2007-01-03 15:46:20** UNSAT 2ND REVIEW
  
 PERMIT # 06120507 TEMPORARY ELECTRICAL SERVICE.
  
 ** PLEASE SEE AS THE RISE HAS BEEN REVISED IN MANY
 ASPECTS, PLEASE SEE SOME COMMENTS ARE NEW AND SOME ARE
 FROM THE PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SEE 240.21C FOR TAPED CONDUCTORS FROM
 THE TRAILER COMPOUND GUTTER TO THE PANEL. PLEASE SEE
 THE CONDUCTOR SIZES ARE SHOWN AS #8'S TO A 100AMP MAIN
 CIRCUIT BREAKER. PLEASE KNOW THESE ARE NOT BEING SHOWN
 AS ALUMINUM OR COPPER; HOWEVER IN EITHER CASE IF
 ALUMINUM THEY ARE ONLY RATED AT 40AMPS, IF COPPER THEY
 ARE ONLY RATED AT 50AMPS.
 PLEASE SEE 110.4, 240.21C, 240.4 AND 310.16.
  
 2) NOTE: PLEASE SEE THE FEEDER NOTATION #7 WHICH IS
 MISSING WHAT IS EITHER A PHASE CONDUCTOR OR A NEUTRAL
 CONDUCTOR FOR THIS SEPARATELY DERIVED SYSTEM. PLEASE
 SEE THAT ALL EQUIPMENT ON THE SECONDARY SIDE OF THIS
 TRANSFORMER REQUIRES A NEUTRAL.
 PLEASE SEE 250.24B, 250.30, 250.20 ETC.
  
 3) NOTE: PLEASE SEE RISER IS MISSING THE CONDUCTORS ON
 THE SECONDARY SIDE OF THE MAIN DISCONNECT GOING INTO
 GUTTER AT TRAILER COMPOUND.
 RISER SHOWS THIS TO BE 3-PHASE, YET ONLY 3-PHASE
 UN-GROUNDED CONDUCTORS AND AN EQUIPMENT GROUNDING
 CONDUCTOR IS BEING SHOWN.
  
 4) NOTE: PLEASE SEE THE CONDUCTORS ON THE PRIMARY SIDE
 OF THE TRANSFORMER WHICH IS SHOWN AS FEEDER NOTE #5
 WHICH IS MISSING A HOT/PHASE CONDUCTOR.
 THIS IS BEING SHOWN AS A THREE PHASE SERVICE.120/208V
 3-PHASE FROM THE 277/480V THREE PHASE TRANSFORMER.
  
 5) NOTE: PLEASE SEE THE MAIN GROUNDING ELECTRODE
 CONDUCTOR SHALL BE SIZED PER 250.66 AS NOTED. PLEASE
 SEE A 3/0 MIN IS REQUIRED.
 PLEASE ALSO SEE 250.64C AND NOTE HOW ALL PF THESE
 GROUNDING ELECTRODE ARE GOING TO BE CONNECTED.
  
 6) NOTE: PLEASE INDICATE THE LOAD ON THE SECONDARY SIDE
 OF THE TRANSFORMER AND MAIN FEEDING THE GUTTER. BASED
 ON THE LOAD SHOWN ON EACH PANEL SUBMITTED FOR THE
 TRAILERS AND THE PANEL ON THE RISER WHICH SHOWS 43
 AMPS, PLEASE SEE THAT THE LOAD IS BEING SHOWN AT
 334AMPS AND THE OVER CURRENT PROTECTION IS 300AMPS. IF
 THERE IS LOAD CALCULATIONS WHICH INDICATE A LESSER
 LOAD, PLEASE SUBMIT OR ADJUST THE OVER CURRENT
 PROTECTION.
 PLEASE SEE 220, 240, 310.16, 240.4 ETC
  
 7) NOTE: PLEASE SEE THAT THE CONDUITS WHICH ARE
 REQUIRED TO SLEEVE THE DIRECT BURIAL CABLE IS TO BE
 PLACED A MIN OF 24" BELOW THE GRADE, WHERE RISER IN
 SOME PLACES SHOWS THE CONDUIT TERMINATING ABOVE
 GRADE.300 THIS CAN BE REDLINED, AS THESE WILL BE FUTURE
 FOR THE ONES AS SHOWN ON RISER AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved