Plan Review Notes
Plan Review Notes For Permit 06120402
Permit Number 06120402
Review Stop E
Sequence Number 3
Notes
Date Text
2007-05-18 16:17:16** UNSAT 3RDREVIEW **
  
  
 ** PLEASE SEE THERE ARE MANY COMMENTS FROM THE PREVIOUS
 TWO REVIEWS WHICH ARE STILL IN NEED OF ADDRESSING. ANY
 NEW COMMENTS ARE FROM CHANGES AND INFORMATION WHICH IS
 NOW BEING SUBMITTED FOR THE FIRST TIME FOR REVIEW.
  
 ** PLEASE KNOW A RESPONSE LETTER FROM THE DESIGN
 PROFESSIONAL IS MOST HELPFUL IN THE REVIEW PROCESS.
  
 ***IMPORANT***
 PLEASE ALSO KNOW DUE TO THE PLANS NOT BEING COMPLETE AT
 THIS TIME AND THE FOLLOWING COMMENTS FOR PLANS
 SUBMITTED, THERE MAY BE COMMENTS ON NEXT REVIEW WHICH
 ARE NOT ON THIS REVIEW.
 **** DUE TO THE EXTENT OF THE ELECTRICAL COMMENTS AND
 OTHER COMMENTS BASED ON LICENSING, ONE SET OF THE
 ELECTRICAL PLANS ARE ONCE AGAIN BEING RETAINED. PLEASE
 SEE COMMENTS WITH RESPECT TO FLORIDA STATUTES FOR
 REPEAT COMMENTS.
  
  
 1) NOTE: PLEASE SEE THERE ARE SEVERAL CODE COMPLIANT
 SECTIONS WHICH HAVE BEEN REPEATED FOR THE THIRD REVIEW
 AND A FEE FOR THE PLAN REVIEW PORTION OF THE PERMIT FEE
 HAS NOW BEEN ASSESSED TO THE DESIGN PROFESSIONAL AS
 REQUIRED UNDER FS 553.80(2)(B). THIS WAS GIVEN AS A
 NOTICE ON PREVIOUS REVIEW AS SEVERAL CODES WERE
 REPEATED IN THE 2ND REVIEW. PLEASE KNOW THAT THIS FEE
 IS ASSESSED TO THE DESIGN PROFESSIONAL UNDER FLORIDA
 STATUTES AND IS NOT THE RESPONSIBILITY OF CONTRACTOR OR
 OWNER. THE PLANS RETAINED FROM BOTH PREVIOUS REVIEWS
 AND THIS REVIEW WILL BE SENT TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW. THE FEE OF $3000.00
 IS DUE BEFORE ANY PLANS MAY BE RE-SUBMITTED FOR REVIEW
 FOR THE 4TH REVIEW.
 ** PLEASE ALSO KNOW THAT TO DATE OF THIS REVIEW, NO ONE
 HAS CONTACTED THIS REVIEWER TO GO OVER ANY COMMENTS OR
 QUESTIONS.
  
 2) NOTE: PLEASE SEE NOTES AS PREVIOUSLY STATED WITH
 RESPECT TO SIGNING OF PLANS. NO SIGNATURE VERIFICATION
 LETTER WAS LOCATED IN PLANS.
 PLEASE SEE PLANS SEEM TO BE SIGNED WITH AN INITIAL OF
 SOME SORT. IF THIS IS INDEED THE LEGAL SIGNATURES OF
 THE DESIGNER OF RECORD PLEASE PROVIDE A SIGNED, DATED
 AND SEALED LETTER WITH STATEMENT OF LEGAL SIGNATURE.
 FS 471.025
 PLEASE BE SURE LETTER IS PROPERLY NOTARIZED UNDER
 FLORIDA STATUTES 117.05.
 PLEASE KNOW THIS LETTER WILL BE PLACED IN OUR SIGNATURE
 FILE FOR ANY FUTURE REFERENCE AS NEEDED AND WILL NOT BE
 NEED TO PROVIDE LETTER ON FUTURE PROJECTS.
 ** PLEASE KNOW, THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADE REVIEWS WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 3) NOTE: THIS IS THE SAME COMMENT. ONLY THE NEC WAS
 ADDED.
 PLEASE SEE ONLY THE 2005 NEC WAS ADDED TO PLANS.
 PLEASE SEE THE CODES WHICH WERE REQUESTED FOR OTHERS
 WERE NOT ADDED. PLEASE SEE THAT ALL PLANS SHALL STATE
 THE CODE IN WHICH THEY ARE DESIGNED UNDER. THIS IS
 SUBMITTED UNDER THE NEW CODES. 2004 FBC W/ THE 2006
 REVISIONS.
  
 4) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW. THIS IS ONE BUILDING BY DEFINITION AND ONLY ONE
 SERVICE IS PERMITTED AND GROUPING OF MAINS IS REQUIRED.
 PLEASE REVISE RISER FOR NEW SINGLE SERVICE.
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE RISER AND PLANS SUBMITTED. PLEASE SEE
 PLANS DO NOT INDICATE GROUPING OF MAINS AS RISER SEEMS
 TO SHOW. PLEASE SEE MISSING SERVICE ENTRANCE CONDUCTORS
 FOR NEW RISER.
 PLEASE SEE THE RISER AS SHOWN IS NOT CODE COMPLIANT
 WITH SEVERAL SECTIONS OF THE NEC. PLEASE SEE OTHER
 COMMENTS RELEVANT TO THE RISER.
 THIS IS ONE *BUILDING* BY DEFINITION IN THE FBC AND
 ONLY ONE SERVICE PER 230.2 WILL BE GRANTED. PLANS SHOW
 TWO DIFFERENT LOCATIONS/SERVICE METERS.
 230.70, 230.72, 240.4, 310.16, 310.15B6, ETC. PLEASE
 SEE THE SIZE OF THE METER CAN, CAN NOT BE VERIFIED AS
 NO LOAD CALCULATIONS WERE SUBMITTED. FBC 106.1.2,
 106.3.5.4(PARA 8) ADMIN SECTION. THERE ARE CURRENTLY
 MANY SECTIONS BESIDES THE ONES NOTED BELOW WHICH COULD
 NOT BE ALL TYPED IN THIS REVIEW.
  
 5) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW. RISER STILL SHOWS THIS. THIS NOTE AND CODE
 SECTION WILL BE APPLICABLE FOR NEW SERVICE ALSO.
 PLEASE SEE 250.6, 250.24B AS NO EQUIPMENT GROUNDING
 CONDUCTORS ARE PERMITTED BEFORE THE FIRST MEANS OF
 DISCONNECT.
  
 6) NOTE:AS THE SERVICE WILL CHANGE, THIS SAME COMMENT
 FROM PREVIOUS REVIEW WILL REMAIN. PLEASE SEE AS THE
 SERVICE IS NOT COMPLETE AND THE SERVICE ENTRANCE
 CONDUCTORS ARE NOT SHOWN REVIEW FOR CODE COMPLIANCE CAN
 NOT BE DONE. BASED ON THE SIZE OF THE GEC AS SHOWN IT
 DOES NOT MEET THE SECTION OF THE CODE PREVIOUSLY
 GIVEN.
 PLEASE SEE 250.66 AS THE SIZE OF SERVICE MAY CHANGE
 WHICH WILL DICTATE THE SIZE OF THE GROUNDING ELECTRODE
 CONDUCTOR.
  
 7) NOTE: SAME NOTE, NOTHING CHANGED. PLANS DO NOT
 INDICATE THE REQUIRED RATINGS FOR MAIN(S).PLEASE SEE
 ONLY THE BRACE RATING AND BRANCH CIRCUIT RATING IS
 BEING SHOWN FOR SUB PANEL(S).
 PLEASE SUBMIT THE AIC RATINGS FOR SERVICE MAINS PER
 110.9.
 PLEASE SEE THE RATING AS SHOWN ON PANEL SCHEDULE WAS
 NOTED, HOWEVER NEEDED FOR MAIN(S).
  
 8) NOTE:THIS IS THE SAME COMMENT. THE PANEL SCHEDULE
 IS NOT COMPLETE AND LOAD CALCULATIONS ARE NOT COMPLETE.
 WHERE ARE LOADS ON SERVICE FOR EACH PANEL AND SERVICE
 AS SHOWN ON RISER? PLEASE COMPLETE AND SUBMIT A
 COMPLETE PANEL SCHEDULE WITH ALL MINIMUM REQUIRED
 DEDICATED LOADS AS WELL AS COMPLETED LOAD CALCULATIONS
 BASED ON MINIMUM REQUIREMENTS FROM THE NEC.
 PLEASE SEE THE SMALL APPLIANCE CIRCUITS ARE NOT
 CORRECT, SHOWS 4500VA FOR TWO CIRCUITS?
 PLEASE SEE THE WASHER/ LAUNDRY LOADS WHICH ARE NOT
 CORRECT FOR MINIMUM LOADS PER NEC.
 PLEASE SEE NO LOAD IS SHOWN FOR A/C SYSTEM. NO LARGER
 LOADS? ETC.
 PLEASE SEE 220.40, 220.82, 220.52, 220.54, 220.60, ETC,
 ETC.
 FBC ADMIN SECTION 106.3.5.4
  
 9) NOTE: THIS IS THE SAME COMMENT AS THE PANEL SCHEDULE
 STILL INDICATE THE DEDICATE BATH RECEPTACLE CIRCUIT ON
 WITH GARAGE RECEPTACLES. PLEASE SEE PLANS AS PLANS DO
 NOT INDICATE ANY KIND OF GARAGE??
 PLEASE SEE 210.52D, 210.11C3, AS NO OTHER LOADS ARE
 PERMITTED ON THE DEDICATED BATH CIRCUIT(S).
  
 10) NOTE: THIS IS THE SAME COMMENT.
 PLEASE SEE 210.52C1 FOR MISSING REQUIRED GFI'S ALONG
 KITCHEN COUNTER SPACE.
 MISSING MINIMUM VA 220.52
  
 11) NOTE:THIS IS THE SAME COMMENT.PLEASE SEE THAT
 THE PANEL SCHEDULE INDICATES THE DINING ROOM
 RECEPTACLES ON WITH LIGHTING AND MANY OTHER AREAS WHICH
 ARE NOT PERMITTED.
 NO INFORMATION WAS SUBMITTED.
 PLEASE SEE MISSING REQUIRED CIRCUITING FOR DINING ROOM
 RECEPTS PER 210.52B1, 210.11C1, AND 220. 52B.
  
 12) NOTE:THIS COMMENT WILL REMAIN AS NOTED ABOVE IN
 NOTE #9 THERE ARE RECEPTACLES ALONG KITCHEN COUNTER
 SPACE WHICH ARE STILL MISSING.
 PLEASE SEE 210.8A6, AS ALL RECEPTS ALONG KITCHEN
 COUNTER SPACE SHALL BE SHOWN AS GFI.
  
 13) NOTE:THIS COMMENT REMAINS AS THE MINIMUM
 CLEARANCES IN SOME OF THE CLOSETS ARE NOT MET. PLEASE
 SEE 410.8 AS THE PC LIGHTING IN CLOSETS ARE NOT
 PERMITTED AS SHOWN. THEY DO NOT MEET MINIMUM
 CLEARANCES.
  
 14) NOTE: PLEASE GO OVER PLANS AS SCALE STILL SEEMS TO
 SHOW SOME NOT SPACED PER 210.52
 PLEASE SEE MISSING RECEPTS PER 210.52 FOR WALL
 SPACES.
 PLEASE SEE PLANS ARE STILL MISSING RECEPTACLES PER
 210.52
  
 15) NOTE:THIS COMMENT IS THE SAME FROM PREVIOUS
 REVIEW. PLEASE SEE ALL SMOKE DEVICES ARE STILL BEING
 SHOWN AS *SMOKE DETECTORS* AND SYMBOL LEGEND EVENS
 STATES AND SHOWS THESE BEING 110V UNITS WHICH THESE
 WOULD BE *SMOKE ALARMS*
 PLANS SHOW BOTH??
 PLEASE SEE ALL SMOKE DEVICES SHALL BE SHOWN AS DEFINED
 IN NFPA-72. PLEASE SEE IF THESE DEVICES AS SHOWN ARE
 PART OF A LOW VOLTAGE ALARM SYSTEM WHICH CONTAINS
 HORN/ALARM DEVICES THEN THE SD AS SHOWN FOR SMOKE
 DETECTOR IS OK. IF THESE DEVICES AS SHOWN ARE DETECT
 AND SOUND AN ALARM, THEN THEY SHALL BE SHOWN AS SA FOR
 SMOKE ALARMS.
 PLEASE ALSO SEE NFPA-72 11.5.1.1, 11.8.3 FOR LOCATIONS
 REQUIRED INSIDE AND OUTSIDE ALL SLEEPING ROOMS. PLEASE
 SEE SOME ROOMS DO NOT INDICATE THE DEVICE OUTSIDE THE
 SLEEPING ROOM, YET INDICATE TWO DEVICES INSIDE ROOM?
 PLEASE SEE OTHER ROOMS WHICH DO INDICATE A DEVICE
 OUTSIDE ROOM, BUT STILL INDICATE TWO OR MORE INSIDE??
  
 16) NOTE: THIS COMMENT IS THE SAME. NO CORRECTION WAS
 MADE.
 PLEASE SEE MISSING DISCONNECTS FOR ALL A/C EQUIPMENT.
 PLEASE SEE 440.11. STILL SHOWN AS RECEPTACLES WHICH ARE
 NOT PERMITTED.
 PLEASE SEE AHU CLOSET APPEARS TO SHOW TWO RECEPTS.
 PLEASE KNOW AS PER 422.31, AHU'S SHALL NOT BE PLUGGED
 IN.
  
 17) NOTE: THIS IS THE SAME COMMENT.
 PLEASE SEE 422.31 FOR DISCONNECTING MEANS REQUIRED FOR
 WATER HEATER(S).
  
  
 18) NOTE: PLEASE SEE 422.13 FOR REQUIRED LOAD
 CALCULATIONS FOR WATER HEATERS AS PREVIOUS PLANS DID
 NOT SHOW LOADS, THIS COMMENT IS NEW NOW THAT LOADS ARE
 SHOWN.
  
 19) NOTE:THIS IS THE SAME COMMENT AS PLANS ARE STILL
 MISSING SEVERAL CIRCUITS WHICH THE REVIEW CAN NOT
 DETERMINE SPECIFIC USE OF SOME WHICH MAY NEED TO BE
 DEDICATED CIRCUITS ETC.
 PLEASE SEE SEVERAL ELECTRICAL DEVICES ON PLANS WHICH
 ARE MISSING CIRCUITING. THERE ARE MANY ITEMS WHICH NEED
 CIRCUITING TO REVIEW FOR CODE COMPLIANCE.
 FBC 106.1.2, 106.3.5.4
  
 20) NOTE: THIS IS THE SAME COMMENT AS THE CODE REQUIRES
 *ALL OUTLETS* IN BEDROOMS TO CONTAIN ARC FAULT
 PROTECTION PLEASE SEE MISSING ARC FAULT PROTECTION FOR
 ALL OUTLETS IN BEDROOMS. 210.12 THIS IS NOT ONLY
 REQUIRED FOR RECEPTACLES.
  
 21) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW.
 PLEASE SEE SOME RECEPTACLES ARE NOT BEING SHOWN
 SWITCHING THE ENTIRE RECEPTACLES WHICH IS OK, HOWEVER
 AS NOTED ABOVE PER 210.52, THEN RECEPTACLES WOULD BE
 REQUIRED IN ADDITION FOR GENERAL PURPOSE.
  
 22) NOTE: THIS IS THE SAME COMMENT PLEASE SEE PLANS
 APPEAR TO NOW HAVE ONE NEW RECEPTACLE FOR WHAT APPEARS
 TO BE FOR THE DISHWASHER AND DISPOSAL BUT IT IS UNCLEAR
 AS ONE UNIT SHOWS THIS OUTLET AS GFI AND THE OTHER NOT
 GFI PROTECTED. PLEASE SEE 210.4, IF THESE ARE ON THE
 SAME YOKE/DEVICE THEN A 2-POLE BREAKER IS REQUIRED.
 PLEASE ALSO SHOW AND IDENTIFY THE RECEPTACLE FOR THESE
 ON PLANS.
  
 23) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW. PLEASE SHOW ALL ROOM AND AREA DESIGNATIONS ON
 PLANS IN ORDER TO REVIEW SOME CIRCUITING FOR CODE
 COMPLIANCE.
 FBC 106.1.2 ADMIN SECTION.
  
 24) NOTE:PLEASE SEE AS THE ADDRESS HAS CHANGED,
 PLEASE ADJUST TITLE BLOCKS AND REMOVE THE OLD 601 14TH
 ST.
 FAC 61G15-23, 61G1-16
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  