Plan Review Notes For Permit 06120402
Permit Number 06120402
Review Stop P
Sequence Number 3
Notes
Date Text
2007-05-23 08:36:18DENIED;
 1. RISER DIAGRAM;
 A) TUB NOT VENTED
 B) KITCHEN SINK NEED A VENT
 C)EXTRA BATHROOM ON RISER DIAGRAM
 2. PLUMBING NOTES;
 A) NOTE 5, DELETE AIR CHAMBERS FROM NOTE, NO
 REFERENCE TO AIR CHAMBERS IN PLUMBING CODE.
 B) NOTE 9 CHANGE NOTE TO " WASTE LINES 3" AND
 LARGER CAN SLOP 1/8" PER FT, PIPE 2 1/2 " TO SLOP 1/4 "
 PER FT.
 PLUMBING PLAN REVIEW BY;