Plan Review Notes
Plan Review Notes For Permit 06120402
Permit Number 06120402
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-17 16:22:02*** UNSAT ***
  
 *** PLEASE KNOW DUE TO THE PLANS NOT BEING COMPLETE AT
 THIS TIME AND ALSO THE FOLLOWING COMMENTS FOR PLANS
 SUBMITTED, THERE MAY BE COMMENTS ON NEXT REVIEW WHICH
 ARE NOT ON THIS REVIEW.
 **DUE TO THE EXTENT OF THE ELECTRICAL COMMENTS AND
 OTHER COMMENTS BASED ON LICENSING, ONE SET OF THE
 ELECTRICAL PLANS ARE BEING RETAINED BY THIS OFFICE.
  
 1) NOTE:PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 FOR MISSING LICENSING INFORMATION
 REQUIRED. PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER AND SOME SHEETS ARE NOT COMPLETE
 WITH OTHER INFORMATION AS REQUIRED.
 FLORIDA STATUTES 471.023
 PLEASE ALSO SEE 61G15-23.001 FOR MINIMUM SIZE OF SEAL.
 THE SIZE AS SHOWN ON PLANS DO NOT APPEAR TO BE LARGE
 ENOUGH?
 PLEASE SEE PLANS SEEM TO BE SIGNED WITH AN INITIAL OF
 SOME SORT. IF THIS IS INDEED THE LEGAL SIGNATURES OF
 THE DESIGNER OF RECORD PLEASE PROVIDE A SIGNED, DATED
 AND SEALED LETTER WITH STATEMENT OF LEGAL SIGNATURE.
 PLEASE BE SURE LETTER IS PROPERLY NOTARIZED UNDER
 FLORIDA STATUTES 117.05.
 PLEASE KNOW THIS LETTER WILL BE PLACED IN OUR SIGNATURE
 FILE FOR ANY FUTURE REFERENCE AS NEEDED AND WILL NOT BE
 NEED TO ROVIDE LETTER ON FUTURE PROJECTS.
 ** PLEASE KNOW, THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADE REVIEWS WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON PLANS.
 NFPA-70 2005, 2002 NFPA-72
 PLEASE KNOW BASED ON THE FACT THAT THE PLANS WERE
 SUBMITTED FOR PERMITTING AFTER THE DATE OF DEC 8TH,
 2006, THE PLANS SHALL BE DESIGNED UNDER THE 2005 NEC.
  
 3) NOTE: PLEASE CORRELATE RISER AND PLANS SUBMITTED.
 PLANS AND PERMIT APPLICATION IS FOR A DUPLEX DWELLING
 UNIT TO BE BUILT, (NOT YET APPROVED OR DISAPPROVED BY
 ZONING) YET RISER SHOWS SINGLE METER AND PLANS SHOW
 TWO?
 PLEASE SEE RISER AS SHOWN MAY NOT FEED PANELS AS SHOWN.
 PLEASE SEE 240.21C FOR TAPPED CONDUCTORS.
 PLEASE SEE THE SIZE OF THE METER CAN, CAN NOT BE
 VERIFIED AS NO LOAD CALCULATIONS WERE SUBMITTED. FBC
 106.1.2, 106.3.5.4(PARA 8) ADMIN SECTION. THERE ARE
 CURRENTLY MANY SECTIONS BESIDES THE ONES NOTED BELOW
 WHICH COULD NOT BE ALL TYPED IN THIS REVIEW.
  
 4) NOTE: PLEASE SEE 250.6, 250.24B AS NO EQUIPMENT
 GROUNDING CONDUCTORS ARE PERMITTED BEFORE THE FIRST
 MEANS OF DISCONNECT.
  
 5) NOTE: PLEASE SEE 250.66 AS THE SIZE OF SERVICE MAY
 CHANGE WHICH WILL DICTATE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR.
  
 6) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR SERVICE
 MAINS PER 110.9.
 PLEASE SEE THE RATING AS SHOWN ON PANEL SCHEDULE WAS
 NOTED, HOWEVER NEEDED FOR MAIN(S).
  
 7) NOTE: PLEASE COMPLETE AND SUBMIT A COMPLETE PANEL
 SCHEDULE WITH ALL MINIMUM REQUIRED DEDICATED LOADS AS
 WELL AS COMPLETED LOAD CALCULATIONS BASED ON MINIMUM
 REQUIREMENTS FROM THE NEC.
 PLEASE SEE 220.40, 220.82, 220.52, 220.54, 220.60, ETC,
 ETC.
 FBC ADMIN SECTION 106.3.5.4
  
 8) NOTE: PLEASE SEE 210.52D, 210.11C3,A S NO OTHER
 LOADS ARE PERMITTED ON THE DEDICATED BATH CIRCUIT(S).
  
 9) NOTE: PLEASE SEE 210.52C1 FOR MISSING REQUIRED GFI'S
 ALONG KITCHEN COUNTER SPACE.
 MISSING MINIMUM VA 220.52
  
 10) NOTE: PLEASE SEE MISSING REQUIRED CIRCUITING FOR
 DINING ROOM RECEPTS PER 210.52B1, 210.11C1, AND 220.
 52B.
  
 11) NOTE: PLEASE SEE 210.8A6, AS ALL RECEPTS ALONG
 KITCHEN COUNTER SPACE SHALL BE SHOWN AS GFI.
  
 12) NOTE: PLEASE SEE 410.8 AS THE PC LIGHTING IN
 CLOSETS ARE NOT PERMITTED AS SHOWN. THEY DO NOT MEET
 MINIMUM CLEARANCES.
  
 13) NOTE: PLEASE SEE MISSING RECEPTS PER 210.52 FOR
 WALL SPACES.
  
 14) NOTE: PLEASE SEE ALL SMOKE DEVICES SHALL BE SHOWN
 AS DEFINED IN NFPA-72. PLEASE SEE IF THESE DEVICES AS
 SHOWN ARE PART OF A LOW VOLTAGE ALARM SYSTEM WHICH
 CONTAINS HORN/ALARM DEVICES THEN THE SD AS SHOWN FOR
 SMOKE DETECTOR IS OK. IF THESE DEVICES AS SHOWN ARE
 DETECT AND SOUND AN ALARM, THEN THEY SHALL BE SHOWN AS
 SA FOR SMOKE ALARMS.
 PLEASE ALSO SEE NFPA-72 11.5.1.1, 11.8.3 FOR LOCATIONS
 REQUIRED INSIDE AND OUTSIDE ALL SLEEPING ROOMS. PLEASE
 SEE SOME ROOMS DO NOT INDICATE THE DEVICE OUTSIDE THE
 SLEEPING ROOM, YET INDICATE TWO DEVICES INSIDE ROOM?
 PLEASE SEE OTHER ROOMS WHICH DO INDICATE A DEVICE
 OUTSIDE ROOM, BUT STILL INDICATE TWO OR MORE INSIDE??
  
 15) NOTE: PLEASE SEE MISSING DISCONNECTS FOR ALL A/C
 EQUIPMENT. PLEASE SEE 440.11.
 PLEASE SEE AHU CLOSET APPEARS TO SHOW TWO RECEPTS.
 PLEASE KNOW AS PER 422.31, AHU?S SHALL NOT BE PLUGGED
 IN.
  
 16) NOTE: PLEASE SEE 422.31 FOR DISCONNECTING MEANS
 REQUIRED FOR WATER HEATER(S).
  
 17) NOTE: PLEASE CLARIFY ROOMS WHICH INDICATE A J-BOX
 FOR "PUT-FAN" AS STATED ON PLANS. PLEASE CLARIFY WHAT
 THIS IS? SYMBOL LEGEND DOES NOT ELABORATE ON THIS.
  
 18) NOTE: PLEASE KNOW SEPARATE PLANS, AND PERMIT
 APPLICATIONS REQUIRED FOR LOW VOLTAGE , PHONE, CATV OR
 BURGLAR ALARM SYSTEMS.
  
 ** PLEASE KNOW SERVICE AND PROPOSED STRUCTURE MAY BE
 GREATLY AFFECT BY ANY POSSIBLE ZONING COMMENTS FOR
 SERVICE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]