Plan Review Notes
Plan Review Notes For Permit 06120402
Permit Number 06120402
Review Stop M
Sequence Number 2
Notes
Date Text
2007-03-12 10:04:24*** DENIED ***
 1) SEE MECHANICAL PLANS PAGE MEP-2 OF 2 "A/C NOTES",
 10,000 TOTAL, 1410KW, AND 13,331 SENS, IS INCORRECT FOR
 A THREE TON A/C SYSTEM, PLEASE OBTAIN THE
 MANUFACTURER'S SPECIFICATION'S AND INTER THE CORRECT
 INFORMATION.
  
 2) COULD NOT FIND THE TRANE A/C SYSTEM LISTED ON THE
 PLANS IN THE ARI DIRECTORY, PLEASE SUBMIT DETAILED
 MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR A/C SYSTEM TO BE INSTALLED.
  
 3) AS NOTED IN LAST REVIEW 12/19/06 NOTE #2. PLEASE SEE
 THE MANUAL J CALCULATIONS ARE CALLING FOR A SMALLER A/C
 SYSTEM THEN THE MECHANICAL PLANS ARE, THEIR FORTHE
 PLANS WOULD NEED TO LIST A SMALLER A/C SYSTEM TO BE
 INSTALLED, SEE 2004 FBC 13-607.ABC.1.1.
  
 4) AS NOTED IN LAST REVIEW 12/19/06 NOTE #3. THE ENERGY
 CALCULATIONS SUBMITTED ARE INCORRECT, PLEASE SUBMIT
 CORRECTED ENERGY CALCULATIONS, SEE 2004 FBC 13-101.2.
  
 5) SEE ENERGY CALCULATIONS #15 IS TAKING THE CF CREDIT,
 ELECTRICAL PLANS SHOW FUTURE FANS, CREDIT MAY NOT BE
 TAKEN FOR FUTURE WORK.
  
 6) PLEASE SEE YELLOW HIGH LIGHTS ON ENERGY CALCULATIONS
 AND MECHANICAL PLANS, PLEASE CORRECT.
  
 7) AS NOTED IN LAST REVIEW 12/19/06 NOTE #4.THE 12X6
 RETURN AIR TRANSFER GRILLS TO THE BEDROOMS ARE TO
 SMALL. BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 8) MECHANICAL PLANS NOW SHOW NEW 12X12 GRILLS AND
 UNKNOWN DUCTS (YELLOW HIGH LIGHTED) IN EACH ROOM,
 PLEASE REMOVE OR CORRECT.
  
 9) SEE TITLE BLOCK ON PLANS IS SHOWING D M & L
 ENGINEERING CORP. "C.O.A. #10784" . CHECKED DBPR WEB
 SITE AND FOUND NO C. O. A. NUMBER OR COMPANY LISTED.
 SEE FAC 61G15-23.002 (2) AND COMPLY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.