Plan Review Notes For Permit 06120431 |
Permit Number |
06120431 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-12-26 13:20:46 | ***DENIED*** | | | | 1) WPB AMENDMENTS TO FBC 2004 EDITION REQUIRES WORK | | VALUED AT GREATER THAN $5000.00 TO BE SIGNED, DATED AND | | SEALED BY PROFESSIONAL ENGINEER. | | | | 2) SMOKE DUCT DETECTORS SHALL INITIATE A GENERAL FIRE | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | 3) FIRE ALARM THAT SUPERVISES A SPRINKLER SYSTEM TO BE | | UL CERTIFIED FOR CENTRAL STATION SERVICE. CERTIFICATE | | REQUIRED PRIOR TO OR AT THE TIME OF FINAL INSPECTION OF | | FIRE ALARM SYSTEM. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | (561) 805-6722 OR 804-4756 |
|