Plan Review Notes For Permit 06120402 |
Permit Number |
06120402 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-05-23 08:36:18 | DENIED; | | 1. RISER DIAGRAM; | | A) TUB NOT VENTED | | B) KITCHEN SINK NEED A VENT | | C)EXTRA BATHROOM ON RISER DIAGRAM | | 2. PLUMBING NOTES; | | A) NOTE 5, DELETE AIR CHAMBERS FROM NOTE, NO | | REFERENCE TO AIR CHAMBERS IN PLUMBING CODE. | | B) NOTE 9 CHANGE NOTE TO " WASTE LINES 3" AND | | LARGER CAN SLOP 1/8" PER FT, PIPE 2 1/2 " TO SLOP 1/4 " | | PER FT. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|