Plan Review Notes
Plan Review Notes For Permit 06120460
Permit Number 06120460
Review Stop M
Sequence Number 1
Notes
Date Text
2007-01-02 09:00:02*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) PLEASE SUBMIT TWO COPY'S OF THE ENERGY CALCULATIONS
 AND MANUAL J CAL'S.
  
 3) PLEASE SHOW LOCATION OF CLOTHES DRYER VENT
 TERMINATION ON MECHANICAL PLANS, INFORMATIONAL VENT MAY
 NOT DISCHARGE NEAR THE A/C CONDENSER UNIT, PER 2004
 FBC/M 501.2 .
  
 4) DOOR TO LAUNDRY ROOM NEEDS TO BE LOUVERED OR A GRILL
 NEEDS TO BE INSTALLED FOR RETURN AIR, PLEASE SHOW ON
 MECHANICAL PLANS.
  
 5) RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS TO BE
 LARGER THAN 12". BALANCED RETURN AIR MAY BE ACHIEVED
 BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.