2007-03-08 14:20:11 | ** UNSAT 2ND REVIEW ** |
| |
| 1) NOTE: PLEASE SEE THE HEAT FOR THE A/C IS NOW BEING |
| SHOWN AT 7.5KW AND OVER CURRENT PROTECTION IS STILL |
| BEING SHOWN AT 60AMPS? PLEASE KNOW THE 60A OCP WOULD BE |
| FOR THE 10KW UNIT BUT TOO HIGH FOR THE 7.5 UNIT. |
| PLEASE SEE MECHANICAL PLANS DO NOT INDICATE HEAT FOR |
| EITHER? |
| |
| 2) NOTE: PLEASE SEE THE DISHWASHER/DISPOSAL ARE BOTH |
| NOW SHOWN ON THE SAME DEVICE/YOKE, HOWEVER PANEL |
| SCHEDULE SHOWS BOTH OF THESE ON SINGLE POLE CIRCUITS. |
| PLEASE SHOW ON A 2-POLE CIRCUIT BREAKER AS REQUIRED PER |
| 210.4. |
| |
| 3) NOTE: PLEASE SEE PANEL SCHEDULE NOW SHOWS A |
| DEDICATED DINING CIRCUIT HOWEVER LOADS AS REQUIRED PER |
| 210.52B1, 210.11C1 AND 220.52A ARE NOT SHOWN OR FIGURED |
| INTO THE LOAD CALCULATIONS. |
| PLEASE INCLUDE. |
| |
| 4) NOTE: PLEASE SEE CONDUIT SIZE FOR FEEDERS FROM MAIN |
| IS TOO SMALL BASED ON THE CONDUCTORS AS SHOWN ALONG |
| WITH THE PIPE SIZE AS SHOWN. |
| PLEASE SEE TABLE IN CHAPTER 9. |
| PLEASE SEE THE NEXT COMMENT AS THIS MAY AFFECT RISER AS |
| SUBMITTED. |
| |
| 5) NOTE: PLEASE CLARIFY RISER: |
| PLEASE SEE RISER SHOWS A MAIN OUTSIDE WHICH IS OK, |
| HOWEVER NO SIZE FOR THIS MAIN CAN BE FOUND ON RISER. |
| PLEASE SEE THAT DUE TO THE SIZE OF THE CONDUCTORS BEING |
| RATED FOR 200AMPS, IT SEEMS THAT PERHAPS THE MAIN |
| DISCONNECT OUTSIDE IS 200AMPS. PLEASE SEE IF THIS IS |
| THE CASE; IT IS FEEDING A 150A RATED PANEL WHICH IS NOT |
| PERMIT. |
| PLEASE SEE RISER SHOWS PANEL AS 150AMP AND CONTAINING A |
| MAIN CIRCUIT BREAKER (MCB), YET THE PANEL SCHEDULE |
| STILL SHOWS THIS AS A MAIN LUG ONLY PANEL (MLO). |
| PLEASE CORRELATE AND INDICATE HOW AND WHAT SIZE THIS |
| SERVICE IS. |
| |
| 6) NOTE: PLEASE SEE THAT THE SMOKE ALARM IN HALL |
| OUTSIDE BEDROOMS AND BATH ROOM IS SHOWN TOO CLOSE TO |
| THE BATHROOM DOOR PER NFPA-72 11.8.3 |
| REQUIRED TO BE A MINIMUM OF 3FT FROM BATH DOOR. |
| ** PLEASE KNOW THIS CAN AND WOULD HAVE BEEN REDLINED; |
| HOWEVER PLANS WERE COMING BACK FOR OTHER COMMENTS. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |