2007-03-19 19:03:03BUILDING REVIEW SECOND CHECKLIST:
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTES.
  
 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY SEC. R401.3
 2004 FLORIDA RESIDENTIAL CODE.
  
 3- ENGINEER TO PROVIDE ALL HIS INFORMATION IN THE TITLE
 BLOCK AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES AND
 FLORIDA ADMINISTRATIVE CODE SEC. 61G15-23.002.
 INCLUDING ENGINEERING FIRM'S CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ***NOTE: ENGINEER'S NAME DOESN'T MATCH ENGINEER'S NAME
 SHOWN ON EMBOSSED SEAL.
  
 4- SHEET SP-1:
 A) REVISE ALL DRIVEWAY AND APPROACH NOTES. CONTACT
 CITY OF WEST PALM BEACH ENGINEERING DEPARTMENT AT
 (561)494-1040 FOR CITY STANDARDS.
  
 B) REVISE SIZE OF PARKING SPACES.NUMBER AND SIZE
 OF PARKING SPACES DON'T MATCHNOTES AT BOTTOM OF
 SHEET. THERE IS NOT ENOUGH ROOM TO BACK UP.CHECK
 SPECIFIED SIZES: 14'-0" X 18'-0"?. SEE ZONING
 COMMENTS.
  
 C) SHOW ALL BUILDING SETBACKS TO VERIFY COMPLIANCE
 WITH SEC. R302 2004 FLORIDA RESIDENTIAL CODE AND TABLE
 704.8 2004 FBC.
  
 D) CLEARLY IDENTIFY PROPERTY LINES.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 5- PROVIDE SOIL TEST REPORT (2 COPIES).
  
 6- SHEET S-1:
 A) COLUMN SCHEDULE AND TYPICAL NOTES IN FOUNDATION
 PLANS DON'T MATCH.REVISE AS REQUIRED.
  
 B) 4" DROP IS SHOWN ON MASTER BEDROOM WINDOW INSTEAD
 OF BEING SHOWN FOR ENTRY DOOR. REVISE AS REQUIRED.
  
 C) FOUNDATION NOTES AND SPECIFICATIONS SHOWN ON
 FOUNDATION PLAN FOR WIRE MESH SIZE DON'T MATCH. REVISE
 AS REQUIRED.
  
 D) DETAIL F2 DOESN'T APPLY TO THIS PROJECT.THIS IS
 NOT WOOD FRAMING. SEE TYPE OF INTERIOR BEARING WALL.
  
 E) FOOTING SCHEDULE SHOWS FOOTING F2 WITH 3 #5 BARS
 AT THE BOTTOM, WHILE DETAIL F2 SHOWS 2 #5 AT BOTTOM AND
 1 #5 AT TOP. REVISE AS REQUIRED.
  
 F) CLARIFY FOOTING SIZE F2. FOOTING SCHEDULE CALLS
 FOR 24"X12", WHILE INTERIOR BEARING WALL SECTION ON
 SHEET A-4 CALLS FOR 12" X 24".WHICH DIMENSION IS THE
 WIDTH AND WHICH IS THE DEPTH OF THE FOOTING. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 G) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS
 PROJECT TO AVOID CONFUSIONS/CONFLICTS AND EXPEDITE
 REVIEW PROCESS.
  
 H) DETAIL F1: SPECIFY FOOTING EMBEDMENT BELOW GRADE
 TO VERIFY COMPLIANCE WITH SEC. R403.1.4 2004 FLORIDA
 RESIDENTIAL CODE.
  
 I) WINDOW DETAIL:
 * WHY SHOWING SHUTTERS DETAILS IF WINDOW NOTES ON
 SHEET A-1 CALLS FOR IMPACT GLASS?.
 ** WHY SHUTTER DETAIL SHOWS ATTACHMENT OF SHUTTER
 TRACK TO CONCRETE SLAB IF THIS IS A WINDOW DETAIL? ***
 REVISE BUCK DETAIL. SEE SEC. R613.6.2 2004 FLORIDA
 RESIDENTIAL CODE FOR PROPER WAY OF ATTACHING BUCKS.
  
 J) ENGINEER TO PROVIDE CALCULATIONS SHOWING HOW
 VERTICAL REINFORCING SHOWN IN FOUNDATION PLAN WILL
 PROVIDETHE REQUIRED LATERAL SUPPORT OF THIS BUILDING.
 SEE PLANS FOR VERTICAL REINFORCEMENT SPACING. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 AND SEC. 1609 FBC
 2004.
  
 K) DIMENSIONS SHOWN ON FOUNDATION PLANAND
 LOCATIONS OF COLUMNS DON'T MATCH REVISE AS REQUIRED.
  
 7- SHEET A-1:
 A) PROVIDEDIMENSIONSFOR ENTRY PORCH TO DETERMINE
 TOTAL PORCH AREA.BUILDING PERMIT VALUATION WILL BE
 ESTIMATED AFTER SQUARE FOOTAGE ISCLARIFIED.
  
 B) PROVIDE COMPLETE STRUCTURAL BUCK DETAIL. SPECIFY
 ALL BUCK FASTENERS AND SEESEC. R613.6.2 2004 FLORIDA
 RESIDENTIAL CODE FOR PROPER BUCK INSTALLATION. BUCK
 NEEDS TO PROVIDE FULL SUPPORT TO THE WINDOW/DOOR.
  
 C) SOME ROOMS DON'T HAVE COMPLETE SPECS FOR SIZE OF
 AND TYPE OF WINDOWS.PROVIDE COMPLETE INFORMATION.
 ALSO, SIZE OF WINDOWS ARE NOT DONE TO SCALE AND DON'T
 MATCH EXTERIOR ELEVATIONS EITHER.REVISE AS REQUIRED.
  
 8- SHEET A-2:
 A) CLARIFY NOTE REGARDING BAHAMA SHUTTERS ON 14TH
 STREET ONLY. ALL ELEVATIONS SHOW COLONIAL SHUTTERS.
 INFORMATION IS MISLEADING.
  
 C) ELEVATIONS DON'T MATCH FLOOR PLAN.SEE REVISED
 FLOOR PLAN FOR SIZE OF WINDOWS. REVISE AS REQUIRED.
  
 D) PROVIDE COMPLETE STRUCTURAL INFORMATION FOR
 OVERHANG ABOVE ENTRY AREA. PROVIDE COMPLETE STRUCTURAL
 SECTION/DETAIL WITH COMPLETE SPECIFICATIONS,
 DIMENSIONS, HEIGHT, ETC.SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 E) WINDOW SCHEDULE DOESN'T MATCH FLOOR PLAN. REVISE
 AS REQUIRED.
  
 9- SHEET A-3:
 A) PROVIDE ONLY THE INFORMATION THAT IS RELEVANT TO
 THIS PROJECT. THERE ARE A LOT OF NOTES AND TABLES THAT
 DON'T APPLY TO THIS PROJECT.
  
 B) PIGGY BACK TRUSS DETAIL:
 * IS THIS THE DETAIL FOR ENTRY PORCH?
 ** WHERE ARE THE RIGHT HAND SIDE TRUSSES SUPPORTED
 ON?. THERE IS NOT BEAM TO SUPPORT THEM.DETAIL IS
 INCOMPLETE AND WRONG. PROVIDE COMPLETE SECTION DETAIL.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) TRUSS CONNECTOR SCHEDULE AND CONNECTORS SPECIFIED
 ON ROOF FRAMING PLAN DON'T MATCH. REVISE AS REQUIRED.
  
 D) REVISE NUMBER AND TYPE OF FASTENERS SPECIFIED ON
 TRUSS CONNECTOR SCHEDULE. SEE CURRENT CATALOG FOR
 UPDATED INFORMATION. OTHERWISE, ENGINEER TO PROVIDE
 COMPLETE ENGINEERING ANALYSIS SHOWING WHY CONNECTORS
 ARE DIFFERENT THAN THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 E) MANUFACTURER FOR CONNECTORS SPECIFIED ON ROOF
 FRAMING PLAN IS OUT OF BUSINESS. REVISE AS REQUIRED.
  
 F) CLEARLY IDENTIFY TRUSSES FOR WHICH UPLIFT
 PRESSURES WERE CALCULATED.
  
 G) ENGINEER TO COORDINATE ALL NOTES AND CHARTS SHOWN
 ON THIS DRAWINGS. THERE IS A LOT OF MIXED INFORMATION
 THAT NEEDS TO BE COORDINATED.SEE 2004 FLORIDA
 RESIDENTIAL CODE AND ALLINFORMATION SUBMITTED IN THIS
 SHEET.PROVIDE ONLY THE REQUIRED INFORMATION.SEE
 SECTIONS . R301 2004 FLORIDA RESIDENTIAL CODE. ALSO,
 SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE
 FOR MINIMUM REQUIREMENTS FOR ROOF SHEATHING. REVISE AND
 COORDINATE ALL INFORMATION IN SHEET A-3 TO MATCH.
  
 H) PNEUMATIC FASTENING SCHEDULE: PROVIDE ONLY THE
 INFORMATION THAT APPLIES TO THIS PROJECT.CHECK/REVISE
 SPACING FOR BUCK DETAILS FASTENING. INFORMATION DOESN'T
 MATCH. ALSO, COORDINATE WITH PROVIDED BUCK DETAIL.
  
 I) ROOF FRAMING PLAN CALLS DWELLING SEPARATION WALL
 A "FIRE WALL".SEEFBC 2004 FOR CORRECT DEFINITION
 FOR "FIRE WALL" AND REVISE AS REQUIRED.
  
 J) PROVIDE COMPLETE SECTION THRU DWELLING SEPARATION
 WALL TO SHOW COMPLIANCE WITH SEC. R317.1 2004 FLORIDA
 RESIDENTIAL CODE.
  
 K) REVISE ATTIC VENTILATION CALCULATIONS AND NOTES
 SEE SEC. R806 2004 FLORIDA RESIDENTIAL CODE FOR PROPER
 INFORMATION.
  
 L) ROOF FRAMING PLAN DOESN'T MATCH EXTERIOR
 ELEVATIONS. SEE ENTRY PORCH. REVISE AS REQUIRED.
  
  
 10- PRIOR TO SUBMITTAL TO THIS OFFICE BRING PLANS FOR
 HISTORICAL APPROVAL AFTER CORRECTIONS ARE DONE TO THE
 PLANS.
  
 11- SHEET A-4:
 A) REVISE INTERIOR BEARING WALL TO MATCH FLOOR PLAN.
 REVISE SIZE OF FOOTING, WALL CONSTRUCTION, ETC.
 * WHAT'S THE BEAM SHOWN ON TOP OF WALL?
 ** HOW ARE TRUSSES RESTING ON THIS WALL. SEE ROOF
 FRAMING PLAN.
 *** WHAT'STHE HOOK SHOWN AT THE BOTTOM OF WALL
 CONNECTING TO FOOTING. PROVIDECOMPLETE SPECS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) SPECIFY FIREBLOCKING ON INTERIOR BEARING WALL
 SECTION AS REQUIRED BY SEC. R602.8 2004 FLORIDA
 RESIDENTIAL CODE.
  
 C PROVIDE DETAIL/SPECS FOR DWELLING SEPARATION AT
 ATTIC AREA. SEC. R317.1 2004 FLORIDA RESIDENTIAL CODE.
  
 D) PROVIDE ALL DESIGN CRITERIA, INCLUDING ALL WIND
 LOADS, AND LIVE AND DEAD LOADS. REFERENCE 2004 FLORIDA
 RESIDENTIAL CODE,WHICH IS THE CODE THAT REGULATES
 THIS BUILDING, NOT SECTIONS 1606 OF FBC 2004. SEE SEC.
 R301 AND TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE.
 REVISE AS REQUIRED. INCLUDE ALL ATTIC LIVE LOADS.
  
 E) PLYWOOD NAILING NOTES TO MATCH INFORMATION ON
 SHEET A-3 AFTER APPROPRIATE REVISIONS ARE DONE.
  
 F) TYPICAL WALL SECTION:
 *WHAT IS 2"X4" STRIP?. IS IT FIREBLOCKING?. ALSO,
 VERIFY SIZE WITH SIZE OF FURRING STRIPS FOR DRYWALL
 INSTALLATION.
 **WHAT IS 325# SHINGLES?
 *** ROOF SHEATHING SIZE AND TYPE TO MATCH
 INFORMATION ON SHEET A-3 AFTER APPROPRIATE REVISIONS
 ARE DONE.
 **** TRUSS CONNECTOR TO MATCH INFORMATION ON SHEET
 A-3 AFTER APPROPRIATE REVISIONS ARE DONE.
 ***** SPECIFY FOOTING MIN. DEPTH AS REQUIRED BY SEC.
 R 403.1.4 2004 FLORIDA RESIDENTIAL CODE.
 ****** SPECIFY MINIMUM FINISH FLOOR AS REQUIRED BY
 SEC. R404.1.6 2004 FLORIDA RESIDENTIALCODE.
  
 G) TRUSS/ WOOD CONNECTOR SCHEDULE DOESN'T APPLY TO
 THIS PROJECT AND IS USING CONNECTORS THAT NO LONGER
 EXIST. COMPANY IS OUT OF BUSINESS.
 ALSO, ROOFTILE INFORMATION DOESN'T APPLY.
  
  
 12- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
  
 B) THIS IS NOT A SINGLE FAMILY DETACHED BUILDING.
 SEE CHAPTER 13 2004 FBC FOR PROPER TYPE OF BUILDING.
 AND, NEED ENERGY CALCULATIONS FOR EACH DWELLING.SEE
 DEFINITIONS ON SUBCHAPTER13-2 OF 2004 FBC. REVISE AS
 REQUIRED.SEE SEC. 15-101.2.5.1 FBC 2004.
  
 C) IF CALCULATIONS ARE NOT DONE FOR WORST CASE
 SCENARIO, THEN THEY SHALL BE DONE ON ACTUAL BUILDING
 ORIENTATION.ENERGY CALCULATIONS SUBMITTED ARE NOT FOR
 WORST CASE SCENARIO AND BUILDING ORIENTATION DON'T
 MATCH ACTUAL BUILDING ORIENTATION. SEE SURVEY AND
 REVISE AS REQUIRED.
  
 D) OVERHANG LENGTH AND HEIGHT ARE INCORRECT.THEY
 CAN'T BE ZERO. REVISE AS REQUIRED.
  
 13- ENERGY CALCULATIONS ARE TAKINGTHE CEILING FAN
 CREDIT. THEREFORE NEED TO SPECIFY CEILING FAN SIZE IN
 ALL ROOMS AS REQUIRED BY TABLE 13-607.1.A.1 FBC 2004.
  
 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) SINGLE HUNG WINDOWS.TWO DIFFERENT PRODUCT
 APPROVALS WERE SUBMITTED. ONLY THE ONE FOR LARGE
 MISSILE IMPACT CAN BE USED FOR OPENINGS BELOW 30'-0"
 HIGH. PROVIDE 2 COPIES.
  
 B) SHINGLES.
  
 C) BAHAMA SHUTTERS AND COLONIAL SHUTTERS SHOWN ON
 EXTERIOR ELEVATIONS. AND PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED INSTALLATION SCHEDULE SAMPLE.
 PROVIDE ALL REQUIRED INFORMATION.
  
 D) PRECAST LINTELS.
  
 E) ENTRY DOORS.
  
 F) REAR DOORS.
  
 G) ALL STRUCTURAL SIMPSON OR USP CONNECTORS
 SPECIFIED ON PLANS ANDDETAILS.
  
  
 15- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 16- DUPLEX REQUIRES TWO SEPARATE ADDRESSESAND PLANS
 NEED TO BE REVISED SHOWING CORRECT ADDRESS.PLEASE
 CONTACT LILLY URSU AT (561)822-1239 TO GET CORRECT
 ADDRESS.
  
 17- PROVIDE SURVEYS (TWO) SHOWING REVISED PARKING
 SPACES.NOTE: ORIGINAL SEAL AND SIGNATURE.
  
 18- ENGINEER TO SEE ATTACHED COPY OF FLORIDA STATUTE
 REGARDING REVIEW OF DESIGN PROFESSIONAL DOCUMENTS.
  
  
 ***NOTE:
 ONE COPY OF PLANS WILL BE SEND TO THE BOARD OF
 ENGINEERS FOR THEIR REVIEW.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712