Plan Review Notes
Plan Review Notes For Permit 06120545
Permit Number 06120545
Review Stop B
Sequence Number 1
Notes
Date Text
2006-12-20 10:51:41DENIED BY BUILDING
  
 1) SPECIFY THE FASTENING OPTION THAT WILL BE USED TO
 INSTALL THE ROOFING SYSTEM. CIRCLE THE APPROPRIATE ONE
 ON THE PRODUCT APPROVAL.
  
 2) NEITHER OF THE TWO FASTENING OPTIONS LISTED ON PAGE
 17 OF THE PRODUCT APPROVAL HAVE SUFFICENT PRESSURES FOR
 ALL ROOF ZONES. LIMITATION 7 ON PAGE 20 ALLOWS ENHANCED
 FASTENING WITH SIGNED AND SEALED RAS 117 CALCULATIONS
 FROM A FLORIDA REGISTERED ENGINEER, ARCHITECT OR ROOF
 CONSULTANT. SUBMIT SIGNED AND SEALED CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  