Plan Review Notes
Plan Review Notes For Permit 06120434
Permit Number 06120434
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-22 14:28:39DENIED
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 BUILDING;
 FBC-2004 CHAPTER 1, CITY OF WEST PALM BEACH AMENDMENTS;
  
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET S-1 OF 2 INDICATES EXISTING 6" X 4" SCUPPERS:
 PLEASE PROVIDE A DETAIL OF THE PRIMARY AND THE
 SECONDARY ROOF DRAINAGE SYSTEMS WITH THE FOLLOWING
 INFORMATION A} SQUARE FEET OF ROOF PER TABLE 1106.7. B}
 VERTICAL WALLS (SQUARE FEET) 1106.4. C} VERTICAL
 CONDUCTORS AND LEADERS 1106.2. D} SECONDARY DRAIN
 REQUIRED 1107.1, SEPERATE SYSTEMS REQUIRED 1107.2 AND
 SIZING OF SECONDARY DRAINS 1107.3.
  
 2. PER FBC-2004 BUILDING SECTION 1503.6 PROTECTION
 AGAINST DECAY AND TERMITES: ROOF DOWNSPOUTS SHALL
 DISCHARGE AT LEAST 1 FOOT AWAY FROM THE STRUCTURE
 SIDEWALL WHETHER BY UNDERGROUND PIPING, TAIL
 EXTENSIONS, OR SPLASH BLOCKS. PLEASE COMPLY ON THE
 RESUBMITTAL.
  
 3. SHEET P-1 OF 1 SANITARY RISER DIAGRAM: A} WASHING
 MACHINE BRANCH DRAIN NEEDS TO BE INDICATED A MINIMUM OF
 THREE INCH (3") PER FBC-2004 PLUMBING SECTION 406.3. B}
 CLEANOUT FOR WASHING MACHINE NEEDS TO BE INDICATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.) PER FBC-2004
 PLUMBING SECTION 708.9. C} SIZE ALL FIXTURE TRAPS PER
 CHAPTER 1 AMENDMENTS SECTION 106.3.5.4. D} PROVIDE TWO
 WAY CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND
 SEWER PER FBC-2004 PLUMBING SECTION 708.3.5.
  
 4. SHEET P-1 OF 1 DOMESTIC WATER ISOMETRIC: POTABLE
 WATER SYSTEM IS SIZED TO SMALL, IT IS SUGGESTED THAT
 FOUR HOT AND TWO COLD PER HALF INCH PIPE OR PROVIDE
 ENGINEERED COPLIANCE TO APPENDIX "E" WATER PIPE SIZING
 TABLES. PLEASE NOTE THAT FLUID VELOCITIES IN EXCESS TO
 5 TO 8 FEET/SECOND NOT USUALLY RECOMENDED.
  
 5. SHEET P-1 OF 1 DOMESTIC WATER ISOMETRIC: PROVIDE
 WATER HAMMER ARRESTORS FOR WASHING MACHINE PER FBC-2004
 PLUMBING SECTION 604.9.
  
 6. IF REQUIRED PLEASE PROVIDE THERMAL EXPANSION
 PROTECTION ON THE WATER HEATER DETAIL ON SHEET P-1 OF 1
 PER FBC-2004 PLUMBING SECTION 607.3.
  
 7.NOTE: PLEASE SEE THAT NOT ALL SHEETS ARE SIGNED,
 DATED, AND SEALED PER FBC 106.1, FS 481, FS 471 ECT...
 NO PERSON HAS TAKEN RESPONSIBILITY FOR SOME SHEETS.
 PLEASE CORRECT ON THE RESUBMITTAL.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  