Plan Review Notes
Plan Review Notes For Permit 06120460
Permit Number 06120460
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-08 14:20:11** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE SEE THE HEAT FOR THE A/C IS NOW BEING
 SHOWN AT 7.5KW AND OVER CURRENT PROTECTION IS STILL
 BEING SHOWN AT 60AMPS? PLEASE KNOW THE 60A OCP WOULD BE
 FOR THE 10KW UNIT BUT TOO HIGH FOR THE 7.5 UNIT.
 PLEASE SEE MECHANICAL PLANS DO NOT INDICATE HEAT FOR
 EITHER?
  
 2) NOTE: PLEASE SEE THE DISHWASHER/DISPOSAL ARE BOTH
 NOW SHOWN ON THE SAME DEVICE/YOKE, HOWEVER PANEL
 SCHEDULE SHOWS BOTH OF THESE ON SINGLE POLE CIRCUITS.
 PLEASE SHOW ON A 2-POLE CIRCUIT BREAKER AS REQUIRED PER
 210.4.
  
 3) NOTE: PLEASE SEE PANEL SCHEDULE NOW SHOWS A
 DEDICATED DINING CIRCUIT HOWEVER LOADS AS REQUIRED PER
 210.52B1, 210.11C1 AND 220.52A ARE NOT SHOWN OR FIGURED
 INTO THE LOAD CALCULATIONS.
 PLEASE INCLUDE.
  
 4) NOTE: PLEASE SEE CONDUIT SIZE FOR FEEDERS FROM MAIN
 IS TOO SMALL BASED ON THE CONDUCTORS AS SHOWN ALONG
 WITH THE PIPE SIZE AS SHOWN.
 PLEASE SEE TABLE IN CHAPTER 9.
 PLEASE SEE THE NEXT COMMENT AS THIS MAY AFFECT RISER AS
 SUBMITTED.
  
 5) NOTE: PLEASE CLARIFY RISER:
 PLEASE SEE RISER SHOWS A MAIN OUTSIDE WHICH IS OK,
 HOWEVER NO SIZE FOR THIS MAIN CAN BE FOUND ON RISER.
 PLEASE SEE THAT DUE TO THE SIZE OF THE CONDUCTORS BEING
 RATED FOR 200AMPS, IT SEEMS THAT PERHAPS THE MAIN
 DISCONNECT OUTSIDE IS 200AMPS. PLEASE SEE IF THIS IS
 THE CASE; IT IS FEEDING A 150A RATED PANEL WHICH IS NOT
 PERMIT.
 PLEASE SEE RISER SHOWS PANEL AS 150AMP AND CONTAINING A
 MAIN CIRCUIT BREAKER (MCB), YET THE PANEL SCHEDULE
 STILL SHOWS THIS AS A MAIN LUG ONLY PANEL (MLO).
 PLEASE CORRELATE AND INDICATE HOW AND WHAT SIZE THIS
 SERVICE IS.
  
 6) NOTE: PLEASE SEE THAT THE SMOKE ALARM IN HALL
 OUTSIDE BEDROOMS AND BATH ROOM IS SHOWN TOO CLOSE TO
 THE BATHROOM DOOR PER NFPA-72 11.8.3
 REQUIRED TO BE A MINIMUM OF 3FT FROM BATH DOOR.
 ** PLEASE KNOW THIS CAN AND WOULD HAVE BEEN REDLINED;
 HOWEVER PLANS WERE COMING BACK FOR OTHER COMMENTS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]