Plan Review Notes
Plan Review Notes For Permit 06120460
Permit Number 06120460
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-28 18:43:53 
 ** UNSAT **
  
  
 ** PLEASE KNOW ANY REFERENCES TO THE FBC CHAPTER 1 IN
 THE FOLLOWING NOTES THE ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE COMPLETE PANEL SCHEDULE WHICH WILL
 PROVIDE DESIGNATIONS TO ROOM/AREAS AT A MINIMUM. IE:
 BEDRM #1, LIVING RM LTS, ETC.
 408.4, 310.16
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS AS THIS PERMIT APPLICATION HAS BEEN MADE UNDER
 THE NEW 2005 NEC.
 THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON
 ELECTRICAL SHEETS.
 2005 NFPA-2005 (SHOWN)
 2002 NFPA-72
 PLANS MAY NOT REFERENCE LATEST EDITION AS THE STATE OF
 FLORIDA ONLY JUST ADOPTED THE NEW REVISIONS TO THE 2004
 FBC AND THE 2005 NECAS OF 12/8/06
  
 3) NOTE:PLEASE SEE MISSING WHAT APPEARS TO BE A
 COUNTER TOP GFI RECEPT ABOVE THE AREA WHERE THE
 DISHWASHER IS LOCATED.
 PLEASE SEE 210.52C1
  
 4) NOTE: PLEASE SEE FBC 2004 13-606.1.ABC.1.2.4 WHICH
 REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED.
 PLEASE NOTE ON PLANS ACCORDINGLY.
  
 5) NOTE: PLEASE VERIFY CONDUIT TYPE AND CONDUIT FILL ON
 THE 1 1/2 INCH CONDUIT WITH THE CONDUCTORS AS SHOWN.
 PLEASE SEE THE ONE CONDUIT IS MISSING THE EQUIPMENT
 GROUNDING CONDUCTOR AS NOTED IN NOTE #10 BELOW. PLEASE
 SEE IF THIS IS PVC AND SOME PART WILL BE SCHEDULE 80,
 ALL SHALL BE FIGURED ON SCHEDULE 80 CONDUIT.
 SEE TABLE IN CHAPTER 9
  
 6) NOTE: PLEASE SEE THAT THE PLANS SHALL BARE THE
 PRINTED NAME, DATE AND SIGNATURE OF THE PERSON TAKING
 RESPONSIBILITY OF THE PLANS. PLEASE SEE ONLY THE
 PRINTED NAME IS BEING SHOWN.
 FBC 106.1.2, FS 481.221, 471.025
  
 7) NOTE: PLEASE SEE WATER HEATER IS BEING SHOWN AS
 HAVING A RECEPT FOR THE CONNECTION. PLEASE SEE 422.31,
 422.32 AS THIS SHALL BE A HARDWIRED UNIT WITH OR
 WITHOUT A DISCONNECT DEPENDING ON THE LOCATION OF PANEL
 ETC.
  
 8) NOTE: PLEASE SEE 210.8A1, AS THE RECEPT(S) LOCATED
 WITHIN THE BATHROOM AREAS AND WITHIN 3FT OF THE SINK
 SHALL BE GFI ALSO. PLEASE SHOW.
  
 9) NOTE: PLEASE SEE 210.8A6 AS ALL THE KITCHEN COUNTER
 SPACE RECEPTS SHALL BE SHOWN AS GFI.
  
 10) NOTE: PLEASE SEE RISER AS THE EQUIPMENT GROUNDING
 CONDUCTOR IS MISSING FROM THE MAIN TO THE SUB PANEL.
 250.24B, 250.110, 250.122
  
 10) NOTE: PLEASE CORRELATE SERVICE, PLEASE SEE PANEL
 SCHEDULE IS SHOWN AS 150AMPS YET THE RISER SHOWS THIS
 AS 200AMP WITH A MAIN CIRCUIT BREAKER.
 PLEASE ALSO SEE THE RISER MENTIONS PANEL IN GARAGE, YET
 THE PANEL ON PLANS APPEAR TO BE IN A LAUNDRY ROOM AND
 THERE IS NO GARAGE.
 PLEASE ADJUST AND CORRELATE PLANS.
 106.1.2, 106.3.5.4, FBC ADMIN SECT
  
 11) NOTE: PLEASE CORRELATE A/C LOADS. PLEASE SEE PANEL
 SCHEDULE SHOWS 7.5KW AND 10KW. WHICH ONE?
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE 210.52 FOR SEVERAL MISSING
 REQUIRED RECEPTACLE FOR WALL SPACES 2FT OR MORE. PLEASE
 SEE COMMENT #15, AS THEY MAY BE OK, IF THE INTENTION IS
 FOR THESE TO BE 1/2 SWITCHED.
  
 13) NOTE: PLEASE CORRELATE LOAD ON IRRIGATION PUMP ON
 PANEL SCHEDULE WITH THAT OF THE LOAD SHOWN ON LOAD
 CALCULATIONS.
 PLEASE ALSO SEE THE CIRCUIT IS BEING SHOWN ON A 1-POLE
 30A CIRCUIT?
  
 14) NOTE:PLEASE CLARIFY IF THE LOAD ON THE POOL PUMP
 IS SHOWN AT THE CONTINUOUS DUTY AS ON LOAD CALCULATIONS
 OR PLEASE SHOW AT 125%.ALSO SHOWN ON A 120V 1-POLE
 30A CIRCUIT?
 215.3, 230.42
  
 15) NOTE: PLEASE SEE 210.70 AND LS 101 7.8, PLEASE SEE
 THE PLANS AS THERE ARE MANY ANY WHICH WILL BE REQUIRED
 TO CONTAIN A LIGHT FIXTURE OF SOME KIND BEFORE FINAL OR
 OTHER EXCEPTION FOR SWITCHED RECEPT ETC.
 PLEASE SEE THE NEW ROOM SHALL CONTAIN A METHOD OF
 CONTROLLING LIGHTING FOR INGRESS INTO THE NEW ROOM FROM
 THE OUTSIDE. PLEASE SEE THIS CAN BE DONE WITH A 3-WAY
 OR OTHER OPTION.
 210.70 , LS 101 7.8
 PLEASE SEE SEVERAL AREAS WHICH INDICATE THE ENTIRE
 RECEPT BEING SWITCHED. PLEASE KNOW THIS IS OK, HOWEVER
 IF SWITCHING THE ENTIRE RECEPT, THEN AN ADDITIONAL
 RECEPT WILL BE REQUIRED PER 210.52. IF ONLY SWITCHING
 HALF, PLEASE ADJUST SYMBOL.
 PLEASE ADJUST PLANS AS NEEDED.
  
  
 16) NOTE: * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved