Plan Review Notes
Plan Review Notes For Permit 06120402
Permit Number 06120402
Review Stop M
Sequence Number 3
Notes
Date Text
2007-05-21 08:58:48*** DENIED ***
 1) SEE TITLE BLOCK ON PLANS SHOW THE WRONG JOB ADDRESS,
 PLEASE CORRECT.
  
 2) AS NOTED IN LAST TWO REVIEWS 3-12-07 NOTE #3 AND
 12-19-07 NOTE #2. PLEASE SEE THE COOLING LOAD
 CALCULATIONS ARE CALLING FOR 13,331 SENSIBLE BTU'S, THE
 MECHANICAL PLANS ARE CALLING FOR 24,800 SENSIBLE BTU'S,
 THE PLANS CAN ONLY CALL FOR 15% MORE SENSIBLE BTU'S
 THAN THE COOLING LOAD CALCULATIONS, SEE 2004 FBC
 13-607.1.ABC.1.1 (12-8-06 REVISION). PLEASE CORRECT.
  
 3) AS NOTED IN LAST REVIEW 3-12-07 NOTE #5. SEE ENERGY
 CALCULATIONS #15 IS TAKING THE CF (CEILING FAN) CREDIT,
 ELECTRICAL PLANS SHOW FUTURE FANS, CREDIT MAY NOT BE
 TAKEN FOR FUTURE WORK, SEE 2004 FBC 13-607.2.A.3.1.
 PLEASE CORRECT.
  
 4) ENERGY CALCULATIONS ARE FOR 2292 SQUARE FEET (BOTH
 UNITS) BUT LINES 12, 13, AND 14 SHOW ONLY ONE A/C
 SYSTEM, ONE HEATER AND ONE WATER HEATER, . WILL NEED TO
 SHOW TWO OF EACH OR SUBMIT TWO SEPARATE ENERGY
 CALCULATIONS FOR EACH UNIT AND CORRECT TOTAL SQUARE
 FEET, PLEASE CORRECT.
  
 5) ENERGY CALCULATIONS LINE 12 SHOWS 29,200 TOTAL
 COOLING BTU'S., MECHANICAL PLANS EQUIPMENT LISTING
 SHOWS 33,200 TOTAL COOLING BTU'S., THE TWO MUST
 COINCIDE PLEASE CORRECT.
  
 6) ENERGY CALCULATIONS LINE 13 SHOWS 34.000 TOTAL
 HEATING BTU'S., MECHANICAL PLANS SHOW 24,000 TOTAL
 HEATING BTU'S., THE TWO MUST COINCIDE PLEASE CORRECT.
  
 7) PLEASE SEE ELECTRICAL REVIEW NOTE #1 AS THIS ALSO
 APPLIES TO THE MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.