Plan Review Notes For Permit 06120570 |
Permit Number |
06120570 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-04-30 16:00:30 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBEXISTING BUILDING CODE 2004 | | FBC R RESIDENTIAL 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | | | 1.)PROVIDE INFORMATION ABOUT THE EXISTING DOOR. | | PROVIDE A DESCRIPTION: | | | | SIZE OF DOOR | | IS THE EXISTING DOOR GLAZED? | | DIMENSIONS OF GLAZING IN THE EXISTING DOOR | | | | THIS IS THE FIFTH REQUEST FOR INFORMATION IN REGARDS TO | | THE EXISTING DOOR.PLEASE PROVIDE REQUESTED | | INFORMATION. | | | | THE PLAN STATES "CHANGEOUT 1 DOOR OPENING NO SIZE | | CHANGE FIBERGLASS DOOR GLAZED."I UNDERSTAND THAT THE | | OPENING SIZE IS NOT CHANGING.THIS STATEMENT DOES NOT | | ADDRESS MY VERY SPECIFIC QUESTIONS IN REGARDS TO THE | | GLAZING.PROVIDE THE REQUESTED INFORMATION, IS THE | | EXISTING DOOR GLAZED?IF IT IS, PROVIDE DIMENSIONS OF | | THE GLAZING IN THE EXISTING DOOR. | | | | NUMEROUS NOTES REFER TO THE 25% RULE.NOTE THAT THIS | | DOES NOT APPLY ON APPLICATONS AFTER JANUARY,2007. | | | | TO GET THIS PERMIT, YOU MUST EITHER PROVIDE HURRICANE | | SHUTTER INFORMATION OR PROVIDE THE INFORMATION | | REQUESTED SO THAT CODE COMPLIANCE CAN BE DETERMINED. | | |
|