Plan Review Notes
Plan Review Notes For Permit 06120434
Permit Number 06120434
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-30 15:23:03*** REDLINED PLANS***
  
 1) NOTE: PANEL SCHEDULE DOES NOT INDICATE AFCI
 PROTECTION FOR SMOKE ALARMS. 210.12
  
 2) NOTE: DRYER/WASHER COMBO INDICATES 3KW ON PANEL
 SCHEDULE AND SHOWS 5.5KW ON LOAD CALCULATIONS. MIN PER
 220.54 OF 5KW REQUIRED.
  
 3) NOTE: PLEASE SEE ONE SET, RISER HAS 3/0 CONDUCTORS
 HAND DRAWN FOR FEEDERS AND ONE SET HAS 2/0 FOR THE SAME
 FEEDERS?
 EITHER MEET 310.16, HOWEVER PLANS NEED TO BE REVISED
 ONCE INSTALLED FOR RECORD OF INSTALLATION.
  
  