2007-01-03 15:46:20 | ** UNSAT 2ND REVIEW |
| |
| PERMIT # 06120507 TEMPORARY ELECTRICAL SERVICE. |
| |
| ** PLEASE SEE AS THE RISE HAS BEEN REVISED IN MANY |
| ASPECTS, PLEASE SEE SOME COMMENTS ARE NEW AND SOME ARE |
| FROM THE PREVIOUS REVIEW. |
| |
| 1) NOTE: PLEASE SEE 240.21C FOR TAPED CONDUCTORS FROM |
| THE TRAILER COMPOUND GUTTER TO THE PANEL. PLEASE SEE |
| THE CONDUCTOR SIZES ARE SHOWN AS #8'S TO A 100AMP MAIN |
| CIRCUIT BREAKER. PLEASE KNOW THESE ARE NOT BEING SHOWN |
| AS ALUMINUM OR COPPER; HOWEVER IN EITHER CASE IF |
| ALUMINUM THEY ARE ONLY RATED AT 40AMPS, IF COPPER THEY |
| ARE ONLY RATED AT 50AMPS. |
| PLEASE SEE 110.4, 240.21C, 240.4 AND 310.16. |
| |
| 2) NOTE: PLEASE SEE THE FEEDER NOTATION #7 WHICH IS |
| MISSING WHAT IS EITHER A PHASE CONDUCTOR OR A NEUTRAL |
| CONDUCTOR FOR THIS SEPARATELY DERIVED SYSTEM. PLEASE |
| SEE THAT ALL EQUIPMENT ON THE SECONDARY SIDE OF THIS |
| TRANSFORMER REQUIRES A NEUTRAL. |
| PLEASE SEE 250.24B, 250.30, 250.20 ETC. |
| |
| 3) NOTE: PLEASE SEE RISER IS MISSING THE CONDUCTORS ON |
| THE SECONDARY SIDE OF THE MAIN DISCONNECT GOING INTO |
| GUTTER AT TRAILER COMPOUND. |
| RISER SHOWS THIS TO BE 3-PHASE, YET ONLY 3-PHASE |
| UN-GROUNDED CONDUCTORS AND AN EQUIPMENT GROUNDING |
| CONDUCTOR IS BEING SHOWN. |
| |
| 4) NOTE: PLEASE SEE THE CONDUCTORS ON THE PRIMARY SIDE |
| OF THE TRANSFORMER WHICH IS SHOWN AS FEEDER NOTE #5 |
| WHICH IS MISSING A HOT/PHASE CONDUCTOR. |
| THIS IS BEING SHOWN AS A THREE PHASE SERVICE.120/208V |
| 3-PHASE FROM THE 277/480V THREE PHASE TRANSFORMER. |
| |
| 5) NOTE: PLEASE SEE THE MAIN GROUNDING ELECTRODE |
| CONDUCTOR SHALL BE SIZED PER 250.66 AS NOTED. PLEASE |
| SEE A 3/0 MIN IS REQUIRED. |
| PLEASE ALSO SEE 250.64C AND NOTE HOW ALL PF THESE |
| GROUNDING ELECTRODE ARE GOING TO BE CONNECTED. |
| |
| 6) NOTE: PLEASE INDICATE THE LOAD ON THE SECONDARY SIDE |
| OF THE TRANSFORMER AND MAIN FEEDING THE GUTTER. BASED |
| ON THE LOAD SHOWN ON EACH PANEL SUBMITTED FOR THE |
| TRAILERS AND THE PANEL ON THE RISER WHICH SHOWS 43 |
| AMPS, PLEASE SEE THAT THE LOAD IS BEING SHOWN AT |
| 334AMPS AND THE OVER CURRENT PROTECTION IS 300AMPS. IF |
| THERE IS LOAD CALCULATIONS WHICH INDICATE A LESSER |
| LOAD, PLEASE SUBMIT OR ADJUST THE OVER CURRENT |
| PROTECTION. |
| PLEASE SEE 220, 240, 310.16, 240.4 ETC |
| |
| 7) NOTE: PLEASE SEE THAT THE CONDUITS WHICH ARE |
| REQUIRED TO SLEEVE THE DIRECT BURIAL CABLE IS TO BE |
| PLACED A MIN OF 24" BELOW THE GRADE, WHERE RISER IN |
| SOME PLACES SHOWS THE CONDUIT TERMINATING ABOVE |
| GRADE.300 THIS CAN BE REDLINED, AS THESE WILL BE FUTURE |
| FOR THE ONES AS SHOWN ON RISER AT THIS TIME. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |