Date |
Text |
2006-12-19 11:39:10 | *** DENIED *** |
| 1) DM&L ENGINEERING CORP. NEED THEIR CERTIFICATE OF |
| AUTHORIZATION NUMBER IN THE TITLE BLOCK, SEE FAC |
| 61G15-23.002. |
| |
| 2) MANUAL J CALCULATIONS ARE CALLING FOR 13,331 |
| SENSIBLE BTU'S., THE MECHANICAL PLANS ARE CALLING FOR |
| 26,200 SENSIBLE BTU'S., THE PLANS CAN ONLY CALL FOR 20% |
| MORE THAN THE MANUAL J CAL'S., SEE 2004 FBC |
| 13-607.ABC.1.1. |
| |
| 3) ENERGY CALCULATIONS ARE CALLING FOR 10,000 BTU |
| COOLING SYSTEM AND 10,000 BTU (=2.9 KW) HEATING SYSTEM, |
| THE MECHANICAL PLANS ARE CALLING FOR 34,000 BTU COOLING |
| AND 10 KW (=34,000 BTU) HEATING. THE ENERGY CAL'S. AND |
| MECHANICAL PLANS MUST COINCIDE, PLEASE CORRECT. |
| |
| 4) THE RETURN AIR TRANSFER GRILLS TO THE BEDROOMS ARE |
| TO SMALL, |
| BALANCED RETURN AIR MAY BE ACHIEVED BY. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |