2007-01-12 08:50:10 | *** UNSAT *** |
| |
| 1) NOTE: |
| |
| A) PLEASE KNOW THAT THE PLANS WILL BE ROUTED TO ZONING |
| FOR DETERMINATION OF THE NEW SERVICE/METER BEING SHOWN |
| ON PLANS. |
| |
| B) PLEASE ALSO KNOW THAT THIS PLAN IS BEING REVIEWED AS |
| BEING PERMITTED AND SHOWN AS A DWELLING UNIT. PLEASE |
| KNOW AT THIS TIME, DEPENDING ON ZONING OUTCOME, THERE |
| MAY BE CHANGES REQUIRED WHICH WILL CHANGE THE |
| ELECTRICAL COMMENTS IF NOT PERMITTED AS A DWELLING |
| UNIT. |
| |
| |
| 2) NOTE: PLEASE SEE MISSING MAIN DISCONNECT FOR |
| SERVICE. PLEASE SEE PANEL IS BEING SHOWN A MLO AND NO |
| MAIN DISCONNECT IS BEING SHOWN OUTSIDE? |
| 230.70, 230.71, 240.4, 310.16 |
| |
| 3) NOTE: PLEASE SEE 250.6 AND 250.24B AS AN EQUIPMENT |
| GROUNDING CONDUCTOR IS BEING SHOWN GOING TO THE PANEL |
| P. PLEASE KNOW WITH THE RISER SHOWN, THIS IS NOT |
| PERMITTED. |
| |
| 4) NOTE: PLEASE SEE MISSING FOOTER STEEL WHICH IS TO BE |
| PART OF THE GROUNDING ELECTRODE SYSTEM. 250.50. |
| |
| 5) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE |
| REFLECTED ON PLANS AS REQUIRED. |
| 2005 NFPA-70, 2002 NFPA-72. |
| |
| 6) NOTE:PLEASE SUBMIT LOAD CALCULATIONS PER NEC |
| 220.82, 220.52 ETC |
| THE LOAD CALCULATIONS AS SHOWN ARE NOT CODE COMPLIANT. |
| PLEASE SHOW. |
| FBC 106.1.2, 106.3.5.4(8) |
| |
| 7) NOTE: PLEASE SEE NFPA-72 11-5.1.1, 11.8.3. PLEASE |
| SEE NFPA-72 DEFINITIONS AS PLANS CALL FOR SD FOR SMOKE |
| DETECTORS THIS IS OK, HOWEVER PLEASE KNOW IF THESE ARE |
| INDEED SMOKE DETECTORS AS DEFINED IN NFPA72, THESE |
| WOULD BE DEVICES WHICH ONLY DETECT AND WOULD SIGNAL TO |
| OTHER ALARM/HORN DEVICES. NO ALARM HORN DEVICES ARE |
| SHOWN. PLEASE INDICATE IF PART OF A FUTURE LV FA |
| SYSTEM. |
| PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED |
| DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY |
| WOULD BE LABELED AS SA FOR SMOKE ALARMS. |
| PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT |
| THE SOUTHERN SECTION MEETING FROM NFPA THAT IF UNITS |
| ARE INDEED DEVICES WHICH DETECT AND SOUND AN ALARM, |
| PLANS SHOULD SHOW THEM AS SA'S AND THIS IS NOT NEW |
| CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST TO |
| SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06 SHOULD |
| BE CHANGING IF AND WHERE APPLICABLE. |
| IF PART OF A LV FIRE/SECURITY SYSTEM PLEASE INDICATE AS |
| SUCH. PLEASE SHOW DEVICES THEN FOR SOUNDING. |
| |
| ** PLEASE ALSO SEE MISSING SMOKE ALARMS OUTSIDE |
| BEDROOMS FOR EACH SLEEPING ROOM. |
| ** PLEASE ALSO SEE SMOKE ALARMS AS SHOWN ARE BEING |
| SHOWN WIRED TO MULTIPLE CIRCUITS WHICH IS NOT POSSIBLE |
| AS THE CODE REQUIRES THEM TO BE WIRED INLINE, WHICH |
| WOULD BE THAT THEY WERE ON THE SAME CIRCUIT. |
| ABOVE PER 11.5.1.1 |
| |
| 8) NOTE: PLEASE SEE THE BATH(S) ARE REQUIRED TO MEET |
| 210.52D AND 210.11C3. PLEASE SEE THE CIRCUITING SHOWS |
| THEM ON THE KITCHEN CIRCUITS AND BOTH WIRED TOGETHER? |
| PLEASE CORRELATE WITH PANEL SCHEDULE. |
| |
| 9) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS CIRCUIT 14 FOR |
| KITCHEN. 210.11C1, 408.4 ETC |
| FBC 106.1.2, 106.3.5.4 (8) |
| |
| 10) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS CIRCUIT 16 |
| FEEDING BATHS WHERE PLANS CONTAIN THIS CIRCUIT IN THE |
| LIVING ROOM.(HOWEVER BOTH ARE NOT PERMITTED ON THE |
| SAME CIRCUIT) |
| 408.4, 310.16, 210.11C3 |
| |
| 11) NOTE: PLEASE SHOW ALL COUNTER SPACES IN THE |
| KITCHEN. COMPLIANCE WITH 210.52C1 CAN NO BE DONE AT |
| THIS TIME. |
| |
| 12) NOTE: PLEASE SEE IF THIS IS A KITCHEN AS PERMITTED |
| FOR A DWELLING, PLEASE SEE MISSING TWO SMALL APPLIANCE |
| CIRCUITS AS REQUIRED PER 210.52B1, 210.11C1, 220.52A |
| PLEASE KNOW THAT NO OUTLETS OTHER THAN AS PERMITTED PER |
| 210.52B1 ARE PERMITTED ON THESE CIRCUITS. PLEASE SEE |
| OUTSIDE GFI RECEPT ETC. |
| |
| 13) NOTE: PLEASE SEE MISSING WP GFI'S PER 210.52E FRONT |
| AND REAR OF DWELLING. (IF THIS APPLIES). |
| |
| 14) NOTE: PLEAS SEE PANEL SCHEDULE CIRCUIT 12, WHICH IS |
| SHOWN ON PLANS FOR KITCHEN OUTLETS AND PANEL SHOWS THIS |
| PART OF THE WASHER/DRYER UNIT? |
| PLEASE CORRELATE CIRCUITING AND PANEL SCHEDULE. |
| 408.4, 310.16, |
| FBC 106.1.2, 106.3.5.4(8). |
| |
| 15) NOTE: PLEASE SEE PLANS ONLY INDICATE THE |
| WASHER/DRYER STACK UNIT AS BEING ON A 1-POLE CIRCUIT? |
| PLEASE CORRELATE CIRCUITING. |
| FBC106.1.2. NEC 408.4, 310.16 ETC |
| |
| 16) NOTE: PLEASE SEE 210.4B AS THE DISHWASHER AND |
| DISPOSAL ARE FED BY SINGLE POLE BREAKERS WHICH ARE NOT |
| PERMITTED. |
| |
| 17) NOTE: PLEASE CLARIFY ALL RECEPTACLES SHOWN IN |
| BEDROOMS AS THE ENTIRE DEVICE BEING SWITCHED? PLEASE |
| CLARIFY THIS AS IF SWITCH THE ENTIRE DEVICE THEN |
| RECEPTS PER 210.52 WILL BE REQUIRED TO BE INSTALLED. |
| PLEASE 210.52, 210.70 |
| |
| 18) NOTE: PLEASE SEE MISSING RECEPT PER 210.52 |
| |
| 19) NOTE: PLEASE SEE THE AHU BEING FED WITH #6 ON A 30A |
| BREAKER. PLEASE KNOW THAT #6 WILL NOT FIT UNDER A 30A |
| BREAKER. |
| |
| 20) NOTE: PLEASE SEE WATER HEATER CAN NOT BE PLUGGED |
| IN. PLEASE SEE SYMBOL ON PLANS CORRELATES WITH A 220 |
| OUTLET. MUST BE HARDWIRED/ |
| 422.31, 422.30 |
| |
| 21) NOTE: PLEASE SEE PLANS ARE NOT, SIGNED, DATED, |
| SEALED ETC NO PERSON HAS TAKEN RESPONSIBILITY FOR |
| PLANS. |
| FBC 106.1, FS 481, FS 471, FS 468 ETC. |
| |
| ** PLEASE KNOW BASED ON THE PLANS SUBMITTED AND ITEMS |
| NOT PROVIDED FOR CODE COMPLIANCE, THERE MAY BE COMMENTS |
| ON THE NEXT REVIEW. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |