Date |
Text |
2007-01-22 14:28:39 | DENIED |
| REFERENCE: FBC-2004 PLUMBING; FBC-2004 BUILDING; |
| FBC-2004 CHAPTER 1, CITY OF WEST PALM BEACH AMENDMENTS; |
| |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SHEET S-1 OF 2 INDICATES EXISTING 6" X 4" SCUPPERS: |
| PLEASE PROVIDE A DETAIL OF THE PRIMARY AND THE |
| SECONDARY ROOF DRAINAGE SYSTEMS WITH THE FOLLOWING |
| INFORMATION A} SQUARE FEET OF ROOF PER TABLE 1106.7. B} |
| VERTICAL WALLS (SQUARE FEET) 1106.4. C} VERTICAL |
| CONDUCTORS AND LEADERS 1106.2. D} SECONDARY DRAIN |
| REQUIRED 1107.1, SEPERATE SYSTEMS REQUIRED 1107.2 AND |
| SIZING OF SECONDARY DRAINS 1107.3. |
| |
| 2. PER FBC-2004 BUILDING SECTION 1503.6 PROTECTION |
| AGAINST DECAY AND TERMITES: ROOF DOWNSPOUTS SHALL |
| DISCHARGE AT LEAST 1 FOOT AWAY FROM THE STRUCTURE |
| SIDEWALL WHETHER BY UNDERGROUND PIPING, TAIL |
| EXTENSIONS, OR SPLASH BLOCKS. PLEASE COMPLY ON THE |
| RESUBMITTAL. |
| |
| 3. SHEET P-1 OF 1 SANITARY RISER DIAGRAM: A} WASHING |
| MACHINE BRANCH DRAIN NEEDS TO BE INDICATED A MINIMUM OF |
| THREE INCH (3") PER FBC-2004 PLUMBING SECTION 406.3. B} |
| CLEANOUT FOR WASHING MACHINE NEEDS TO BE INDICATED AT |
| FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.) PER FBC-2004 |
| PLUMBING SECTION 708.9. C} SIZE ALL FIXTURE TRAPS PER |
| CHAPTER 1 AMENDMENTS SECTION 106.3.5.4. D} PROVIDE TWO |
| WAY CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND |
| SEWER PER FBC-2004 PLUMBING SECTION 708.3.5. |
| |
| 4. SHEET P-1 OF 1 DOMESTIC WATER ISOMETRIC: POTABLE |
| WATER SYSTEM IS SIZED TO SMALL, IT IS SUGGESTED THAT |
| FOUR HOT AND TWO COLD PER HALF INCH PIPE OR PROVIDE |
| ENGINEERED COPLIANCE TO APPENDIX "E" WATER PIPE SIZING |
| TABLES. PLEASE NOTE THAT FLUID VELOCITIES IN EXCESS TO |
| 5 TO 8 FEET/SECOND NOT USUALLY RECOMENDED. |
| |
| 5. SHEET P-1 OF 1 DOMESTIC WATER ISOMETRIC: PROVIDE |
| WATER HAMMER ARRESTORS FOR WASHING MACHINE PER FBC-2004 |
| PLUMBING SECTION 604.9. |
| |
| 6. IF REQUIRED PLEASE PROVIDE THERMAL EXPANSION |
| PROTECTION ON THE WATER HEATER DETAIL ON SHEET P-1 OF 1 |
| PER FBC-2004 PLUMBING SECTION 607.3. |
| |
| 7.NOTE: PLEASE SEE THAT NOT ALL SHEETS ARE SIGNED, |
| DATED, AND SEALED PER FBC 106.1, FS 481, FS 471 ECT... |
| NO PERSON HAS TAKEN RESPONSIBILITY FOR SOME SHEETS. |
| PLEASE CORRECT ON THE RESUBMITTAL. |
| |
| **********IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |