2007-03-14 14:05:56DENIED;
 1. CA# MISSING FROM TITLE BLOCK
 2. PLUMBING NOTES;NOTE# 5. WATER HAMMER ARRESTORS TO
 BE USED PER FBC-2004 PLUMBING SECTION 604.9. AIR
 CHAMBERS ARE NOT AND ENGINEERED AND APPROVED PRODUCT.
 NOTE# 9HORIZONTAL DRAIN LINES TO SLOPE PER TABLE
 704.1 PIPES LESS THAN 2 1/2" IN DIAMETER OR SMALLER
 MUST SLOPE 1/4" PER FT. NOTE #12 GAS PIPING IS A
 SEPARATE PERMIT. PLANS MUST BE SUBMITED BY THE PLUMBING
 CONTRACTOR IF NATURAL GAS IS BEING USED. REMOVE NOTE 12
 FROM PLANS.
 3. RISER DIAGRAM;BATHROOM #2 SHOWER NOT VENTED. FLOOR
 PLAN SHOWS ALL SHOWERS, RISER DIAGRAM CALLS THEM TUBS
 PLEASE COORDINATE. BOTH MASTER BATHROOMS ARE ON THE
 RISER DIAGRAM. ONLY ONE SHOULD BE SHOWN IF EACH UNIT
 HAS IT'S OWN SEWER.