Date |
Text |
2007-05-18 16:17:16 | ** UNSAT 3RDREVIEW ** |
| |
| |
| ** PLEASE SEE THERE ARE MANY COMMENTS FROM THE PREVIOUS |
| TWO REVIEWS WHICH ARE STILL IN NEED OF ADDRESSING. ANY |
| NEW COMMENTS ARE FROM CHANGES AND INFORMATION WHICH IS |
| NOW BEING SUBMITTED FOR THE FIRST TIME FOR REVIEW. |
| |
| ** PLEASE KNOW A RESPONSE LETTER FROM THE DESIGN |
| PROFESSIONAL IS MOST HELPFUL IN THE REVIEW PROCESS. |
| |
| ***IMPORANT*** |
| PLEASE ALSO KNOW DUE TO THE PLANS NOT BEING COMPLETE AT |
| THIS TIME AND THE FOLLOWING COMMENTS FOR PLANS |
| SUBMITTED, THERE MAY BE COMMENTS ON NEXT REVIEW WHICH |
| ARE NOT ON THIS REVIEW. |
| **** DUE TO THE EXTENT OF THE ELECTRICAL COMMENTS AND |
| OTHER COMMENTS BASED ON LICENSING, ONE SET OF THE |
| ELECTRICAL PLANS ARE ONCE AGAIN BEING RETAINED. PLEASE |
| SEE COMMENTS WITH RESPECT TO FLORIDA STATUTES FOR |
| REPEAT COMMENTS. |
| |
| |
| 1) NOTE: PLEASE SEE THERE ARE SEVERAL CODE COMPLIANT |
| SECTIONS WHICH HAVE BEEN REPEATED FOR THE THIRD REVIEW |
| AND A FEE FOR THE PLAN REVIEW PORTION OF THE PERMIT FEE |
| HAS NOW BEEN ASSESSED TO THE DESIGN PROFESSIONAL AS |
| REQUIRED UNDER FS 553.80(2)(B). THIS WAS GIVEN AS A |
| NOTICE ON PREVIOUS REVIEW AS SEVERAL CODES WERE |
| REPEATED IN THE 2ND REVIEW. PLEASE KNOW THAT THIS FEE |
| IS ASSESSED TO THE DESIGN PROFESSIONAL UNDER FLORIDA |
| STATUTES AND IS NOT THE RESPONSIBILITY OF CONTRACTOR OR |
| OWNER. THE PLANS RETAINED FROM BOTH PREVIOUS REVIEWS |
| AND THIS REVIEW WILL BE SENT TO THE FLORIDA BOARD OF |
| PROFESSIONAL ENGINEERS FOR REVIEW. THE FEE OF $3000.00 |
| IS DUE BEFORE ANY PLANS MAY BE RE-SUBMITTED FOR REVIEW |
| FOR THE 4TH REVIEW. |
| ** PLEASE ALSO KNOW THAT TO DATE OF THIS REVIEW, NO ONE |
| HAS CONTACTED THIS REVIEWER TO GO OVER ANY COMMENTS OR |
| QUESTIONS. |
| |
| 2) NOTE: PLEASE SEE NOTES AS PREVIOUSLY STATED WITH |
| RESPECT TO SIGNING OF PLANS. NO SIGNATURE VERIFICATION |
| LETTER WAS LOCATED IN PLANS. |
| PLEASE SEE PLANS SEEM TO BE SIGNED WITH AN INITIAL OF |
| SOME SORT. IF THIS IS INDEED THE LEGAL SIGNATURES OF |
| THE DESIGNER OF RECORD PLEASE PROVIDE A SIGNED, DATED |
| AND SEALED LETTER WITH STATEMENT OF LEGAL SIGNATURE. |
| FS 471.025 |
| PLEASE BE SURE LETTER IS PROPERLY NOTARIZED UNDER |
| FLORIDA STATUTES 117.05. |
| PLEASE KNOW THIS LETTER WILL BE PLACED IN OUR SIGNATURE |
| FILE FOR ANY FUTURE REFERENCE AS NEEDED AND WILL NOT BE |
| NEED TO PROVIDE LETTER ON FUTURE PROJECTS. |
| ** PLEASE KNOW, THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| ALL TRADE REVIEWS WHETHER OR NOT COMMENT IS MADE BY |
| OTHER REVIEWER(S). |
| |
| 3) NOTE: THIS IS THE SAME COMMENT. ONLY THE NEC WAS |
| ADDED. |
| PLEASE SEE ONLY THE 2005 NEC WAS ADDED TO PLANS. |
| PLEASE SEE THE CODES WHICH WERE REQUESTED FOR OTHERS |
| WERE NOT ADDED. PLEASE SEE THAT ALL PLANS SHALL STATE |
| THE CODE IN WHICH THEY ARE DESIGNED UNDER. THIS IS |
| SUBMITTED UNDER THE NEW CODES. 2004 FBC W/ THE 2006 |
| REVISIONS. |
| |
| 4) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS |
| REVIEW. THIS IS ONE BUILDING BY DEFINITION AND ONLY ONE |
| SERVICE IS PERMITTED AND GROUPING OF MAINS IS REQUIRED. |
| PLEASE REVISE RISER FOR NEW SINGLE SERVICE. |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CORRELATE RISER AND PLANS SUBMITTED. PLEASE SEE |
| PLANS DO NOT INDICATE GROUPING OF MAINS AS RISER SEEMS |
| TO SHOW. PLEASE SEE MISSING SERVICE ENTRANCE CONDUCTORS |
| FOR NEW RISER. |
| PLEASE SEE THE RISER AS SHOWN IS NOT CODE COMPLIANT |
| WITH SEVERAL SECTIONS OF THE NEC. PLEASE SEE OTHER |
| COMMENTS RELEVANT TO THE RISER. |
| THIS IS ONE *BUILDING* BY DEFINITION IN THE FBC AND |
| ONLY ONE SERVICE PER 230.2 WILL BE GRANTED. PLANS SHOW |
| TWO DIFFERENT LOCATIONS/SERVICE METERS. |
| 230.70, 230.72, 240.4, 310.16, 310.15B6, ETC. PLEASE |
| SEE THE SIZE OF THE METER CAN, CAN NOT BE VERIFIED AS |
| NO LOAD CALCULATIONS WERE SUBMITTED. FBC 106.1.2, |
| 106.3.5.4(PARA 8) ADMIN SECTION. THERE ARE CURRENTLY |
| MANY SECTIONS BESIDES THE ONES NOTED BELOW WHICH COULD |
| NOT BE ALL TYPED IN THIS REVIEW. |
| |
| 5) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS |
| REVIEW. RISER STILL SHOWS THIS. THIS NOTE AND CODE |
| SECTION WILL BE APPLICABLE FOR NEW SERVICE ALSO. |
| PLEASE SEE 250.6, 250.24B AS NO EQUIPMENT GROUNDING |
| CONDUCTORS ARE PERMITTED BEFORE THE FIRST MEANS OF |
| DISCONNECT. |
| |
| 6) NOTE:AS THE SERVICE WILL CHANGE, THIS SAME COMMENT |
| FROM PREVIOUS REVIEW WILL REMAIN. PLEASE SEE AS THE |
| SERVICE IS NOT COMPLETE AND THE SERVICE ENTRANCE |
| CONDUCTORS ARE NOT SHOWN REVIEW FOR CODE COMPLIANCE CAN |
| NOT BE DONE. BASED ON THE SIZE OF THE GEC AS SHOWN IT |
| DOES NOT MEET THE SECTION OF THE CODE PREVIOUSLY |
| GIVEN. |
| PLEASE SEE 250.66 AS THE SIZE OF SERVICE MAY CHANGE |
| WHICH WILL DICTATE THE SIZE OF THE GROUNDING ELECTRODE |
| CONDUCTOR. |
| |
| 7) NOTE: SAME NOTE, NOTHING CHANGED. PLANS DO NOT |
| INDICATE THE REQUIRED RATINGS FOR MAIN(S).PLEASE SEE |
| ONLY THE BRACE RATING AND BRANCH CIRCUIT RATING IS |
| BEING SHOWN FOR SUB PANEL(S). |
| PLEASE SUBMIT THE AIC RATINGS FOR SERVICE MAINS PER |
| 110.9. |
| PLEASE SEE THE RATING AS SHOWN ON PANEL SCHEDULE WAS |
| NOTED, HOWEVER NEEDED FOR MAIN(S). |
| |
| 8) NOTE:THIS IS THE SAME COMMENT. THE PANEL SCHEDULE |
| IS NOT COMPLETE AND LOAD CALCULATIONS ARE NOT COMPLETE. |
| WHERE ARE LOADS ON SERVICE FOR EACH PANEL AND SERVICE |
| AS SHOWN ON RISER? PLEASE COMPLETE AND SUBMIT A |
| COMPLETE PANEL SCHEDULE WITH ALL MINIMUM REQUIRED |
| DEDICATED LOADS AS WELL AS COMPLETED LOAD CALCULATIONS |
| BASED ON MINIMUM REQUIREMENTS FROM THE NEC. |
| PLEASE SEE THE SMALL APPLIANCE CIRCUITS ARE NOT |
| CORRECT, SHOWS 4500VA FOR TWO CIRCUITS? |
| PLEASE SEE THE WASHER/ LAUNDRY LOADS WHICH ARE NOT |
| CORRECT FOR MINIMUM LOADS PER NEC. |
| PLEASE SEE NO LOAD IS SHOWN FOR A/C SYSTEM. NO LARGER |
| LOADS? ETC. |
| PLEASE SEE 220.40, 220.82, 220.52, 220.54, 220.60, ETC, |
| ETC. |
| FBC ADMIN SECTION 106.3.5.4 |
| |
| 9) NOTE: THIS IS THE SAME COMMENT AS THE PANEL SCHEDULE |
| STILL INDICATE THE DEDICATE BATH RECEPTACLE CIRCUIT ON |
| WITH GARAGE RECEPTACLES. PLEASE SEE PLANS AS PLANS DO |
| NOT INDICATE ANY KIND OF GARAGE?? |
| PLEASE SEE 210.52D, 210.11C3, AS NO OTHER LOADS ARE |
| PERMITTED ON THE DEDICATED BATH CIRCUIT(S). |
| |
| 10) NOTE: THIS IS THE SAME COMMENT. |
| PLEASE SEE 210.52C1 FOR MISSING REQUIRED GFI'S ALONG |
| KITCHEN COUNTER SPACE. |
| MISSING MINIMUM VA 220.52 |
| |
| 11) NOTE:THIS IS THE SAME COMMENT.PLEASE SEE THAT |
| THE PANEL SCHEDULE INDICATES THE DINING ROOM |
| RECEPTACLES ON WITH LIGHTING AND MANY OTHER AREAS WHICH |
| ARE NOT PERMITTED. |
| NO INFORMATION WAS SUBMITTED. |
| PLEASE SEE MISSING REQUIRED CIRCUITING FOR DINING ROOM |
| RECEPTS PER 210.52B1, 210.11C1, AND 220. 52B. |
| |
| 12) NOTE:THIS COMMENT WILL REMAIN AS NOTED ABOVE IN |
| NOTE #9 THERE ARE RECEPTACLES ALONG KITCHEN COUNTER |
| SPACE WHICH ARE STILL MISSING. |
| PLEASE SEE 210.8A6, AS ALL RECEPTS ALONG KITCHEN |
| COUNTER SPACE SHALL BE SHOWN AS GFI. |
| |
| 13) NOTE:THIS COMMENT REMAINS AS THE MINIMUM |
| CLEARANCES IN SOME OF THE CLOSETS ARE NOT MET. PLEASE |
| SEE 410.8 AS THE PC LIGHTING IN CLOSETS ARE NOT |
| PERMITTED AS SHOWN. THEY DO NOT MEET MINIMUM |
| CLEARANCES. |
| |
| 14) NOTE: PLEASE GO OVER PLANS AS SCALE STILL SEEMS TO |
| SHOW SOME NOT SPACED PER 210.52 |
| PLEASE SEE MISSING RECEPTS PER 210.52 FOR WALL |
| SPACES. |
| PLEASE SEE PLANS ARE STILL MISSING RECEPTACLES PER |
| 210.52 |
| |
| 15) NOTE:THIS COMMENT IS THE SAME FROM PREVIOUS |
| REVIEW. PLEASE SEE ALL SMOKE DEVICES ARE STILL BEING |
| SHOWN AS *SMOKE DETECTORS* AND SYMBOL LEGEND EVENS |
| STATES AND SHOWS THESE BEING 110V UNITS WHICH THESE |
| WOULD BE *SMOKE ALARMS* |
| PLANS SHOW BOTH?? |
| PLEASE SEE ALL SMOKE DEVICES SHALL BE SHOWN AS DEFINED |
| IN NFPA-72. PLEASE SEE IF THESE DEVICES AS SHOWN ARE |
| PART OF A LOW VOLTAGE ALARM SYSTEM WHICH CONTAINS |
| HORN/ALARM DEVICES THEN THE SD AS SHOWN FOR SMOKE |
| DETECTOR IS OK. IF THESE DEVICES AS SHOWN ARE DETECT |
| AND SOUND AN ALARM, THEN THEY SHALL BE SHOWN AS SA FOR |
| SMOKE ALARMS. |
| PLEASE ALSO SEE NFPA-72 11.5.1.1, 11.8.3 FOR LOCATIONS |
