Plan Review Notes
Plan Review Notes For Permit 06120402
Permit Number 06120402
Review Stop M
Sequence Number 1
Notes
Date Text
2006-12-19 11:39:10*** DENIED ***
 1) DM&L ENGINEERING CORP. NEED THEIR CERTIFICATE OF
 AUTHORIZATION NUMBER IN THE TITLE BLOCK, SEE FAC
 61G15-23.002.
  
 2) MANUAL J CALCULATIONS ARE CALLING FOR 13,331
 SENSIBLE BTU'S., THE MECHANICAL PLANS ARE CALLING FOR
 26,200 SENSIBLE BTU'S., THE PLANS CAN ONLY CALL FOR 20%
 MORE THAN THE MANUAL J CAL'S., SEE 2004 FBC
 13-607.ABC.1.1.
  
 3) ENERGY CALCULATIONS ARE CALLING FOR 10,000 BTU
 COOLING SYSTEM AND 10,000 BTU (=2.9 KW) HEATING SYSTEM,
 THE MECHANICAL PLANS ARE CALLING FOR 34,000 BTU COOLING
 AND 10 KW (=34,000 BTU) HEATING. THE ENERGY CAL'S. AND
 MECHANICAL PLANS MUST COINCIDE, PLEASE CORRECT.
  
 4) THE RETURN AIR TRANSFER GRILLS TO THE BEDROOMS ARE
 TO SMALL,
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.