Plan Review Notes
Plan Review Notes For Permit 06120513
Permit Number 06120513
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-19 09:12:47 
  
 PROVISO
  
 THIS PERMIT IS BEING ISSUED TO
 FACILITATE THE REPAIR OF THIS PROPERTY.
 THE PLANS HOWEVER ARE INCOMPLETE. PLEASE
 RESUBMIT A REVISION SHOWING ACTUAL
 CONDITIONS PRIOR TO CALLING ROUGH
 ELECTRICAL INSPECTION.
 THE REVIEWED PLAN MUST BE ON THE JOB
 SITE AT TIME OF INSPECTION. ALLOW AT
 LEAST ONE WEEK (PER TRADE) FOR PLAN
 REVIEW.
  
 1}PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, 215.5
  
 2}PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718