Date |
Text |
2007-06-01 08:37:51 | ***NOTE: PLANS SENT TO ENGINEERING FOR REVIEW OF |
| SIDEWALK AND APPROACH. |
| |
| BUILDING REVIEW THIRD CHECKLIST: |
| 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| |
| 2- DRAINAGE PLAN SHOWS ARROWS LEADING THE WATER TO THE |
| NEIGHBOR'S PROPERTY. WATER CAN'T BE DIVERTED TO THE |
| NEIGHBOR'S PROPERTY. REVISE PLAN AS REQUIRED. |
| |
| 3- SHEET SP-1: |
| A) SIZE OF PARKING SPACESSHOWN ON SITE PLAN DON'T |
| MATCH SPECIFICATIONS ON PARKING NOTES AT BOTTOM OF |
| PAGE. REVISE AS REQUIRED TO MATCH. |
| |
| B) SITE PLAN AND SURVEY DON'T MATCH. REVISE AS |
| REQUIRED. SEE SURVEY. |
| |
| C) REVISE ADDRESS. CORRECT ADDRESS IS 1503 AND 1507 |
| HENRIETTA AVE. |
| |
| D) DRIVEWAY TURN OUTS DETAIL DOESN'T MATCH PLANS. |
| |
| E) CLARIFY WHY INSTALLING BACK FLOW PREVENTER AND |
| WHY ONLY ON ONE DWELLING?. |
| |
| F) LOCATION OF WATER METER IS WRONG. REVISE AS |
| REQUIRED. |
| |
| G) SETBACKS SHOWN ON SITE PLAN DON'T MATCH SETBACKS |
| SHOWN ON SURVEY. REVISE AS REQUIRED. |
| |
| H) SITE PLANAND SURVEY DON'T SHOW ALL CONCRETE |
| SLABS SHOWN ON FOUNDATION PLAN. PROVIDE ALL |
| INFORMATION. |
| |
| 4- REVISE ADDRESS IN ALL DRAWINGS. |
| |
| 5- PROVIDE TWO SURVEYS WITH CORRECT ADDRESS AND CORRECT |
| DIMENSIONS. SEE FLOOR PLANS.AND SHOWING ALL CONCRETE |
| SLABS.ONLY ONE SUBMITTED THIS TIME. |
| |
| 6- SHEET S-1: |
| A) DIMENSIONS ANDCOLUMN SPACINGDON'T MATCH.SEE |
| PLANS. REVISE AS REQUIRED. |
| |
| B) THERE ARE TWO F1 FOOTING DETAILS. ONE SHOULD BE |
| F1 AND THE OTHERF2. REVISE AS REQUIRED. |
| |
| C) FOUNDATION PLAN SHOWS CONCRETE SLAB EDGE TE AND |
| TE#2. THERE IS NOT FOOTING SCHEDULE SPECIFYING WHAT ARE |
| TE AND TE#2 SPECIFICATIONS. PROVIDE INFORMATION AS |
| REQUIRED. AND CLARIFY WHY IS REAR CONCRETE SLAB SHOWN |
| WITH DOTTED LINE. |
| |
| D) DIMENSIONS DON'T MATCH THOSE DIMENSIONS SHOWN ON |
| SURVEY. REVISE AS REQUIRED. ALSO, DIMENSIONS DON'T |
| MATCH DIMENSIONS SHOWN ON FIRST FLOOR PLAN. REVISE AS |
| REQUIRED. |
| |
| E) REVISE TYP. EXT. CONT. MONOLITHIC FOOTING DETAIL. |
| BOTTOM OF FOOTING NEEDS TO BE AT LEAST 12" BELOW GRADE. |
| SEC. R403.1.4 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| F) ENGINEER TO PROVIDE CALCULATIONS SHOWING HOW |
| VERTICAL REINFORCEMENT SHOWN IN FOUNDATION PLAN IS |
| ADEQUATE TO PROVIDE THE REQUIRED WALL LATERAL |
| STABILITY.SEE PLANS FOR COLUMN SPACING. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| G) ENGINEER TO READ SOIL TEST REPORT AND REVISE |
| FOUNDATION NOTES AS REQUIRED. |
| |
| 7- SHEET A-1: |
| A) WINDOWS SPECIFIEDON PLAN DON'T MATCH. |
| COORDINATE SIZE OF WINDOWS WITH WINDOW SCHEDULE AND |
| WITH EXTERIOR ELEVATIONS.ALL WINDOWS ARE KEYED AS I, |
| BUT THEY ARE DIFFERENT SIZES.ALSO,INSTALLATION |
| SCHEDULE DOESN'T SHOW ANY I SYMBOL. THEY ARE SHOWN AS |
| WINDOW 1 OR 2.ALSO, WINDOWS NOT DRAWN TO SCALE. |
| COORDINATE AND REVISE AS REQUIRED. |
| |
| B) WINDOW ON KITCHEN AREA IS NOT AN EGRESS WINDOW. |
| REVISE AS REQUIRED. |
| |
| C) REVISE WINDOW AND DOOR BUCK DETAILS.BUCK NEEDS |
| TO PROVIDE FULLWINDOW/DOOR FRAME SUPPORT. SEE SEC. |
| R613.6.2 OF 2004 FLORIDA RESIDENTIAL CODE FOR PROPER |
| WAY OF INSTALLING BUCKS. |
| |
| D) WINDOW SILL DETAIL IS WRONG. REVISE AS REQUIRED. |
| |
| E) FLOOR PLAN DOESN'T SHOW REAR CONCRETE SLAB. |
| |
| 8- SHEET A-2: |
| A) DECORATIVE SHUTTERS NOTE SAYS THAT BAHAMA |
| SHUTTERS ON 14TH STREET ONLY, BUT ALL ELEVATIONS SHOW |
| BAHAMA SHUTTERS. REVISE AS REQUIRED. |
| |
| B) WINDOW SCHEDULE SHOWS WINDOW 1 WITH TRANSOM |
| ABOVE. THERE ARE NOT WINDOWS WITH TRANSOM ABOVE SHOWN |
| ON THE EXTERIOR ELEVATIONS. REVISE AS REQUIRED. |
| |
| C) OVERHANG AT FRONT OF BUILDING IS SHOWN AS 3'-0". |
| THIS INFORMATION DOESN'T MATCHROOF PLAN AND TRUSS |
| PLAN. REVISE AS REQUIRED. |
| |
| D) PROVIDE COMPLETE DETAILS FOR INSTALLATION OF ROOF |
| BRACKETS AT ENTRY AREA. SEC. 106.1.2 CITY AMENDMENTS TO |
| FBC 2004. |
| |
| 9- SHEET A-3: |
| A) NEW NOTE IN THE MIDDLE OF PAGE STATES THAT |
| BUILDING DESIGNED PER HVHZ.HVHZREQUIRES EXPOSURE |
| "C" IN ALL DESIGN.SEE SEC. 1620.3 FBC 2004.REVISE |
| INFORMATION ON TOP LEFT OF PAGE AND REVISE ALL LOAD |
| CALCULATIONS AS REQUIRED. |
| |
| B) INFORMATION ON TOP LEFT PAGE CALLS FOR 140 MPH, |
| WHILE TRUSS AND GIRDER NOTES CALLS FOR 146 MPH. REVISE |
| AS REQUIRED. |
| |
| C) WHAT IS THE ROOF +92.0 PSFSHOWN ON TOP LEFT |
| PAGE STANDS FOR?. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| 2004. |
| |
| D) TRUSS ANCHOR SCHEDULE: |
| * ANCHORS ARE NOT KEYED CORRECTLY IN THE ROOF FRAMING |
| PLAN. |
| |
| ** REVISE H-14 CONNECTOR. NEED TO SPECIFY WOOD TO |
| MASONRY CONNECTOR. |
| |
| *** SPECIFY SIZE OF META CONNECTOR. |
| |
| **** REVISE NUMBER OF FASTENERS AND LOADS FOR WHICH |
| CONNECTORS ARE DESIGNED FOR. SEE CURRENT SIMPSON |
| CATALOGUE AND REVISE AS REQUIRED. OTHERWISE, COMPLETE |
| ENGINEERING ANALYSIS WILL BE REQUIRED FOR FASTENERS AND |
| LOADS THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY |
| THE MANUFACTURE. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| 2004. |
| |
| ***** SEE TRUSS PACKAGE AND REVISE SPECIFIED CONNECTORS |
| TO RESIST THE CALCULATED LOADS. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| E) ROOF PLAN SHOWS TRUSSESRUNNING FRONT TO BACK BY |
| TENANT SEPARATION WALL. SEE TRUSS PLAN FOR CORRECT |
| TRUSS LAYOUT AND REVISE AS REQUIRED.AND SPECIFY ALL |
| TRUSS CONNECTORS AT BOTH ENDS. |
| |
| F) PROVIDE COMPLETE DETAILS AND SPECS FOR WOOD |
| LEDGER TO RECEIVE ROOF TRUSSES. SEE TRUSS PLAN. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| G) PROVIDE COMPLETE SPECIFICATIONS FOR CONTINUITY OF |
| TENANT SEPARATION WALL.SPECIFY TIE BEAM AND RAKE |
| BEAM. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| H) PNEUMATIC FASTENING SCHEDULE: |
| * PROVIDE ONLY THE INFORMATION THAT PERTAINS TO THIS |
| PROJECT TO AVOID CONFLICTS. |
| |
| ** COORDINATE INFORMTIONTO MATCH WITH PLANS AND |
| DETAILS. EG: CHECK ROOF SHEATHING SIZE AND BUCK DETAILS |
| AND REVISE AS REQUIRED. |
| |
| 10- PRIOR TO SUBMITTAL TO THIS OFFICE, BRING PLANS TO |
| THE FIFTH FLOOR FOR HISTORICAL APPROVAL AFTER |
| CORRECTIONS ARE DONE TO THE ORIGINAL PLANS. |
| |
| 11- SHEET A-4: |
| A) TENANT SEPARATION WALL DETAIL: |
| * PROVIDE COMPLETE INFORMATION FOR TOP PORTION OF THE |
| WALL. |
| |
| ** CLARIFY WHY SOFFIT ELEVATION VARIES? |
| |
| *** REVISE NOTE REGARDING APPROVED HURRICANE STRAPS. |
| THIS IS NOT A WOOD FRAMED WALL. |
| |
| **** CONCRETE SLAB INFORMATION DOESN'T MATCH FOUNDATION |
| PLAN. REVISE AS REQUIRED. |
| |
| ***** DETAIL FOR VERTICAL REINFORCEMENT IS DRAWN |
| INCORRRECTLY.PROVIDE COMPLETE SPECIFICATIONS FOR |
| VERTICAL REINFORCEMENT INCLUDING SPLICING ETC.SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| ****** HOW ARE THE TRUSSES RESTING ON THIS WALL? |
| |
| B) WHERE DOES THE STRAP AND TIE DOWN DETAIL APPLIES |
| TO?SEC. 106.1.2CITY AMENDMENTS TO FBC 2004. |
| |
| C) TYPICAL WALL SECTION: |
| * TRUSS CONNECTOR INFORMATION TO MATCH TRUSS ANCHOR |
| SCHEDULE. |
| |
| ** SPECIFY MIN. FOOTING DEPTH AS REQUIRED BY SEC. |
| R403.1.4 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 12- ENERGY CALCULATIONS: |
| A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING CORRECT ADDRESS AND BUILDER. |
| |
| B) PROVIDE REVISED FORM 600A-2004 R. |
| |
| C) IF CALCULATIONS ARE NOT DONE FOR WORST CASE |
| SCENARIO, THEN THEY SHALL BE DONE WITH ACTUAL BUILDING |
| ORIENTATION. SEE SURVEY FOR CORRECT ORIENTATION. |
| |
| D) ENGINEER TO PROVIDE HIS NAME AND LICENSE NUMBER |
| AS REQUIRED BY CHAPTER 471 OF FLORIDA STATUTE. |
| |
| E) OVERHANG HEIGHT AND OVERHANG LENGTH ARE |
| INCORRECT. THEY CAN'T BE ZERO. REVISE AS REQUIRED. |
| |
| 13- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN |
| CREDIT. THEREFORE NEED TO SPECIFY IN DRAWINGS CEILING |
| FAN SIZE IN ALL ROOMS AS REQUIRED BY TABLE 13-607.1.A.1 |
| FBC 2004. |
| |
| 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| FOR: |
| A) ROOF SHINGLES. |
| |
| B) PRECAST LINTELS. |
| |
| C) ALL TRUSS CONNECTORS SPECIFIED ON PLANS. |
| |
| 15- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| ***NOTE: SOME PRODUCT APPROVALS HAVE THE REVIEW STAMP |
| FROM AMD GROUP. WHO IS THIS?THE ENGINEER OF RECORD IS |
| DM & L ENGINEERING. |
| |
| 16- PROVIDE 2 SURVEYS WITH CORRECT ADDRESS. |
| |
| 17- ENGINEER WAS CHARGED 4 TIMES FEE FOR PLAN REVIEW |
| FOR MULTIPLE DENIED CHECKLIST AS REQUIRED BY FLORIDA |
| STATUTE 553.80(2)(B).SEE ATTACHED COPY.ENGINEER |
| OWES $3362.34. |
| |
| 18- TRUSS PACKAGE: |
| A) TRUSSES NEED TO BE DESIGNED USING ASCE 7-02NOT |
| ASCE 7-05.REVISE AS REQUIRED. |
| |
| B) ENGINEER TO DATE DRAWINGS WHEN SEAL IS IMPRESSED |
| AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| |
| C) GENERAL DETAILS ARE TOO DARK AND ARE NOT |
| LEGIBLE. |
| |
| D) WHO'S ADM GROUP?.THIS IS NOT THE ENGINEER OF |
| RECORD. |
| |
| D) REVISED TRUSS PACKAGE TO BE SUBMITTED TO BUILDING |
| INSPECTOR AT TIME OF FRAMING INSPECTION. |
| |
| 19- SOIL TEST REPORT: |
| A) MISSING KEY PLAN SHOWING LOCATION OF BORINGS. |
| |
| B) ENGINEER TO PROVIDE THE COMPANY CERTIFICATE OF |
| AUTHORIZATION NUMBER IN THE LETTERHEAD AS REQUIRED BY |
| SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| |
| ***NOTE: |
| * PLEASE DON'T ATTACHPRODUCT APPROVALS TO PLANS. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |