Date |
Text |
2007-01-12 18:52:49 | ** UNSAT ** |
| |
| ** PLEASE SEE THESE ARE COMMENTS BASED ON THE PLANS |
| SUBMITTED. PLEASE SEE THAT THERE MAY BE COMMENTS ON THE |
| NEXT REVIEW WHICH MAY BE NEW AS SOME INFORMATION AS |
| SHOWN ON THESE PLANS WILL BE CHANGING SYSTEMS. |
| |
| ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO |
| CHAPTER 1 OF THE FBC AS THAT WHICH IS ADOPTED BY THE |
| CITY OF WEST PALM BEACH. |
| |
| 1) NOTE: PLEASE SEE PLANS ARE BEING SUBMITTED AND |
| LABELED AS TOWNHOUSE UNITS, HOWEVER PLEASE SEE IF THESE |
| ARE INDEED FEE SIMPLE "TOWNHOUSES" AS PER FBC |
| DEFINITIONS, PLEASE SEE REQUIREMENTS OF THE FBC AND |
| ELECTRICAL CODE WHICH WOULD CHANGE MANY ITEMS IN THE |
| DESIGN AND PLEASE KNOW SEPARATE PERMIT APPLICATIONS, |
| PLANS AND FEES WOULD BE REQUIRED ON EACH FEE SIMPLE |
| TOWNHOUSE. PLEASE SEE AS ALL UNITS ARE CONNECTED BY A |
| COMMON AREA AND ONE BUILDING THIS DOES NOT SEEM |
| POSSIBLE. |
| PLEASE KNOW THE PLANS AS SUBMITTED IS FOR ONE BUILDING |
| AND PLEASE SEE COMMENTS FOR ELECTRICAL SERVICE(S) AS |
| SUBMITTED. |
| |
| PLEASE SEE COMMENTS FROM OTHER TRADES |
| FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 2) NOTE: PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES ALL |
| SMOKE DEVICES TO BE A MINIMUM OF 3FT FROM BATH DOORS |
| AND 20FT FROM COOKING APPLIANCES. THERE ARE EXCEPTIONS |
| FOR COOKING APPLIANCES IF DEVICE IS OF AN PHOTOELECTRIC |
| TYPE AND/OR RESETTING TYPE. |
| |
| 3) NOTE: PLEASE SEE SOME RECEPTACLES SPACED ALONG |
| KITCHEN COUNTER SPACE. IT APPEARS SOME NEED TO BE |
| RELOCATED TO MEET 210.52C1 |
| |
| 4) NOTE: PLEASE SEE ALL RECEPTACLES SERVING KITCHEN |
| COUNTER SPACE SHALL BE SHOWN AS GFI/GFI PROTECTED. |
| 210.8A6. |
| |
| 5) NOTE: PLEASE SEE NO RECEPTACLE BEING SHOWN FOR THE |
| DISPOSAL FOR DISCONNECTING MEANS. |
| 422.31 |
| |
| 6) NOTE: PLEASE CLARIFY THE TYPE FIRE PROTECTION BEING |
| INSTALLED FOR BUILDING. PLEASE SEENFPA-72 11-5.1.1, |
| 11.8.3. PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL |
| FOR SD FOR SMOKE DETECTORS THIS IS OK, HOWEVER PLEASE |
| KNOW IF THESE ARE INDEED SMOKE DETECTORS AS DEFINED IN |
| NFPA72, THESE WOULD BE DEVICES WHICH ONLY DETECT AND |
| WOULD SIGNAL TO OTHER ALARM/HORN DEVICES. NO ALARM HORN |
| DEVICES ARE SHOWN. PLEASE INDICATE IF PART OF A FUTURE |
| LV FA SYSTEM. |
| PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED |
| DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY |
| WOULD BE LABELED AS SA FOR SMOKE ALARMS. |
| PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT |
| THE SOUTHERN SECTION IAEI MEETING FROM NFPA THAT IF |
| UNITS ARE INDEED DEVICES WHICH DETECT AND SOUND AN |
| ALARM, PLANS SHOULD SHOW THEM AS SA'S AND THIS IS NOT |
| NEW CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST |
| TO SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06 |
| SHOULD BE CHANGING IF AND WHERE APPLICABLE. PLEASE SEE |
| SECTIONS OF THE FBC AS STATED ON PLANS WHICH ACTUALLY |
| CONTAIN THE WORDING OF SMOKE ALARMS IN THE FBC. |
| IF PART OF A LV FIRE/SECURITY SYSTEM PLEASE INDICATE AS |
| SUCH. PLEASE SHOW DEVICES THEN FOR SOUNDING. PLEASE |
| ALSO SEE MISSING SMOKE DETECTION/ SMOKE ALARM DEVICE IN |
| UNIT "C" FIRST FLOOR. |
| |
| 7) NOTE: PLEASE SEE FBC 2004 13-103.1.1.1 WHICH |
| REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED. |
| PLEASE NOTE ON PLANS ACCORDINGLY AND INDICATE |
| FIXTURES. |
| |
| 8) NOTE: PLEASE BE SURE PLANS REFLECT THE CODES IN |
| WHICH THE DESIGN IS UNDER AND PERMITTED UNDER. PLEASE |
| LIST THE FOLLOWING AT A MINIMUM FOR ELECTRICAL SHEETS |
| AND ARCHITECTURAL SHEETS. |
| 2005 NFPA-70 (NEC), 2002-NFPA-72 NATIONAL FIRE ALARM |
| CODE |
| ** PLEASE KNOW FOR INFORMATIONAL PURPOSE, AS OF |
| DECEMBER 8TH, 2006 THE STATE OF FLORIDA ADOPTED THE |
| 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70( |
| NEC). AS THIS PROJECT WAS SUBMITTED FOR PERMIT BEFORE |
| THIS DATE, THIS PROJECT IS UNDER THE PREVIOUS CODES AS |
| STATED ABOVE. PLEASE SEE THAT THERE ARE STRUCTURAL |
| DESIGN CHANGES ALSO DONE UNDER THE NEW 2006 REVISIONS |
| TO THE FBC. PLEASE SEE BUILDING REVIEW NOTES FOR DESIGN |
| PRESSURES ETC. (NOTED FOR INFORMATION ONLY) |
| |
| 9) NOTE: PLEASE SEE THE HWH IS BEING SHOWN WITH |
| RECEPTACLE FOR THE CONNECTION OF THIS UNIT WHICH IS NOT |
| PERMITTED. PLAN NEEDS TO SHOW A DISCONNECT/J-BOX IF |
| BREAKER IS GOING TO BE USED TO MEET THE CODE. PLEASE |
| SEE EXCEPTIONS FOR WITHIN SITE. |
| 422.30, 4220.31 |
| |
| 10) NOTE: PLEASE SEE MISSING GFI RECEPTS FOR KITCHEN |
| PENINSULAR PER 210.52C3, 210.8A6 |
| |
| 11) NOTE: PLEASE SEE THE FOLLOWING COMMENT, HOWEVER |
| PLEASE STILL SEE RISER DOES NOT INDICATE ANY MAIN |
| DISCONNECT FOR SERVICE. THE FOLLOWING COMMENT AND HOW |
| PLANS WILL BE SUBMITTED WILL DICTATE WHAT TYPE OF |
| SERVICE AND HOW MUCH WILL CHANGE; HOWEVER IN EITHER |
| CASE MAINS ARE REQUIRED. |
| 230.70, 230.71, 240.4 ETC |
| |
| 12) NOTE: PLEASE SEE AS THIS IS ONE BUILDING; PLEASE |
| SEE 230.2 AS THE PROPOSED SERVICESFOR EACH UNIT ARE |
| NOT GRANTED AS SHOWN ON PLANS. PLEASE REVISE SERVICE |
| RISER DIAGRAM FOR GROUPING OF MAINS INTO ONE SERVICE. |
| PLEASE KNOW IF THESE ARE SUBMITTED AS TRUE |
| TOWNHOUSES/FEE SIMPLE, PROPERTY LINES, SEPARATE PERMIT |
| APPLICATIONS ETC, AND THEN INDIVIDUAL SERVICES TO EACH |
| UNIT MAY BE PERMITTED. THIS WILL CHANGE RISER AS SHOWN |
| OR NOT? |
| PLEASE REVISE RISER DIAGRAM. |
| |
| 13) NOTE: PLEASE SEE RISER AS SHOWN NOW SHOWS AN |
| EQUIPMENT GROUNDING CONDUCTOR FROM THE METER TO THE |
| PANEL. WITHOUT SHOWING MAIN ON RISER IT IS NOT POSSIBLE |
| TO CORRECTLY DETERMINE THE LOCATION OF THE EGC. PLEASE |
| SEE 250.6, 250.24B AS THE EGC IS NOT PERMITTED BEFORE |
| THE FIRST MEANS OF DISCONNECT. |
| |
| 14) NOTE: PLEASE SHOW ALL ROOMS AND AREA DESIGNATIONS |
| ON PLANS. PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. PLEASE |
| SEE THERE ARE SOME ITEMS WHICH CAN NOT BE REVIEWED FOR |
| CODE COMPLIANCE AT THIS TIME DUE TO THIS INFORMATION |
| NOT SHOWN. |
| NEC 408.4, 310.16, 240.4 ETC. |
| FBC 106.1.2, 106.3.5.1.2 ADMIN SECTIONS. |
| |
| 15) NOTE: PLEASE SEE 250.66 FOR SIZING OF THE GROUNDING |
| ELECTRODE CONDUCTOR. DEPENDING ON THE SERVICE AND WHAT |
| THE BUILDING FINALLY COMES DOWN TO AND THE SIZE OF THE |
| SERVICE, THIS WILL DETERMINE THE SIZE OF THE GEC. |
| PLEASE SEE THE 150A METER AS SHOWN INDICATES A 1/0? |
| |
| 16) NOTE: PLEASE KNOW BASED ON SOME OF THE CIRCUITING |
| AT THIS TIME NOT BEING SHOWN; PLEASE BE SURE TO SEE |
| 210.12 FOR AFCI PROTECTED CIRCUITS. THIS APPEARS TO BE |
| ADDRESSED, BUT CAN NOT BE CONFIRMED AT THIS TIME. |
| |
| 17) NOTE: PLEASE SEE MISSING THE REQUIRED GFI FOR SOME |
| CONDENSING UNITS PER 210.63, 210.8A3 (UNIT "A"). |
| |
| 23) NOTE: PLEASE SEE SUBMIT COMPLETE LOAD CALCULATIONS |
| FOR SERVICE. 220.84, 220.12, 220.42, 220.44 ETC. PLEASE |
| KNOW DEPENDING ON THE NEW SERVICE AND LOAD, |
| CONSIDERATION OF 230.2 WILL BE REVIEWED, HOWEVER PLEASE |
| KNOW AT THIS TIME THE SINGLE METER/SERVICE FOR EACH IS |
| OK, HOWEVER IF ONE MAIN AND A METER BANK IS INSTALLED |
| FOR MULTI-FAMILY/CONDO SERVICE, THISH WILL REQUIRE |
| CALCULATIONS FOR SUCH. |
| |
| 24) NOTE:PLEASE SEE 210.52 FOR AREAS FOR REQUIRED |
| RECEPTS WHICH ARE MISSING ON PLANS. PLEASE SEE UNIT |
| "A/B" ETC. |
| PLEASE SEE ONE SET OF PLANS ARE REDLINED FOR LOCATIONS |
| WHICH ARE MISSING DEVICES WITHIN 6FT OF DOOR, 2FT OR |
| MORE OF WALL SPACE AND HALLWAYS AS NOTED. |
| |
| 25) NOTE: PLEASE COMPLETE RISER DIAGRAM WITH ALL |
| FEEDERS TO UNITS AND CORRELATE WITH THE OVER CURRENT |
| PROTECTION DEVICES OF THAT FOR EACH UNIT ONCE RISER IS |
| FINALIZED. |
| 215.5, 310.16, 240.4 ETC. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 26) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING |
| CONDUCTORS FROM MAINS TO EACH UNIT PER 250.122. |
| 250.24B, 250.110, ETC. (WHERE REQUIRED AND |
| APPLICABLE). |
| |
| 27) NOTE: PLEASE SEE THAT THE ADDRESS FOR THIS PROJECT |
| SHALL BE PLACED ON THE TITLE BLOCKS. PLEASE KNOW AT |
| THIS TIME, THIS IS A MULTI-FAMILY SINGLE BUILDING WITH |
| THE ADDRESS OF 1800 EMBASSY DR. PLEASE SEE NOTE FROM |
| ADDRESSING REVIEWER FOR ADDRESS?S ALSO DEPENDING ON HOW |
| THESE ARE BEING PERMITTED AND SUBMITTED. |
| THIS IS NOT AND HAS NOT BEEN SUBMITTED AS TOWNHOUSES, |
| OR CONDO'S. |
| FAC 61G15-23.002, FAC 61G1-16.004 |
| |
| 28) NOTE: PLEASE CLARIFY DINING ROOM/AREA ON PLANS SO |
| THAT ONCE CIRCUITING IS SHOWN COMPLIANCE WITH 210.52B1, |
| 210.11C1 AND 220.52 CAN BE VERIFIED. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |