Plan Review Notes
Plan Review Notes For Permit 06120431
Permit Number 06120431
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-12-26 13:20:46***DENIED***
  
 1) WPB AMENDMENTS TO FBC 2004 EDITION REQUIRES WORK
 VALUED AT GREATER THAN $5000.00 TO BE SIGNED, DATED AND
 SEALED BY PROFESSIONAL ENGINEER.
  
 2) SMOKE DUCT DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 3) FIRE ALARM THAT SUPERVISES A SPRINKLER SYSTEM TO BE
 UL CERTIFIED FOR CENTRAL STATION SERVICE. CERTIFICATE
 REQUIRED PRIOR TO OR AT THE TIME OF FINAL INSPECTION OF
 FIRE ALARM SYSTEM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW