Plan Review Notes
Plan Review Notes For Permit 06120498
Permit Number 06120498
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-01 15:49:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PLAN SPECIFIES HUGHES CONNECTORS.THEY HAVE BEEN
 OUT OF BUSINESS FOR MANY YEARS.SPECIFY AN AVAILABLE
 CONNECTOR.
  
 2.)PLANS ARE NOT CLEAR.THE BOX APPEARS TO BE
 OPEN,BUTDESIGN CRITERIA GIVES AN INTERNAL PRESSURE
 COEFFICIENT OF .18 WHICH IS FOR ENCLOSED BUILDINGS.
 NOTE THE TYPE OF SIDING, OR REVISE CRITERIA.
  