Plan Review Notes For Permit 06120402 |
Permit Number |
06120402 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-03-14 14:05:56 | DENIED; | | 1. CA# MISSING FROM TITLE BLOCK | | 2. PLUMBING NOTES;NOTE# 5. WATER HAMMER ARRESTORS TO | | BE USED PER FBC-2004 PLUMBING SECTION 604.9. AIR | | CHAMBERS ARE NOT AND ENGINEERED AND APPROVED PRODUCT. | | NOTE# 9HORIZONTAL DRAIN LINES TO SLOPE PER TABLE | | 704.1 PIPES LESS THAN 2 1/2" IN DIAMETER OR SMALLER | | MUST SLOPE 1/4" PER FT. NOTE #12 GAS PIPING IS A | | SEPARATE PERMIT. PLANS MUST BE SUBMITED BY THE PLUMBING | | CONTRACTOR IF NATURAL GAS IS BEING USED. REMOVE NOTE 12 | | FROM PLANS. | | 3. RISER DIAGRAM;BATHROOM #2 SHOWER NOT VENTED. FLOOR | | PLAN SHOWS ALL SHOWERS, RISER DIAGRAM CALLS THEM TUBS | | PLEASE COORDINATE. BOTH MASTER BATHROOMS ARE ON THE | | RISER DIAGRAM. ONLY ONE SHOULD BE SHOWN IF EACH UNIT | | HAS IT'S OWN SEWER. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|