2007-01-05 14:16:27 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SUBMITTED SHEETS A0, A3, AND A4 ARE UNACCEPTABLE DUE |
| TO THE FACT SHEETS ARE NOT SIGNED AND SEALED. |
| FAC-CODE-61G1-16001 ARCHITECT'S AND |
| INTERIOR DESIGNER'S SEAL: |
| EACH ARCHITECT AND INTERIOR DESIGNER |
| SHALL ACQUIRE A SEAL WITH WHICH HE OR |
| SHE SHALL IDENTIFY ALL PLANS, |
| SPECIFICATIONS OR REPORTS PREPARED OR |
| ISSUED BY HIM OR HER AND FILED FOR |
| PUBLIC RECORD. THE SEAL SHALL BE OF A |
| TYPE WHICH WILL MAKE AN IMPRESSION ON |
| THE SURFACE OF PRINTS OR OTHER |
| DUPLICATIONS OF DRAWINGS, AND AS |
| APPROPRIATE, UPON SPECIFICATION PAGES, |
| AND OTHER ARTICLES OF SERVICE. |
| NOTE:ON THE RESUBMITTAL JUST REFERENCE THE MASTER |
| PERMIT #05100303 AND DELETE RESUBMITTING SHEETS A0, A3, |
| AND A4. |
| |
| 2. THE SUBMITTED GAS RISER DIAGRAM DOES NOT RELECT THE |
| APPROVED SIGED AND SEALED PRINTS OF MASTER PERMIT |
| #05100303. THE 2ND FLOOR TANKLESS WATER HEATER IN THE |
| LAUNDRY ROOM IS MISSING FROM THE GAS RISER DIAGRAM. DUE |
| TO THE INCREASE BTU LOAD GAS PIPING TO THAT AREA NEEDS |
| TO BE INCEASED TO 1" ON THE RESUBMITTAL. ON YOUR |
| SUBMITTED ARCH. DRAWINGS THERE IS A HAND WRITTEN CHANGE |
| IN THE GENERATOR LOCATION THAT IS DIFFERENT THAN THE |
| SIGNED AND SEALED MASTER PERMIT #05100303. IF IT IS THE |
| INTENT TO CHANGE THE LOCATION OF THE GENERATOR THE |
| ARCHITECT OF RECORD NEEDS TO MAKE SAID CHANGES WITH A |
| REVISION. |
| |
| 3. ON THE RESUBMITTAL PLEASE INDICATE ALL PIPING |
| MATERIALS. |
| |
| 4. PLEASE SUBMIT MANUFACTURER CUT SHEETS OF THE MP |
| REGULATORS (2PSI TO 0.5PSI REG.) |
| |
| 5. THE VALUE OF THIS JOB SEEMS LOW PLEASE PROVIDE COPY |
| OF SIGNED CONTRACT WITH VALUE ATTACHED INCLUDING MP |
| REGULATORS. |
| PER FBC-2004, CHAPTER 1, SECTION |
| 108.3, BUILDING PERMIT VALUATION: IF IN |
| THE OPINION OF THE BUILDING OFFICIAL, |
| THE CLAIMED VALUATION OF THE BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, |
| THE PERMIT SHALL BE DENIED. FOR |
| PERMITTING PURPOSES, VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| FINISH, NORMAL SITE WORK (EXCAVATION AND |
| BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| VALUE. VALUATION REFERENCES MAY INCLUDE |
| THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| MEANS ECT.) WITH |
| REGIONAL ADJUSTMENTS FOR LOCATION AS |
| PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. |
| |
| |
| **********IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |