Date |
Text |
2006-12-28 18:43:53 | |
| ** UNSAT ** |
| |
| |
| ** PLEASE KNOW ANY REFERENCES TO THE FBC CHAPTER 1 IN |
| THE FOLLOWING NOTES THE ADMINISTRATIVE SECTION AS |
| ADOPTED BY THE CITY OF WEST PALM BEACH. |
| |
| 1) NOTE: PLEASE COMPLETE PANEL SCHEDULE WHICH WILL |
| PROVIDE DESIGNATIONS TO ROOM/AREAS AT A MINIMUM. IE: |
| BEDRM #1, LIVING RM LTS, ETC. |
| 408.4, 310.16 |
| |
| 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| ON PLANS AS THIS PERMIT APPLICATION HAS BEEN MADE UNDER |
| THE NEW 2005 NEC. |
| THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON |
| ELECTRICAL SHEETS. |
| 2005 NFPA-2005 (SHOWN) |
| 2002 NFPA-72 |
| PLANS MAY NOT REFERENCE LATEST EDITION AS THE STATE OF |
| FLORIDA ONLY JUST ADOPTED THE NEW REVISIONS TO THE 2004 |
| FBC AND THE 2005 NECAS OF 12/8/06 |
| |
| 3) NOTE:PLEASE SEE MISSING WHAT APPEARS TO BE A |
| COUNTER TOP GFI RECEPT ABOVE THE AREA WHERE THE |
| DISHWASHER IS LOCATED. |
| PLEASE SEE 210.52C1 |
| |
| 4) NOTE: PLEASE SEE FBC 2004 13-606.1.ABC.1.2.4 WHICH |
| REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED. |
| PLEASE NOTE ON PLANS ACCORDINGLY. |
| |
| 5) NOTE: PLEASE VERIFY CONDUIT TYPE AND CONDUIT FILL ON |
| THE 1 1/2 INCH CONDUIT WITH THE CONDUCTORS AS SHOWN. |
| PLEASE SEE THE ONE CONDUIT IS MISSING THE EQUIPMENT |
| GROUNDING CONDUCTOR AS NOTED IN NOTE #10 BELOW. PLEASE |
| SEE IF THIS IS PVC AND SOME PART WILL BE SCHEDULE 80, |
| ALL SHALL BE FIGURED ON SCHEDULE 80 CONDUIT. |
| SEE TABLE IN CHAPTER 9 |
| |
| 6) NOTE: PLEASE SEE THAT THE PLANS SHALL BARE THE |
| PRINTED NAME, DATE AND SIGNATURE OF THE PERSON TAKING |
| RESPONSIBILITY OF THE PLANS. PLEASE SEE ONLY THE |
| PRINTED NAME IS BEING SHOWN. |
| FBC 106.1.2, FS 481.221, 471.025 |
| |
| 7) NOTE: PLEASE SEE WATER HEATER IS BEING SHOWN AS |
| HAVING A RECEPT FOR THE CONNECTION. PLEASE SEE 422.31, |
| 422.32 AS THIS SHALL BE A HARDWIRED UNIT WITH OR |
| WITHOUT A DISCONNECT DEPENDING ON THE LOCATION OF PANEL |
| ETC. |
| |
| 8) NOTE: PLEASE SEE 210.8A1, AS THE RECEPT(S) LOCATED |
| WITHIN THE BATHROOM AREAS AND WITHIN 3FT OF THE SINK |
| SHALL BE GFI ALSO. PLEASE SHOW. |
| |
| 9) NOTE: PLEASE SEE 210.8A6 AS ALL THE KITCHEN COUNTER |
| SPACE RECEPTS SHALL BE SHOWN AS GFI. |
| |
| 10) NOTE: PLEASE SEE RISER AS THE EQUIPMENT GROUNDING |
| CONDUCTOR IS MISSING FROM THE MAIN TO THE SUB PANEL. |
| 250.24B, 250.110, 250.122 |
| |
| 10) NOTE: PLEASE CORRELATE SERVICE, PLEASE SEE PANEL |
| SCHEDULE IS SHOWN AS 150AMPS YET THE RISER SHOWS THIS |
| AS 200AMP WITH A MAIN CIRCUIT BREAKER. |
| PLEASE ALSO SEE THE RISER MENTIONS PANEL IN GARAGE, YET |
| THE PANEL ON PLANS APPEAR TO BE IN A LAUNDRY ROOM AND |
| THERE IS NO GARAGE. |
| PLEASE ADJUST AND CORRELATE PLANS. |
| 106.1.2, 106.3.5.4, FBC ADMIN SECT |
| |
| 11) NOTE: PLEASE CORRELATE A/C LOADS. PLEASE SEE PANEL |
| SCHEDULE SHOWS 7.5KW AND 10KW. WHICH ONE? |
| FBC 106.1.2 |
| |
| 12) NOTE: PLEASE SEE 210.52 FOR SEVERAL MISSING |
| REQUIRED RECEPTACLE FOR WALL SPACES 2FT OR MORE. PLEASE |
| SEE COMMENT #15, AS THEY MAY BE OK, IF THE INTENTION IS |
| FOR THESE TO BE 1/2 SWITCHED. |
| |
| 13) NOTE: PLEASE CORRELATE LOAD ON IRRIGATION PUMP ON |
| PANEL SCHEDULE WITH THAT OF THE LOAD SHOWN ON LOAD |
| CALCULATIONS. |
| PLEASE ALSO SEE THE CIRCUIT IS BEING SHOWN ON A 1-POLE |
| 30A CIRCUIT? |
| |
| 14) NOTE:PLEASE CLARIFY IF THE LOAD ON THE POOL PUMP |
| IS SHOWN AT THE CONTINUOUS DUTY AS ON LOAD CALCULATIONS |
| OR PLEASE SHOW AT 125%.ALSO SHOWN ON A 120V 1-POLE |
| 30A CIRCUIT? |
| 215.3, 230.42 |
| |
| 15) NOTE: PLEASE SEE 210.70 AND LS 101 7.8, PLEASE SEE |
| THE PLANS AS THERE ARE MANY ANY WHICH WILL BE REQUIRED |
| TO CONTAIN A LIGHT FIXTURE OF SOME KIND BEFORE FINAL OR |
| OTHER EXCEPTION FOR SWITCHED RECEPT ETC. |
| PLEASE SEE THE NEW ROOM SHALL CONTAIN A METHOD OF |
| CONTROLLING LIGHTING FOR INGRESS INTO THE NEW ROOM FROM |
| THE OUTSIDE. PLEASE SEE THIS CAN BE DONE WITH A 3-WAY |
| OR OTHER OPTION. |
| 210.70 , LS 101 7.8 |
| PLEASE SEE SEVERAL AREAS WHICH INDICATE THE ENTIRE |
| RECEPT BEING SWITCHED. PLEASE KNOW THIS IS OK, HOWEVER |
| IF SWITCHING THE ENTIRE RECEPT, THEN AN ADDITIONAL |
| RECEPT WILL BE REQUIRED PER 210.52. IF ONLY SWITCHING |
| HALF, PLEASE ADJUST SYMBOL. |
| PLEASE ADJUST PLANS AS NEEDED. |
| |
| |
| 16) NOTE: * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |