Plan Review Notes For Permit 06120431 |
Permit Number |
06120431 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-01-22 09:21:59 | ******APPROVED***** | | | | | | 1.THE FIRE ALARM SYSTEM IN CONJUNCTION WITH THE FIRE | | SPRINKLER SYTEM,WATERFLOW SHALL ACTIVATE GENERAL FIRE | | ALARM WITHIN 45 TO 60 SECONDS. | | | | 2.FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR CENTRAL | | STATION.INSTALL UL CERTIFICATE AT THE FIRE ALARM | | CONTROL PANEL AND PROVIDE A COPY TO WPBFR PRIOR TO OR | | AT THE FINAL FIRE ALARM INSPECTION. |
|