| REQUIRED INSIDE AND OUTSIDE ALL SLEEPING ROOMS. PLEASE |
| SEE SOME ROOMS DO NOT INDICATE THE DEVICE OUTSIDE THE |
| SLEEPING ROOM, YET INDICATE TWO DEVICES INSIDE ROOM? |
| PLEASE SEE OTHER ROOMS WHICH DO INDICATE A DEVICE |
| OUTSIDE ROOM, BUT STILL INDICATE TWO OR MORE INSIDE?? |
| |
| 16) NOTE: THIS COMMENT IS THE SAME. NO CORRECTION WAS |
| MADE. |
| PLEASE SEE MISSING DISCONNECTS FOR ALL A/C EQUIPMENT. |
| PLEASE SEE 440.11. STILL SHOWN AS RECEPTACLES WHICH ARE |
| NOT PERMITTED. |
| PLEASE SEE AHU CLOSET APPEARS TO SHOW TWO RECEPTS. |
| PLEASE KNOW AS PER 422.31, AHU'S SHALL NOT BE PLUGGED |
| IN. |
| |
| 17) NOTE: THIS IS THE SAME COMMENT. |
| PLEASE SEE 422.31 FOR DISCONNECTING MEANS REQUIRED FOR |
| WATER HEATER(S). |
| |
| |
| 18) NOTE: PLEASE SEE 422.13 FOR REQUIRED LOAD |
| CALCULATIONS FOR WATER HEATERS AS PREVIOUS PLANS DID |
| NOT SHOW LOADS, THIS COMMENT IS NEW NOW THAT LOADS ARE |
| SHOWN. |
| |
| 19) NOTE:THIS IS THE SAME COMMENT AS PLANS ARE STILL |
| MISSING SEVERAL CIRCUITS WHICH THE REVIEW CAN NOT |
| DETERMINE SPECIFIC USE OF SOME WHICH MAY NEED TO BE |
| DEDICATED CIRCUITS ETC. |
| PLEASE SEE SEVERAL ELECTRICAL DEVICES ON PLANS WHICH |
| ARE MISSING CIRCUITING. THERE ARE MANY ITEMS WHICH NEED |
| CIRCUITING TO REVIEW FOR CODE COMPLIANCE. |
| FBC 106.1.2, 106.3.5.4 |
| |
| 20) NOTE: THIS IS THE SAME COMMENT AS THE CODE REQUIRES |
| *ALL OUTLETS* IN BEDROOMS TO CONTAIN ARC FAULT |
| PROTECTION PLEASE SEE MISSING ARC FAULT PROTECTION FOR |
| ALL OUTLETS IN BEDROOMS. 210.12 THIS IS NOT ONLY |
| REQUIRED FOR RECEPTACLES. |
| |
| 21) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS |
| REVIEW. |
| PLEASE SEE SOME RECEPTACLES ARE NOT BEING SHOWN |
| SWITCHING THE ENTIRE RECEPTACLES WHICH IS OK, HOWEVER |
| AS NOTED ABOVE PER 210.52, THEN RECEPTACLES WOULD BE |
| REQUIRED IN ADDITION FOR GENERAL PURPOSE. |
| |
| 22) NOTE: THIS IS THE SAME COMMENT PLEASE SEE PLANS |
| APPEAR TO NOW HAVE ONE NEW RECEPTACLE FOR WHAT APPEARS |
| TO BE FOR THE DISHWASHER AND DISPOSAL BUT IT IS UNCLEAR |
| AS ONE UNIT SHOWS THIS OUTLET AS GFI AND THE OTHER NOT |
| GFI PROTECTED. PLEASE SEE 210.4, IF THESE ARE ON THE |
| SAME YOKE/DEVICE THEN A 2-POLE BREAKER IS REQUIRED. |
| PLEASE ALSO SHOW AND IDENTIFY THE RECEPTACLE FOR THESE |
| ON PLANS. |
| |
| 23) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS |
| REVIEW. PLEASE SHOW ALL ROOM AND AREA DESIGNATIONS ON |
| PLANS IN ORDER TO REVIEW SOME CIRCUITING FOR CODE |
| COMPLIANCE. |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 24) NOTE:PLEASE SEE AS THE ADDRESS HAS CHANGED, |
| PLEASE ADJUST TITLE BLOCKS AND REMOVE THE OLD 601 14TH |
| ST. |
| FAC 61G15-23, 61G1-16 |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |