2007-03-09 19:00:58 | ** UNSAT 2ND REVIEW ** |
| |
| |
| ** PLEASE SEE THERE ARE MANY COMMENTS FROM THE PREVIOUS |
| REVIEW WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH |
| SEVERAL NEW COMMENTS DUE TO CHANGES IN THE PLANS |
| SUBMITTED. |
| |
| ** PLEASE KNOW A RESPONSE LETTER FROM THE DESIGN |
| PROFESSIONAL IS MOST HELPFUL IN THE REVIEW PROCESS. |
| |
| *** PLEASE ALSO KNOW DUE TO THE PLANS NOT BEING |
| COMPLETE AT THIS TIME AND THE FOLLOWING COMMENTS FOR |
| PLANS SUBMITTED, THERE MAY BE COMMENTS ON NEXT REVIEW |
| WHICH ARE NOT ON THIS REVIEW. |
| **DUE TO THE EXTENT OF THE ELECTRICAL COMMENTS AND |
| OTHER COMMENTS BASED ON LICENSING, ONE SET OF THE |
| ELECTRICAL PLANS ARE ONCE AGAIN BEING RETAINED. PLEASE |
| SEE NEW COMMENTS ADDED TO THIS REVIEW AND COMMENT WITH |
| RESPECT TO FLORIDA STATUTES FOR REPEAT COMMENTS. |
| |
| 1) NOTE:PLEASE SEE THIS MOSTLY THE SAME COMMENT. ONLY |
| A NEW SEAL WAS USED WHEN PLANS WERE SIGNED AND SEALED. |
| PLEASE SEE THAT THE MISSING CA # IS STILL NOT ON ANY |
| TITLE BLOCKS. PLEASE SEE THE PRINTED NAME IS NOT THE |
| SAME AS IN SEAL. PLEASE SEE NO LETTER FOR SIGNATURE |
| VERIFICATION WAS SUBMITTED. PLEASE SEE FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.002 FOR MISSING LICENSING |
| INFORMATION REQUIRED. PLEASE SEE MISSING CERTIFICATE OF |
| AUTHORIZATION NUMBER AND SOME SHEETS ARE NOT COMPLETE |
| WITH OTHER INFORMATION AS REQUIRED. |
| FLORIDA STATUTES 471.023 |
| PLEASE SEE PLANS SEEM TO BE SIGNED WITH AN INITIAL OF |
| SOME SORT. IF THIS IS INDEED THE LEGAL SIGNATURES OF |
| THE DESIGNER OF RECORD PLEASE PROVIDE A SIGNED, DATED |
| AND SEALED LETTER WITH STATEMENT OF LEGAL SIGNATURE. |
| PLEASE BE SURE LETTER IS PROPERLY NOTARIZED UNDER |
| FLORIDA STATUTES 117.05. |
| PLEASE KNOW THIS LETTER WILL BE PLACED IN OUR SIGNATURE |
| FILE FOR ANY FUTURE REFERENCE AS NEEDED AND WILL NOT BE |
| NEED TO PROVIDE LETTER ON FUTURE PROJECTS. |
| ** PLEASE KNOW, THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| ALL TRADE REVIEWS WHETHER OR NOT COMMENT IS MADE BY |
| OTHER REVIEWER(S). |
| |
| 2) NOTE: PLEASE SEE ONLY THE 2005 NEC WAS ADDED TO |
| PLANS. PLEASE SEE THE CODES WHICH WERE REQUESTED FOR |
| OTHERS WERE NOT ADDED. PLEASE SEE THAT ALL PLANS SHALL |
| STATE THE CODE IN WHICH THEY ARE DESIGNED UNDER. THIS |
| IS SUBMITTED UNDER THE NEW CODES. 2004 FBC W/ THE 2006 |
| REVISIONS. |
| |
| PLEASE SEE THE FOLLOWING CODES SHALL BE STATED ON |
| PLANS. |
| NFPA-70 2005, 2002 NFPA-72 |
| PLEASE KNOW BASED ON THE FACT THAT THE PLANS WERE |
| SUBMITTED FOR PERMITTING AFTER THE DATE OF DEC 8TH, |
| 2006, THE PLANS SHALL BE DESIGNED UNDER THE 2005 NEC. |
| |
| 3) NOTE: PLEASE CORRELATE RISER AND PLANS SUBMITTED. |
| PLEASE SEE PLANS DO NOT INDICATE GROUPING OF MAINS AS |
| RISER SEEMS TO SHOW. PLEASE SEE MISSING SERVICE |
| ENTRANCE CONDUCTORS FOR NEW RISER. |
| PLEASE SEE THE RISER AS SHOWN IS NOT CODE COMPLIANT |
| WITH SEVERAL SECTIONS OF THE NEC. PLEASE SEE OTHER |
| COMMENTS RELEVANT TO THE RISER. |
| THIS IS ONE *BUILDING* BY DEFINITION IN THE FBC AND |
| ONLY ONE SERVICE PER 230.2 WILL BE GRANTED. PLANS SHOW |
| TWO DIFFERENT LOCATIONS/SERVICE METERS. |
| 230.70, 230.72, 240.4, 310.16, 310.15B6, ETC. PLEASE |
| SEE THE SIZE OF THE METER CAN, CAN NOT BE VERIFIED AS |
| NO LOAD CALCULATIONS WERE SUBMITTED. FBC 106.1.2, |
| 106.3.5.4(PARA 8) ADMIN SECTION. THERE ARE CURRENTLY |
| MANY SECTIONS BESIDES THE ONES NOTED BELOW WHICH COULD |
| NOT BE ALL TYPED IN THIS REVIEW. |
| |
| 4) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS |
| REVIEW. |
| PLEASE SEE 250.6, 250.24B AS NO EQUIPMENT GROUNDING |
| CONDUCTORS ARE PERMITTED BEFORE THE FIRST MEANS OF |
| DISCONNECT. |
| |
| 5) NOTE: THIS IS THE SAME COMMENT FROM PREVIOUS REVIEW. |
| PLEASE SEE AS THE SERVICE IS NOT COMPLETE AND THE |
| SERVICE ENTRANCE CONDUCTORS ARE NOT SHOWN REVIEW FOR |
| CODE COMPLIANCE CAN NOT BE DONE. BASED ON THE SIZE OF |
| THE GEC AS SHOWN IT DOES NOT MEET THE SECTION OF THE |
| CODE PREVIOUSLY GIVEN. |
| PLEASE SEE 250.66 AS THE SIZE OF SERVICE MAY CHANGE |
| WHICH WILL DICTATE THE SIZE OF THE GROUNDING ELECTRODE |
| CONDUCTOR. |
| |
| 6) NOTE: NO, PLEASE SEE ONLY THE BRACE RATING AND |
| BRANCH CIRCUIT RATING IS BEING SHOWN. |
| PLEASE SUBMIT THE AIC RATINGS FOR SERVICE MAINS PER |
| 110.9. |
| PLEASE SEE THE RATING AS SHOWN ON PANEL SCHEDULE WAS |
| NOTED, HOWEVER NEEDED FOR MAIN(S). |
| |
| 7) NOTE:THIS IS THE SAME COMMENT. PANEL SCHEDULE IS |
| COMPLETELY BLANK FOR LOAD CALCULATIONS AND FOR LOAD ON |
| SERVICE FOR EACH PANEL AND SERVICE AS SHOWN ON RISER. |
| PLEASE COMPLETE AND SUBMIT A COMPLETE PANEL SCHEDULE |
| WITH ALL MINIMUM REQUIRED DEDICATED LOADS AS WELL AS |
| COMPLETED LOAD CALCULATIONS BASED ON MINIMUM |
| REQUIREMENTS FROM THE NEC. |
| PLEASE SEE 220.40, 220.82, 220.52, 220.54, 220.60, ETC, |
| ETC. |
| FBC ADMIN SECTION 106.3.5.4 |
| |
| 8) NOTE: THIS IS THE SAME COMMENT AS THE PANEL SCHEDULE |
| STILL INDICATE THE DEDICATE BATH RECEPTACLE CIRCUIT ON |
| WITH GARAGE RECEPTACLES. PLEASE SEE PLANS AS PLANS DO |
| NOT INDICATE ANY KIND OF GARAGE?? |
| PLEASE SEE 210.52D, 210.11C3, AS NO OTHER LOADS ARE |
| PERMITTED ON THE DEDICATED BATH CIRCUIT(S). |
| |
| 9) NOTE: THIS IS THE SAME COMMENT. |
| PLEASE SEE 210.52C1 FOR MISSING REQUIRED GFI'S ALONG |
| KITCHEN COUNTER SPACE. |
| MISSING MINIMUM VA 220.52 |
| |
| 10) NOTE:THIS IS THE SAME COMMENT.PLEASE SEE THAT |
| THE PANEL SCHEDULE INDICATES THE DINING ROOM |
| RECEPTACLES ON WITH LIGHTING AND MANY OTHER AREAS WHICH |
| ARE NOT PERMITTED. |
| NO INFORMATION WAS SUBMITTED. |
| PLEASE SEE MISSING REQUIRED CIRCUITING FOR DINING ROOM |
| RECEPTS PER 210.52B1, 210.11C1, AND 220. 52B. |
| |
| 11) NOTE:THIS COMMENT WILL REMAIN AS NOTED ABOVE IN |
| NOTE #9 THERE ARE RECEPTACLES ALONG KITCHEN COUNTER |
| SPACE WHICH ARE STILL MISSING. |
| PLEASE SEE 210.8A6, AS ALL RECEPTS ALONG KITCHEN |
| COUNTER SPACE SHALL BE SHOWN AS GFI. |
| |
| 12) NOTE: THIS COMMENT REMAINS AS THE MINIMUM |
| CLEARANCES IN SOME OF THE CLOSETS ARE NOT MET. PLEASE |
| SEE 410.8 AS THE PC LIGHTING IN CLOSETS ARE NOT |
| PERMITTED AS SHOWN. THEY DO NOT MEET MINIMUM |
| CLEARANCES. |
| |
| 13) NOTE: PLEASE GO OVER PLANS AS SCALE STILL SEEMS TO |
| SHOW SOME NOT SPACED PER 210.52 |
| PLEASE SEE MISSING RECEPTS PER 210.52 FOR WALL |
| SPACES. |
| |
| 14) NOTE:THIS COMMENT IS FROM PREVIOUS REVIEW. PLEASE |
| SEE ALL SMOKE DEVICES ARE STILL BEING SHOWN AS *SMOKE |
| DETECTORS* AND SYMBOL LEGEND EVENS STATES AND SHOWS |
| THESE BEING 110V UNITS WHICH THESE WOULD BE *SMOKE |
| ALARMS* |
| PLEASE SEE ALL SMOKE DEVICES SHALL BE SHOWN AS DEFINED |
| IN NFPA-72. PLEASE SEE IF THESE DEVICES AS SHOWN ARE |
| PART OF A LOW VOLTAGE ALARM SYSTEM WHICH CONTAINS |
| HORN/ALARM DEVICES THEN THE SD AS SHOWN FOR SMOKE |
| DETECTOR IS OK. IF THESE DEVICES AS SHOWN ARE DETECT |
| AND SOUND AN ALARM, THEN THEY SHALL BE SHOWN AS SA FOR |
| SMOKE ALARMS. |
| PLEASE ALSO SEE NFPA-72 11.5.1.1, 11.8.3 FOR LOCATIONS |
| REQUIRED INSIDE AND OUTSIDE ALL SLEEPING ROOMS. PLEASE |
| SEE SOME ROOMS DO NOT INDICATE THE DEVICE OUTSIDE THE |
