Plan Review Notes
Plan Review Notes For Permit 06120434
Permit Number 06120434
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-03 19:11:032004 FBC EXISTING BUILDING
 STRUCTURALS REPAIRS
 SECOND REVIEW
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE ENERGY CALCULATION FORMS SPECIFIES R 8.9 FOR THE
 WALLS AND THE PLANS SPECIFY R-11 ON S-1. PLEASE
 COORDINATE.
  
 3) SPECIFY THE REQUIRED LOAD BEARING CAPACITY OF THE
 SOIL IN POUNDS PER SQUARE FOOT, BASED ON THE DESIGN OF
 THE STRUCTURE. SEE NUMBER 12 FROM PREVIOUS REVIEW. SEE
 FBC 106.1.2 AND R401.
  
 4) SPECIFY THE SPACING OF THE ROOF TRUSS ON THE PLANS.
 SEE NUMBER 16 FROM PREVIOUS REVIEW. FBC 106.1.2
  
 5) THE TRUSS DRAWINGS REQUIRE CONNECTIONS TO BEARING
 FOR 2465 LBS. HORIZONTAL REACTION. PLEASE REVIEW THE
 TRUSS DRAWINGS AND SPECIFY ADEQUATE CONNECTIONS ON THE
 ROOF FRAMING PLAN. SEE COMMENT NUMBER 17 FROM LAST
 REVIEW.
  
 6) THE TRUSS DRAWINGS ARE REQUIRED TO HAVE THE ORIGINAL
 SIGNATURE OF THE TRUSS ENGINEER. PHOTO COPIED
 SIGNATURES OR STAMPS ARE NOT ACCEPTABLE. SEE FS471. SEE
 # 18 ON LAST REVIEW. THE TRUSS LAYOUT DOES HAVE THE
 TRUSS ENGINEER'S ORIGINAL SIGNATURE, HOWEVER, THE TRUSS
 DRAWINGS HAVE PHOTO COPIED SIGNATURES.
  
 7) THE APPROVED ROOFING SYSTEM AND FASTENING OPTION
 SELECTED FOR THE GAF MODIFIED ROOF SYSTEM HAS A DESIGN
 PRESSURE OF -45 PSF WHICH IS TOO LOW FOR THE PERIMETER
 AND CORNER ROOF AREAS. SUBMIT RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING IN THESE AREAS AS ALLOWED BY
 LIMITATION NUMBER 7 ON PAGE 32 OF THE NOA. SEE NUMBER
 20 ON LAST REVIEW.
  
 8)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE PRODUCT APPROVAL FOR
 THE ROOFING MATERIAL HAS NOT BEEN APPROVED IN WRITING
 BY THE D.O.R.
  
 9) THE PLANS SPECIFY THAT THE WINDOWS AND DOORS WILL BE
 IMPACT RATED. THE PRODUCT APPROVALS THAT WERE SUBMITTED
 FOR THE WINDOWS AND DOORS HAVE NO MISSLE IMPACT RATING.
 PLEASE CORRECT. NOTE: IF NOT USING IMPACT RATED
 PRODUCTS, SUBMIT PRODUCT APPROVALS FOR STORM PANELS
 ALONG WITH A KEY PLAN AND INSTALLATION SCHEDULE.
  
 10) THE INFORMATION SUBMITTED FROM INTERTEK IS NOT
 ACCEPTABLE. THE PRODUCT ARE REQUIRED TO HAVE STATE
 APPROVAL OR MIAMI-DADE APPROVAL. THE MANUFACTURER CAN
 APPLY FOR LOCAL PRODUCT APPROVAL IN COMPLIANCE WITH
 RULE 9B-72.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  