Plan Review Notes
Plan Review Notes For Permit 06120434
Permit Number 06120434
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-12 08:50:10*** UNSAT ***
  
 1) NOTE:
  
 A) PLEASE KNOW THAT THE PLANS WILL BE ROUTED TO ZONING
 FOR DETERMINATION OF THE NEW SERVICE/METER BEING SHOWN
 ON PLANS.
  
 B) PLEASE ALSO KNOW THAT THIS PLAN IS BEING REVIEWED AS
 BEING PERMITTED AND SHOWN AS A DWELLING UNIT. PLEASE
 KNOW AT THIS TIME, DEPENDING ON ZONING OUTCOME, THERE
 MAY BE CHANGES REQUIRED WHICH WILL CHANGE THE
 ELECTRICAL COMMENTS IF NOT PERMITTED AS A DWELLING
 UNIT.
  
  
 2) NOTE: PLEASE SEE MISSING MAIN DISCONNECT FOR
 SERVICE. PLEASE SEE PANEL IS BEING SHOWN A MLO AND NO
 MAIN DISCONNECT IS BEING SHOWN OUTSIDE?
 230.70, 230.71, 240.4, 310.16
  
 3) NOTE: PLEASE SEE 250.6 AND 250.24B AS AN EQUIPMENT
 GROUNDING CONDUCTOR IS BEING SHOWN GOING TO THE PANEL
 P. PLEASE KNOW WITH THE RISER SHOWN, THIS IS NOT
 PERMITTED.
  
 4) NOTE: PLEASE SEE MISSING FOOTER STEEL WHICH IS TO BE
 PART OF THE GROUNDING ELECTRODE SYSTEM. 250.50.
  
 5) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE
 REFLECTED ON PLANS AS REQUIRED.
 2005 NFPA-70, 2002 NFPA-72.
  
 6) NOTE:PLEASE SUBMIT LOAD CALCULATIONS PER NEC
 220.82, 220.52 ETC
 THE LOAD CALCULATIONS AS SHOWN ARE NOT CODE COMPLIANT.
 PLEASE SHOW.
 FBC 106.1.2, 106.3.5.4(8)
  
 7) NOTE: PLEASE SEE NFPA-72 11-5.1.1, 11.8.3. PLEASE
 SEE NFPA-72 DEFINITIONS AS PLANS CALL FOR SD FOR SMOKE
 DETECTORS THIS IS OK, HOWEVER PLEASE KNOW IF THESE ARE
 INDEED SMOKE DETECTORS AS DEFINED IN NFPA72, THESE
 WOULD BE DEVICES WHICH ONLY DETECT AND WOULD SIGNAL TO
 OTHER ALARM/HORN DEVICES. NO ALARM HORN DEVICES ARE
 SHOWN. PLEASE INDICATE IF PART OF A FUTURE LV FA
 SYSTEM.
 PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED
 DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY
 WOULD BE LABELED AS SA FOR SMOKE ALARMS.
 PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT
 THE SOUTHERN SECTION MEETING FROM NFPA THAT IF UNITS
 ARE INDEED DEVICES WHICH DETECT AND SOUND AN ALARM,
 PLANS SHOULD SHOW THEM AS SA'S AND THIS IS NOT NEW
 CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST TO
 SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06 SHOULD
 BE CHANGING IF AND WHERE APPLICABLE.
 IF PART OF A LV FIRE/SECURITY SYSTEM PLEASE INDICATE AS
 SUCH. PLEASE SHOW DEVICES THEN FOR SOUNDING.
  
 ** PLEASE ALSO SEE MISSING SMOKE ALARMS OUTSIDE
 BEDROOMS FOR EACH SLEEPING ROOM.
 ** PLEASE ALSO SEE SMOKE ALARMS AS SHOWN ARE BEING
 SHOWN WIRED TO MULTIPLE CIRCUITS WHICH IS NOT POSSIBLE
 AS THE CODE REQUIRES THEM TO BE WIRED INLINE, WHICH
 WOULD BE THAT THEY WERE ON THE SAME CIRCUIT.
 ABOVE PER 11.5.1.1
  
 8) NOTE: PLEASE SEE THE BATH(S) ARE REQUIRED TO MEET
 210.52D AND 210.11C3. PLEASE SEE THE CIRCUITING SHOWS
 THEM ON THE KITCHEN CIRCUITS AND BOTH WIRED TOGETHER?
 PLEASE CORRELATE WITH PANEL SCHEDULE.
  
 9) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS CIRCUIT 14 FOR
 KITCHEN. 210.11C1, 408.4 ETC
 FBC 106.1.2, 106.3.5.4 (8)
  
 10) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS CIRCUIT 16
 FEEDING BATHS WHERE PLANS CONTAIN THIS CIRCUIT IN THE
 LIVING ROOM.(HOWEVER BOTH ARE NOT PERMITTED ON THE
 SAME CIRCUIT)
 408.4, 310.16, 210.11C3
  
 11) NOTE: PLEASE SHOW ALL COUNTER SPACES IN THE
 KITCHEN. COMPLIANCE WITH 210.52C1 CAN NO BE DONE AT
 THIS TIME.
  
 12) NOTE: PLEASE SEE IF THIS IS A KITCHEN AS PERMITTED
 FOR A DWELLING, PLEASE SEE MISSING TWO SMALL APPLIANCE
 CIRCUITS AS REQUIRED PER 210.52B1, 210.11C1, 220.52A
 PLEASE KNOW THAT NO OUTLETS OTHER THAN AS PERMITTED PER
 210.52B1 ARE PERMITTED ON THESE CIRCUITS. PLEASE SEE
 OUTSIDE GFI RECEPT ETC.
  
 13) NOTE: PLEASE SEE MISSING WP GFI'S PER 210.52E FRONT
 AND REAR OF DWELLING. (IF THIS APPLIES).
  
 14) NOTE: PLEAS SEE PANEL SCHEDULE CIRCUIT 12, WHICH IS
 SHOWN ON PLANS FOR KITCHEN OUTLETS AND PANEL SHOWS THIS
 PART OF THE WASHER/DRYER UNIT?
 PLEASE CORRELATE CIRCUITING AND PANEL SCHEDULE.
 408.4, 310.16,
 FBC 106.1.2, 106.3.5.4(8).
  
 15) NOTE: PLEASE SEE PLANS ONLY INDICATE THE
 WASHER/DRYER STACK UNIT AS BEING ON A 1-POLE CIRCUIT?
 PLEASE CORRELATE CIRCUITING.
 FBC106.1.2. NEC 408.4, 310.16 ETC
  
 16) NOTE: PLEASE SEE 210.4B AS THE DISHWASHER AND
 DISPOSAL ARE FED BY SINGLE POLE BREAKERS WHICH ARE NOT
 PERMITTED.
  
 17) NOTE: PLEASE CLARIFY ALL RECEPTACLES SHOWN IN
 BEDROOMS AS THE ENTIRE DEVICE BEING SWITCHED? PLEASE
 CLARIFY THIS AS IF SWITCH THE ENTIRE DEVICE THEN
 RECEPTS PER 210.52 WILL BE REQUIRED TO BE INSTALLED.
 PLEASE 210.52, 210.70
  
 18) NOTE: PLEASE SEE MISSING RECEPT PER 210.52
  
 19) NOTE: PLEASE SEE THE AHU BEING FED WITH #6 ON A 30A
 BREAKER. PLEASE KNOW THAT #6 WILL NOT FIT UNDER A 30A
 BREAKER.
  
 20) NOTE: PLEASE SEE WATER HEATER CAN NOT BE PLUGGED
 IN. PLEASE SEE SYMBOL ON PLANS CORRELATES WITH A 220
 OUTLET. MUST BE HARDWIRED/
 422.31, 422.30
  
 21) NOTE: PLEASE SEE PLANS ARE NOT, SIGNED, DATED,
 SEALED ETC NO PERSON HAS TAKEN RESPONSIBILITY FOR
 PLANS.
 FBC 106.1, FS 481, FS 471, FS 468 ETC.
  
 ** PLEASE KNOW BASED ON THE PLANS SUBMITTED AND ITEMS
 NOT PROVIDED FOR CODE COMPLIANCE, THERE MAY BE COMMENTS
 ON THE NEXT REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]