Plan Review Notes For Permit 06120545 |
Permit Number |
06120545 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-01-11 13:50:37 | DENIED BY BUILDING | | | | 1) THE ENGINEERS CALCULATIONS ARE BASED ON PAGE 28 OF | | NOA 03-0501.02 FOR AN ASSEMBLY WITH A DESIGN PRESSURE | | OF -45 PSF. THE PRDUCT APPROVAL THAT WAS SUBMITTED IS | | NOA 02-0212.07 AND THE ASSEMBLY IS ON PAGE 17 THERE ARE | | TWO DESIGN PRESSURES BASED ON FASTENING OF THE ANCHOR | | SHEET ONE IS -52.5 PSF AND THE OTHER IS -60 PSF. | | (PLEASE INDICATE THE ONE THAT WILL BE USED). THE | | ENGINEERING AND PRODUCT APPROVAL MUST CORRESPOND. | | | | 2) THE ENGINEER SPECIFIES THE BASE SHEET TO BE FASTENED | | WITH 2 ROWS AT 6" OC AT THE LAP IN THE CORNER AREAS. | | EXPLAIN HOW THIS IS TO BE ACCOMPLISHED IF THE LAP IS 4" | | AND RAS 117 SPECIFIES THAT THE MINIMUM FASTENER | | SEPARATION SHALL NOT BE LESS THAN 4" OC. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|