| SLEEPING ROOM, YET INDICATE TWO DEVICES INSIDE ROOM? |
| PLEASE SEE OTHER ROOMS WHICH DO INDICATE A DEVICE |
| OUTSIDE ROOM, BUT STILL INDICATE TWO OR MORE INSIDE?? |
| |
| 15) NOTE: THIS COMMENT IS THE SAME. NO CORRECTION WAS |
| MADE. |
| PLEASE SEE MISSING DISCONNECTS FOR ALL A/C EQUIPMENT. |
| PLEASE SEE 440.11. |
| PLEASE SEE AHU CLOSET APPEARS TO SHOW TWO RECEPTS. |
| PLEASE KNOW AS PER 422.31, AHU'S SHALL NOT BE PLUGGED |
| IN. |
| |
| 16) NOTE: THIS IS THE SAME COMMENT. |
| PLEASE SEE 422.31 FOR DISCONNECTING MEANS REQUIRED FOR |
| WATER HEATER(S). |
| |
| 17) NOTE: OK. |
| |
| 18) NOTE: OK. |
| |
| ** NEW NOTES** |
| |
| 19) NOTE: PLEASE SEE SEVERAL ELECTRICAL DEVICES ON |
| PLANS WHICH ARE MISSING CIRCUITING. THERE ARE MANY |
| ITEMS WHICH NEED CIRCUITING TO REVIEW FOR CODE |
| COMPLIANCE. |
| FBC 106.1.2, 106.3.5.4 |
| |
| 20) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION FOR |
| ALL OUTLETS IN BEDROOMS. 210.12 THIS IS NOT ONLY |
| REQUIRED FOR RECEPTACLES. |
| |
| 21) NOTE: PLEASE SEE SOME RECEPTACLES ARE NOT BEING |
| SHOWN SWITCHING THE ENTIRE RECEPTACLES WHICH IS OK, |
| HOWEVER AS NOTED ABOVE PER 210.52, THEN RECEPTACLES |
| WOULD BE REQUIRED IN ADDITION FOR GENERAL PURPOSE. |
| |
| 22) NOTE: PLEASE SEE PLANS APPEAR TO NOW HAVE ONE NEW |
| RECEPTACLE FOR WHAT APPEARS TO BE FOR THE DISHWASHER |
| AND DISPOSAL BUT IT IS UNCLEAR AS ONE UNIT SHOWS THIS |
| OUTLET AS GFI AND THE OTHER NOT GFI PROTECTED. PLEASE |
| SEE 210.4, IF THESE ARE ON THE SAME YOKE/DEVICE THEN A |
| 2-POLE BREAKER IS REQUIRED. |
| PLEASE ALSO SHOW AND IDENTIFY THE RECEPTACLE FOR THESE |
| ON PLANS. |
| |
| 23) NOTE: PLEASE SHOW ALL ROOM AND AREA DESIGNATIONS ON |
| PLANS IN ORDER TO REVIEW SOME CIRCUITING FOR CODE |
| COMPLIANCE. |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 24) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| RESPECT TO DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR |
| CODE COMPLIANCE. |
| PLEASE KNOW THAT DUE TO THE AMOUNT OF ELECTRICAL |
| COMMENTS PLANS WILL BE RETAINED BY THIS OFFICE. PLEASE |
| KNOW PLANS WILL BE SUBMITTED TO THE FLORIDA BOARD OF |
| PROFESSIONAL ENGINEERS FOR REVIEW ITEMS ON PLANS AND |
| MISSING LICENSE AS REQUIRED UNDER THE FLORIDA STATUTES |
| AND FLORIDA ADMINISTRATIVE CODE. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |