCONNECT/J-BOX IF
 BREAKER IS GOING TO BE USED TO MEET THE CODE. PLEASE
 SEE EXCEPTIONS FOR WITHIN SITE.
 422.30, 4220.31
  
 10) NOTE: PLEASE SEE MISSING GFI RECEPTS FOR KITCHEN
 PENINSULAR PER 210.52C3, 210.8A6
  
 11) NOTE: PLEASE SEE THE FOLLOWING COMMENT, HOWEVER
 PLEASE STILL SEE RISER DOES NOT INDICATE ANY MAIN
 DISCONNECT FOR SERVICE. THE FOLLOWING COMMENT AND HOW
 PLANS WILL BE SUBMITTED WILL DICTATE WHAT TYPE OF
 SERVICE AND HOW MUCH WILL CHANGE; HOWEVER IN EITHER
 CASE MAINS ARE REQUIRED.
 230.70, 230.71, 240.4 ETC
  
 12) NOTE: PLEASE SEE AS THIS IS ONE BUILDING; PLEASE
 SEE 230.2 AS THE PROPOSED SERVICESFOR EACH UNIT ARE
 NOT GRANTED AS SHOWN ON PLANS. PLEASE REVISE SERVICE
 RISER DIAGRAM FOR GROUPING OF MAINS INTO ONE SERVICE.
 PLEASE KNOW IF THESE ARE SUBMITTED AS TRUE
 TOWNHOUSES/FEE SIMPLE, PROPERTY LINES, SEPARATE PERMIT
 APPLICATIONS ETC, AND THEN INDIVIDUAL SERVICES TO EACH
 UNIT MAY BE PERMITTED. THIS WILL CHANGE RISER AS SHOWN
 OR NOT?
 PLEASE REVISE RISER DIAGRAM.
  
 13) NOTE: PLEASE SEE RISER AS SHOWN NOW SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR FROM THE METER TO THE
 PANEL. WITHOUT SHOWING MAIN ON RISER IT IS NOT POSSIBLE
 TO CORRECTLY DETERMINE THE LOCATION OF THE EGC. PLEASE
 SEE 250.6, 250.24B AS THE EGC IS NOT PERMITTED BEFORE
 THE FIRST MEANS OF DISCONNECT.
  
 14) NOTE: PLEASE SHOW ALL ROOMS AND AREA DESIGNATIONS
 ON PLANS. PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. PLEASE
 SEE THERE ARE SOME ITEMS WHICH CAN NOT BE REVIEWED FOR
 CODE COMPLIANCE AT THIS TIME DUE TO THIS INFORMATION
 NOT SHOWN.
 NEC 408.4, 310.16, 240.4 ETC.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTIONS.
  
 15) NOTE: PLEASE SEE 250.66 FOR SIZING OF THE GROUNDING
 ELECTRODE CONDUCTOR. DEPENDING ON THE SERVICE AND WHAT
 THE BUILDING FINALLY COMES DOWN TO AND THE SIZE OF THE
 SERVICE, THIS WILL DETERMINE THE SIZE OF THE GEC.
 PLEASE SEE THE 150A METER AS SHOWN INDICATES A 1/0?
  
 16) NOTE: PLEASE KNOW BASED ON SOME OF THE CIRCUITING
 AT THIS TIME NOT BEING SHOWN; PLEASE BE SURE TO SEE
 210.12 FOR AFCI PROTECTED CIRCUITS. THIS APPEARS TO BE
 ADDRESSED, BUT CAN NOT BE CONFIRMED AT THIS TIME.
  
 17) NOTE: PLEASE SEE MISSING THE REQUIRED GFI FOR SOME
 CONDENSING UNITS PER 210.63, 210.8A3 (UNIT "A").
  
 23) NOTE: PLEASE SEE SUBMIT COMPLETE LOAD CALCULATIONS
 FOR SERVICE. 220.84, 220.12, 220.42, 220.44 ETC. PLEASE
 KNOW DEPENDING ON THE NEW SERVICE AND LOAD,
 CONSIDERATION OF 230.2 WILL BE REVIEWED, HOWEVER PLEASE
 KNOW AT THIS TIME THE SINGLE METER/SERVICE FOR EACH IS
 OK, HOWEVER IF ONE MAIN AND A METER BANK IS INSTALLED
 FOR MULTI-FAMILY/CONDO SERVICE, THISH WILL REQUIRE
 CALCULATIONS FOR SUCH.
  
 24) NOTE:PLEASE SEE 210.52 FOR AREAS FOR REQUIRED
 RECEPTS WHICH ARE MISSING ON PLANS. PLEASE SEE UNIT
 "A/B" ETC.
 PLEASE SEE ONE SET OF PLANS ARE REDLINED FOR LOCATIONS
 WHICH ARE MISSING DEVICES WITHIN 6FT OF DOOR, 2FT OR
 MORE OF WALL SPACE AND HALLWAYS AS NOTED.
  
 25) NOTE: PLEASE COMPLETE RISER DIAGRAM WITH ALL
 FEEDERS TO UNITS AND CORRELATE WITH THE OVER CURRENT
 PROTECTION DEVICES OF THAT FOR EACH UNIT ONCE RISER IS
 FINALIZED.
 215.5, 310.16, 240.4 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 26) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING
 CONDUCTORS FROM MAINS TO EACH UNIT PER 250.122.
 250.24B, 250.110, ETC. (WHERE REQUIRED AND
 APPLICABLE).
  
 27) NOTE: PLEASE SEE THAT THE ADDRESS FOR THIS PROJECT
 SHALL BE PLACED ON THE TITLE BLOCKS. PLEASE KNOW AT
 THIS TIME, THIS IS A MULTI-FAMILY SINGLE BUILDING WITH
 THE ADDRESS OF 1800 EMBASSY DR. PLEASE SEE NOTE FROM
 ADDRESSING REVIEWER FOR ADDRESS?S ALSO DEPENDING ON HOW
 THESE ARE BEING PERMITTED AND SUBMITTED.
 THIS IS NOT AND HAS NOT BEEN SUBMITTED AS TOWNHOUSES,
 OR CONDO'S.
 FAC 61G15-23.002, FAC 61G1-16.004
  
 28) NOTE: PLEASE CLARIFY DINING ROOM/AREA ON PLANS SO
 THAT ONCE CIRCUITING IS SHOWN COMPLIANCE WITH 210.52B1,
 210.11C1 AND 220.52 CAN BE VERIFIED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved