Plan Review Notes
Plan Review Notes For Permit 06120548
Permit Number 06120548
Review Stop B
Sequence Number 2
Notes
Date Text
2007-07-30 16:37:56****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)IT IS ACCEPTABLE TO PROVIDE THE INFORMATION
 REQUIRED IN A FORMAT OTHER THAN THE SUGGESTED
 INSTALLATION SCHEDULE BUT YOU MUST INCLUDE ALL
 INFORMATION.SHUTTER CONNECTION MOUNTING TYPE, ANCHOR
 SPACING, SHUTTER GLASS SEPARATION, DESIGN PRESSURE,
 ETC. ARE MISSING FROM YOUR FORM.SEE ATTACHED
 INSTALLATION SCHEDULE AND PROVIDE ALL INFORMATION AS
 REQUESTED.
  