Plan Review Notes
Plan Review Notes For Permit 06120402
Permit Number 06120402
Review Stop B
Sequence Number 3
Notes
Date Text
2007-06-01 08:37:51***NOTE: PLANS SENT TO ENGINEERING FOR REVIEW OF
 SIDEWALK AND APPROACH.
  
 BUILDING REVIEW THIRD CHECKLIST:
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 2- DRAINAGE PLAN SHOWS ARROWS LEADING THE WATER TO THE
 NEIGHBOR'S PROPERTY. WATER CAN'T BE DIVERTED TO THE
 NEIGHBOR'S PROPERTY. REVISE PLAN AS REQUIRED.
  
 3- SHEET SP-1:
 A) SIZE OF PARKING SPACESSHOWN ON SITE PLAN DON'T
 MATCH SPECIFICATIONS ON PARKING NOTES AT BOTTOM OF
 PAGE. REVISE AS REQUIRED TO MATCH.
  
 B) SITE PLAN AND SURVEY DON'T MATCH. REVISE AS
 REQUIRED. SEE SURVEY.
  
 C) REVISE ADDRESS. CORRECT ADDRESS IS 1503 AND 1507
 HENRIETTA AVE.
  
 D) DRIVEWAY TURN OUTS DETAIL DOESN'T MATCH PLANS.
  
 E) CLARIFY WHY INSTALLING BACK FLOW PREVENTER AND
 WHY ONLY ON ONE DWELLING?.
  
 F) LOCATION OF WATER METER IS WRONG. REVISE AS
 REQUIRED.
  
 G) SETBACKS SHOWN ON SITE PLAN DON'T MATCH SETBACKS
 SHOWN ON SURVEY. REVISE AS REQUIRED.
  
 H) SITE PLANAND SURVEY DON'T SHOW ALL CONCRETE
 SLABS SHOWN ON FOUNDATION PLAN. PROVIDE ALL
 INFORMATION.
  
 4- REVISE ADDRESS IN ALL DRAWINGS.
  
 5- PROVIDE TWO SURVEYS WITH CORRECT ADDRESS AND CORRECT
 DIMENSIONS. SEE FLOOR PLANS.AND SHOWING ALL CONCRETE
 SLABS.ONLY ONE SUBMITTED THIS TIME.
  
 6- SHEET S-1:
 A) DIMENSIONS ANDCOLUMN SPACINGDON'T MATCH.SEE
 PLANS. REVISE AS REQUIRED.
  
 B) THERE ARE TWO F1 FOOTING DETAILS. ONE SHOULD BE
 F1 AND THE OTHERF2. REVISE AS REQUIRED.
  
 C) FOUNDATION PLAN SHOWS CONCRETE SLAB EDGE TE AND
 TE#2. THERE IS NOT FOOTING SCHEDULE SPECIFYING WHAT ARE
 TE AND TE#2 SPECIFICATIONS. PROVIDE INFORMATION AS
 REQUIRED. AND CLARIFY WHY IS REAR CONCRETE SLAB SHOWN
 WITH DOTTED LINE.
  
 D) DIMENSIONS DON'T MATCH THOSE DIMENSIONS SHOWN ON
 SURVEY. REVISE AS REQUIRED. ALSO, DIMENSIONS DON'T
 MATCH DIMENSIONS SHOWN ON FIRST FLOOR PLAN. REVISE AS
 REQUIRED.
  
 E) REVISE TYP. EXT. CONT. MONOLITHIC FOOTING DETAIL.
 BOTTOM OF FOOTING NEEDS TO BE AT LEAST 12" BELOW GRADE.
 SEC. R403.1.4 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 F) ENGINEER TO PROVIDE CALCULATIONS SHOWING HOW
 VERTICAL REINFORCEMENT SHOWN IN FOUNDATION PLAN IS
 ADEQUATE TO PROVIDE THE REQUIRED WALL LATERAL
 STABILITY.SEE PLANS FOR COLUMN SPACING. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 G) ENGINEER TO READ SOIL TEST REPORT AND REVISE
 FOUNDATION NOTES AS REQUIRED.
  
 7- SHEET A-1:
 A) WINDOWS SPECIFIEDON PLAN DON'T MATCH.
 COORDINATE SIZE OF WINDOWS WITH WINDOW SCHEDULE AND
 WITH EXTERIOR ELEVATIONS.ALL WINDOWS ARE KEYED AS I,
 BUT THEY ARE DIFFERENT SIZES.ALSO,INSTALLATION
 SCHEDULE DOESN'T SHOW ANY I SYMBOL. THEY ARE SHOWN AS
 WINDOW 1 OR 2.ALSO, WINDOWS NOT DRAWN TO SCALE.
 COORDINATE AND REVISE AS REQUIRED.
  
 B) WINDOW ON KITCHEN AREA IS NOT AN EGRESS WINDOW.
 REVISE AS REQUIRED.
  
 C) REVISE WINDOW AND DOOR BUCK DETAILS.BUCK NEEDS
 TO PROVIDE FULLWINDOW/DOOR FRAME SUPPORT. SEE SEC.
 R613.6.2 OF 2004 FLORIDA RESIDENTIAL CODE FOR PROPER
 WAY OF INSTALLING BUCKS.
  
 D) WINDOW SILL DETAIL IS WRONG. REVISE AS REQUIRED.
  
 E) FLOOR PLAN DOESN'T SHOW REAR CONCRETE SLAB.
  
 8- SHEET A-2:
 A) DECORATIVE SHUTTERS NOTE SAYS THAT BAHAMA
 SHUTTERS ON 14TH STREET ONLY, BUT ALL ELEVATIONS SHOW
 BAHAMA SHUTTERS. REVISE AS REQUIRED.
  
 B) WINDOW SCHEDULE SHOWS WINDOW 1 WITH TRANSOM
 ABOVE. THERE ARE NOT WINDOWS WITH TRANSOM ABOVE SHOWN
 ON THE EXTERIOR ELEVATIONS. REVISE AS REQUIRED.
  
 C) OVERHANG AT FRONT OF BUILDING IS SHOWN AS 3'-0".
 THIS INFORMATION DOESN'T MATCHROOF PLAN AND TRUSS
 PLAN. REVISE AS REQUIRED.
  
 D) PROVIDE COMPLETE DETAILS FOR INSTALLATION OF ROOF
 BRACKETS AT ENTRY AREA. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 9- SHEET A-3:
 A) NEW NOTE IN THE MIDDLE OF PAGE STATES THAT
 BUILDING DESIGNED PER HVHZ.HVHZREQUIRES EXPOSURE
 "C" IN ALL DESIGN.SEE SEC. 1620.3 FBC 2004.REVISE
 INFORMATION ON TOP LEFT OF PAGE AND REVISE ALL LOAD
 CALCULATIONS AS REQUIRED.
  
 B) INFORMATION ON TOP LEFT PAGE CALLS FOR 140 MPH,
 WHILE TRUSS AND GIRDER NOTES CALLS FOR 146 MPH. REVISE
 AS REQUIRED.
  
 C) WHAT IS THE ROOF +92.0 PSFSHOWN ON TOP LEFT
 PAGE STANDS FOR?. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 D) TRUSS ANCHOR SCHEDULE:
 * ANCHORS ARE NOT KEYED CORRECTLY IN THE ROOF FRAMING
 PLAN.
  
 ** REVISE H-14 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR.
  
 *** SPECIFY SIZE OF META CONNECTOR.
  
 **** REVISE NUMBER OF FASTENERS AND LOADS FOR WHICH
 CONNECTORS ARE DESIGNED FOR. SEE CURRENT SIMPSON
 CATALOGUE AND REVISE AS REQUIRED. OTHERWISE, COMPLETE
 ENGINEERING ANALYSIS WILL BE REQUIRED FOR FASTENERS AND
 LOADS THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY
 THE MANUFACTURE. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 ***** SEE TRUSS PACKAGE AND REVISE SPECIFIED CONNECTORS
 TO RESIST THE CALCULATED LOADS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 E) ROOF PLAN SHOWS TRUSSESRUNNING FRONT TO BACK BY
 TENANT SEPARATION WALL. SEE TRUSS PLAN FOR CORRECT
 TRUSS LAYOUT AND REVISE AS REQUIRED.AND SPECIFY ALL
 TRUSS CONNECTORS AT BOTH ENDS.
  
 F) PROVIDE COMPLETE DETAILS AND SPECS FOR WOOD
 LEDGER TO RECEIVE ROOF TRUSSES. SEE TRUSS PLAN. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 G) PROVIDE COMPLETE SPECIFICATIONS FOR CONTINUITY OF
 TENANT SEPARATION WALL.SPECIFY TIE BEAM AND RAKE
 BEAM. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 H) PNEUMATIC FASTENING SCHEDULE:
 * PROVIDE ONLY THE INFORMATION THAT PERTAINS TO THIS
 PROJECT TO AVOID CONFLICTS.
  
 ** COORDINATE INFORMTIONTO MATCH WITH PLANS AND
 DETAILS. EG: CHECK ROOF SHEATHING SIZE AND BUCK DETAILS
 AND REVISE AS REQUIRED.
  
 10- PRIOR TO SUBMITTAL TO THIS OFFICE, BRING PLANS TO
 THE FIFTH FLOOR FOR HISTORICAL APPROVAL AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL PLANS.
  
 11- SHEET A-4:
 A) TENANT SEPARATION WALL DETAIL:
 * PROVIDE COMPLETE INFORMATION FOR TOP PORTION OF THE
 WALL.
  
 ** CLARIFY WHY SOFFIT ELEVATION VARIES?
  
 *** REVISE NOTE REGARDING APPROVED HURRICANE STRAPS.
 THIS IS NOT A WOOD FRAMED WALL.
  
 **** CONCRETE SLAB INFORMATION DOESN'T MATCH FOUNDATION
 PLAN. REVISE AS REQUIRED.
  
 ***** DETAIL FOR VERTICAL REINFORCEMENT IS DRAWN
 INCORRRECTLY.PROVIDE COMPLETE SPECIFICATIONS FOR
 VERTICAL REINFORCEMENT INCLUDING SPLICING ETC.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 ****** HOW ARE THE TRUSSES RESTING ON THIS WALL?
  
 B) WHERE DOES THE STRAP AND TIE DOWN DETAIL APPLIES
 TO?SEC. 106.1.2CITY AMENDMENTS TO FBC 2004.
  
 C) TYPICAL WALL SECTION:
 * TRUSS CONNECTOR INFORMATION TO MATCH TRUSS ANCHOR
 SCHEDULE.
  
 ** SPECIFY MIN. FOOTING DEPTH AS REQUIRED BY SEC.
 R403.1.4 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 12- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING CORRECT ADDRESS AND BUILDER.
  
 B) PROVIDE REVISED FORM 600A-2004 R.
  
 C) IF CALCULATIONS ARE NOT DONE FOR WORST CASE
 SCENARIO, THEN THEY SHALL BE DONE WITH ACTUAL BUILDING
 ORIENTATION. SEE SURVEY FOR CORRECT ORIENTATION.
  
 D) ENGINEER TO PROVIDE HIS NAME AND LICENSE NUMBER
 AS REQUIRED BY CHAPTER 471 OF FLORIDA STATUTE.
  
 E) OVERHANG HEIGHT AND OVERHANG LENGTH ARE
 INCORRECT. THEY CAN'T BE ZERO. REVISE AS REQUIRED.
  
 13- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. THEREFORE NEED TO SPECIFY IN DRAWINGS CEILING
 FAN SIZE IN ALL ROOMS AS REQUIRED BY TABLE 13-607.1.A.1
 FBC 2004.
  
 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) ROOF SHINGLES.
  
 B) PRECAST LINTELS.
  
 C) ALL TRUSS CONNECTORS SPECIFIED ON PLANS.
  
 15- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: SOME PRODUCT APPROVALS HAVE THE REVIEW STAMP
 FROM AMD GROUP. WHO IS THIS?THE ENGINEER OF RECORD IS
 DM & L ENGINEERING.
  
 16- PROVIDE 2 SURVEYS WITH CORRECT ADDRESS.
  
 17- ENGINEER WAS CHARGED 4 TIMES FEE FOR PLAN REVIEW
 FOR MULTIPLE DENIED CHECKLIST AS REQUIRED BY FLORIDA
 STATUTE 553.80(2)(B).SEE ATTACHED COPY.ENGINEER
 OWES $3362.34.
  
 18- TRUSS PACKAGE:
 A) TRUSSES NEED TO BE DESIGNED USING ASCE 7-02NOT
 ASCE 7-05.REVISE AS REQUIRED.
  
 B) ENGINEER TO DATE DRAWINGS WHEN SEAL IS IMPRESSED
 AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 C) GENERAL DETAILS ARE TOO DARK AND ARE NOT
 LEGIBLE.
  
 D) WHO'S ADM GROUP?.THIS IS NOT THE ENGINEER OF
 RECORD.
  
 D) REVISED TRUSS PACKAGE TO BE SUBMITTED TO BUILDING
 INSPECTOR AT TIME OF FRAMING INSPECTION.
  
 19- SOIL TEST REPORT:
 A) MISSING KEY PLAN SHOWING LOCATION OF BORINGS.
  
 B) ENGINEER TO PROVIDE THE COMPANY CERTIFICATE OF
 AUTHORIZATION NUMBER IN THE LETTERHEAD AS REQUIRED BY
 SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 ***NOTE:
 * PLEASE DON'T ATTACHPRODUCT APPROVALS TO PLANS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712