Date |
Text |
2007-01-02 11:27:09 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1. |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: PLEASE INDICATE ON THE RESUBMITTED DRAWINGS THAT |
| THE 100' INDICATED IS THE TOTAL DEVELOPED LENGTH FROM |
| THE METER TO THE POOL HEATER. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: PLEASE INDICATE THE ABOVE GROUND PIPING MATERIAL |
| BEING USED, THE ONLY MATERIAL INDICATED ON DRAWINGS |
| BEING USED IS PE. PLEASE CORRECT THIS ON THE |
| RESUBMITTAL. |
| |
| 3. TYPE OF GAS, (LP OR NATURAL) MUST BE INDICATED ON |
| THE RESUBMITTED DRAWINGS. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| NOTE: PLEASE INDICATE ON THE RESUBMITED DRAWINGS THE |
| EXISTING HOUSE BTU LOAD TO VERIFY WETHER THE MP |
| REGULATOR SPECIFIED IS COMPLIANT. |
| |
| 5. THE MP REGULATOR SPECIFIED FOR THE POOL HEATER IS |
| WRONG. PLEASE REFERENCE THE ATTACHED MAXITROL |
| SPECIFICATION SHEET FOR THE RESUBMITTAL. THE MAXIMUM |
| INDIVIDUAL LOAD FOR A MAXITROL-5AL IS 300,000 BTU'S THE |
| INDICATED POOL HEATER IS 399,000 BTU'S. THE CORRECT MP |
| REGULATOR SHOULD BE A MAXITROL 325-7L. PLEASE CORRECT |
| THIS ON THE RESUBMITTAL. |
| |
| 6. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |