Plan Review Notes
Plan Review Notes For Permit 06120507
Permit Number 06120507
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-21 18:31:08** UNSAT **
  
  
 ** PLEASE SEE PLANS ARE BEING ROUTED TO PLUMBING FOR
 REVIEW AS ELECTRICAL AND PLUMBING WERE SUBMITTED
 TOGETHER. CALLED CATALFUMO REP TO LET THEM KNOW
 ELECTRICAL COMMENTS WERE ONLINE.
  
 1) NOTE: PLEASE SEE 240.21C AS TAPPED CONDUCTORS ON THE
 SECONDARY SIDE OF THE TRANSFORMERS SHALL TERMINATE IN A
 SINGLE MEANS OF OVER CURRENT PROTECTION.
 PLEASE SEE ALL TAPS GOING INTO GUTTERS AS SHOWN ARE NOT
 PERMITTED.
  
 2) NOTE: PLEASE INDICATE TWO GROUND RODS ON THE
 SECONDARY SIDE OF ALL TRANSFORMER FOR THE SD SYSTEM PER
 250.20, 250.30, 250.56
  
 3) NOTE: PLEASE SEE MISSING COLD WATER AS PART OF THE
 GROUNDING ELECTRODE SYSTEM.
 250.50
  
 4) NOTE: PLEASE PROVIDE INFORMATION ON TYPE OF DB CABLE
 BEING INSTALLED.
 PLEASE SEE 590.4
 CONDUCTORS SHALL BE PERMITTED WITHIN CABLE ASSEMBLIES
 OR WITHIN MULTI-CONDUCTOR CORDS OR CABLES OF A TYPE
 IDENTIFIED IN TABLE 400.4 FOR HARD USAGE OR EXTRA-HARD
 USAGE.
 PLEASE ALSO SEE SECTION WHICH SPEAKS OF CABLE.
  
 5) NOTE: PLEASE SEE LOAD CALCULATIONS FOR MAIN 4 OF 5
 ARE NOT COMPLETE. PLEASE THERE IS A PANEL WHICH FEEDS
 LIGHTING, CRANE LIGHTS ETC WHICH IS NOT FIGURED OR
 SHOWN. PLEASE ALSO SEE PREVIOUS COMMENTS WITH RESPECT
 TO TAPS.
  
 6) NOTE: PLEASE SEE NO HAND DRAWN CHANGES MAY BE DONE
 TO PLANS WHICH ARE SIGNED, DATED AND SEALED BY AN
 ENGINEER.
 FS 471.025
  
 7) NOTE: PLEASE SEE POWER AS SHOWN WHICH WILL BE ON THE
 SECONDARY SIDES OF THE CITY HALL, LIBRARY AND GARAGE
 TRANSFORMER IS BEING SHOWN FOR FUTURE PANELS ETC,
 HOWEVER NO MEANS OF DISCONNECT AND OCP IS BEING SHOWN
 ON THE SECONDARY SIDE.
 PLEASE TERMINATE IN A SINGLE MEANS OF OCP WHICH LIMITS
 THE OCP ON THE CONDUCTORS, TRANSFORMER ETC.
 PLEASE SEE 240.21C ETC
  
 8) NOTE: PLEASE SEE 250.66 FOR SIZING OF THE GROUNDING
 ELECTRODE CONDUCTOR(S) ON THE TRANSFORMER. MOST ARE
 OK.
  
 9) NOTE: PLEASE SEE 450.3B FOR THE MAX OCP ON THE
 PRIMARY SIDE OF TRANSFORMERS. PLEASE SEE TRANS #1 AS
 THE OCP IS TOO HIGH. ( OR ) PLEASE SEE EXCEPTIONS AND
 PROVIDE INFORMATION ON THE TYPE OF UNIT BEING
 INSTALLED.
  
 10) NOTE: PLEASE PROVIDE A LAYOUT/SITE PLANS WHICH
 INDICATES THE LOCATIONS OF ALL SERVICE EQUIPMENT BEING
 INSTALLED AND PROPOSED.
 FBC 106.1.2 ADMIN SECTION
  
 11) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK FOR THE SERVICE AS SHOWN AND BEING PROPOSED SHALL
 INCLUDE ALL LABOR AND MATERIALS, EVEN IF MATERIALS WERE
 OWNER SUPPLIED. PLEASE KNOW IF NOT ADJUSTED FOR VALUE,
 ONE WILL BE ADJUSTED USING MARSHALL?S AND SWIFT GUIDE
 AS ADOPTED PER THE FBC 108.3 ADMIN SECTION.
  
 12) NOTE: PLEASE SUPPLY INFORMATION ON TRAILERS BEING
 INSTALLED FOR LOADS. THE LOAD AS SHOWN ON RISER CAN NOT
 BE VERIFIED AS THE TRAILERS THEMSELVES ARE NOT
 PERMITTED.
 220, 215.5, ETC
  
 13) NOTE: PLEASE INDICATE CONTINUOUS LOADS AT 125%.
 PLEASE SEE LOAD AS SHOWN IS EXACTLY AT THE RATING OF
 THE SEC?S WHICH ARE BEING INSTALLED. PLEASE AS
 CONTINUOUS LOADS AND OTHER FACTORS HAVE NOT BEEN TAKEN
 OR SHOWN INTO CONSIDERATION THE SIZE OF THE SEC?S DO
 NOT SUPPLY ANY ROOM FOR ANY FUTURE LOADS.?
 215.3, 230.42 , 310.16, 240.4, ETC
  
 14) NOTE:PLEASE SEE RISER SEEMS TO IDENTIFY A
 "GROUND" "G" FROM FPL TO GUTTER AND FROM GUTTER TO ALL
 FIRST MEANS OF DISCONNECTS? PLEASE SEE THIS IS THE SAME
 SYMBOL BEING USED ON ALL OTHER LOCATIONS FOR GROUNDS
 ALSO. PLEASE CLARIFY AS THIS SHOULD BE SHOWN AS THE
 NEUTRAL OR "GROUNDED" CONDUCTOR AS THERE ARE NO
 EQUIPMENT GROUNDING CONDUCTORS BEFORE THE FIRST MEANS
 OF DISCONNECT. 250.6, 250.24B.
 PLEASE PROVIDE COMPLETE NEUTRAL LOAD CALCULATIONS AS
 THE NEUTRAL CONDUCTOR(S) FOR THE SERVICE ENTRANCE
 CONDUCTORS AND FEEDERS ARE SUBSTANTIALLY DECREASED.
 PLEASE INDICATE HOW AND WHERE THE LOAD FOR THE NEUTRAL
 WAS DERIVED AND SHOW ON PLANS IN ORDER TO VERIFY THE
 CORRECT SIZING OF THE CONDUCTORS AS SHOWN.
  
 15) NOTE: PLEASE SEE LABELING OF MAINS SHALL BE AS
 FOLLOWS, 1 OF 5, 2 OF 5 ETC.
 PLEASE SEE RISER NOW SHOWS WHAT APPEARS TO BE A
 MISPRINT OF 105,205,305, ETC
  
 16) NOTE: PLEASE SEE BASED ON THE NUMBER OF CONDUCTORS
 BEING SHOWN ON THE SECONDARY SIDE OF THE TRANSFORMER TO
 GUTTER THESE ARE ONLY SINGLE PHASE BEING BROUGHT TO
 GUTTERS???
 PLEASE SEE PANEL FROM GUTTER WHICH INDICATES A THREE
 PHASE FEED??
 PLEASE KNOW AS THIS TIME THE RISER IS VERY CONFUSING AS
 THREE PHASES ARE BEING BROUGHT TO TRANSFORMERS AND ONLY
 SINGLE PHASE BEING BROUGHT OUT?
 THERE ARE TOO MANY CODE SECTIONS TO PLACE FOR THIS
 NOTE, PLEASE SEE NEC 2005.
  
 17) NOTE: PLEASE SEE THE MINIMUM SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR SHALL BE SIZED PER 250.66.
  
 ** PLEASE KNOW AS THERE ARE ITEMS ON RISER WHICH WILL
 BE CHANGING, THERE MAY BE COMMENTS ON FUTURE ELECTRICAL
 RISER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717