Plan Review Notes For Permit 06120578 |
Permit Number |
06120578 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-30 07:23:27 | BUILDING PLAN REVIEW | | PERMIT:06120578 | | ADD: 9477 LANTERN BAY CIR | | CONT: PIONEER SCREEN | | TEL: (772)283-9197 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | 1)2004 FL. BLD CODE 1603.1.4 THE | | FOLLOWING INFORMATION RELATED TO WIND | | SHALL BE SHOWN ON THE CONSTRUCTION | | DRAWINGS, | | 1)- BASIC WIND SPEED, MPH | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | CATEGORY | | 3)- WIND EXPOSURE | | 4)- INTERNAL PRESSURE COEFFICIENT, | | 5)- COMPONENTS & CLADDING, THE DESIGN | | WIND PRESSURES IN TERMS OF PSF. | | | | 2)106.1.2 ADDITIONAL DATA. THE | | BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, | | STRESS DIAGRAMS, AND OTHER | | DATA NECESSARY TO DESCRIBE THE | | CONSTRUCTION OR INSTALLATION AND THE | | BASIS OF CALCULATION. ALL DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | REQUIRED BY THE BUILDING OFFICIAL TO BE | | PREPARED BY AN ARCHITECT OR ENGINEER | | SHALL BE AFFIXED WITH THIER OFFICIAL | | SEAL, SIGNATURE AND DATE AS STATE LAW | | REQUIRES. THE DRAWINGS HAS TO BE SIGNED AND SEALED BY | | THE ENGINEER OF RECORD. THE DRAWINGS ARE ALSO MISSING | | SOME DIMENTIONS. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | | | | | | | | | | | | | | | | | |
|