2007-01-29 18:59:15BUILDING REVIEW CHECKLIST:
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTES.
  
 2- PAY IMPACT FEES TO PALM BEACH COUNTY. BRING BACK
 STAMPED DRAWINGS AND COPY OF PAID RECEIPT.
  
 3- PROVIDE TRUSS DRAWINGS FOR REVIEW PRIOR TO
 INSTALLATION. SEE SEC. R802.10 2004 FLORIDA RESIDENTIAL
 CODE FOR ALL REQUIRED INFORMATION ON TRUSS DRAWINGS.
 ALSO, DESIGNER OF RECORD TO REVIEW AND APPROVE THEM
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 4- PROVIDE DRAINAGE PLANS AS REQUIRED BY SEC. R401.3
 2004 FLORIDA RESIDENTIAL CODE.
  
 5- ENGINEER TO PROVIDE ALL HIS INFORMATION IN THE TITLE
 BLOCK AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES AND
 FLORIDA ADMINISTRATIVE CODE SEC. 61G15-23.002.
 INCLUDING ENGINEERING FIRM'S CERTIFICATE OF
 AUTHORIZATION NUMBER.
  
  
 6- SHEET SP-1:A) REVISE ALL DRIVEWAY AND APPROACH
 NOTES. CONTACT CITY OF WEST PALM BEACH ENGINEERING
 DEPARTMENT AT (561)494-1040 FOR CITY STANDARDS.
  
 B) DRAINAGE CAP CALCS HAVE NOTHING TO DO WITH
 PROJECT.
  
 C) REVISE SIZE OF PARKING SPACES.
  
 D) PAVEMENT DETAILS DON'T APPLY TO THIS JOB.
  
 E) FLOOR PLAN IS CALLED EXISTING SITE PLAN. THIS IS
 THE PROPOSED SITE PLAN. REVISE AS REQUIRED.
  
 F) CLARIFY WHY BACKFLOW PREVENTER IS SHOWN FOR ONE
 UNIT ONLY?
  
 7- PROVIDE SOIL TEST REPORT (2 COPIES).
  
 8- SHEET S-1:A) FOOTING SCHEDULE AND FOOTING TYPICAL
 NOTES SHOWN ON FOUNDATION PLAN DON'T MATCH.REVISE AS
 REQUIRED.
  
 B) COLUMN SCHEDULE AND TYPICAL NOTES IN FOUNDATION
 PLANS DON'T MATCH EITHER. REVISE AS REQUIRED.
  
 C) ENGINEER TO SPECIFY CONCRETE SLABS JOINTS AS
 REQUIRED BY SEC. R506.2.4 2004 FLORIDA RESIDENTIAL
 CODE.
  
 D) 4" DROP IS SHOWN ON MASTER BEDROOM WINDOW INSTEAD
 OF BEING SHOWN FOR ENTRY DOOR. REVISE AS REQUIRED.
  
 E) CORRECT WORDING IN CONCRETE SLAB SPECS IS 6 MIL
 VISQUEEN (NOT JISQUEEN) REVISE AS REQUIRED.
  
 F) DETAIL F1 CALLS FOR WELDED WIRE MESH SPECS ON
 FOUNDATION NOTES. WHERE ARE THE FOUNDATION NOTES?
  
 G) DETAIL F2 DOESN'T APPLY TO THIS PROJECT.THIS IS
 NOT WOOD FRAMING. SEE TYPE OF INTERIOR BEARING WALL.
 AND,SPECIFY SIZE OF FOOTING ACCORDINGTO TYPE OF
 WALL TO BE SUPPORTED. SEC. 106.1.2CITY AMENDMENTS TO
 FBC 2004.
  
 H) DETAIL F2 SHOWS 3 RE-BARS, WHILE FOOTING SCHEDULE
 CALLS FOR 2 RE-BARS. REVISE AS REQUIRED.
  
 I) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS
 PROJECT TO AVOID CONFUSIONS/CONFLICTS AND EXPEDITE
 REVIEW PROCESS.
  
 9- SHEET A-1:A) PROVIDE CALCULATIONS AND DIMENSIONS
 SHOWING HOW102SF OF COVERED ENTRY WAS ACHIEVED? PLANS
 DON'T PROVIDE ENOUGH INFORMATION TO VERIFY SQUARE
 FOOTAGE.BUILDING PERMIT VALUATION WILL BE ESTIMATED
 AFTER SQUARE FOOTAGES ARE CLARIFIED.
  
 B) SPECIFY ATTIC ACCESS SIZE. SEC. R807 2004 FLORIDA
 RESIDENTIAL CODE.
  
 C) DRAWINGS ARE INCOMPLETE: MISSING SIZE OF ENTRY
 DOORS,CLOSET DOORS, ETC.
  
 D) PROVIDE COMPLETE STRUCTURAL BUCK DETAIL. SPECIFY
 ALL BUCK FASTENERS AND SEESEC. R613.6.2 2004 FLORIDA
 RESIDENTIAL CODE FOR PROPER BUCK INSTALLATION. BUCK
 NEEDS TO PROVIDE FULL SUPPORT TO THE WINDOW/DOOR.
  
 10- SHEET A-2:A) SPECIFY CALCULATED DESIGN PRESSURES
 FOR ENTRY DOORS. SEC. R301 2004 FLORIDA RESIDENTIAL
 CODE.
  
 B) CLARIFY NOTE REGARDING BAHAMA SHUTTERS ON 14TH
 STREET ONLY. ALL ELEVATIONS SHOW COLONIAL SHUTTERS.
  
 C) ELEVATIONS DON'T MATCH FLOOR PLAN.SOME ROOMS
 HAVE DOUBLE WINDOWS MULLED TOGETHER. REVISE AS
 REQUIRED.
  
 D) PROVIDE COMPLETE STRUCTURAL INFORMATION FOR
 OVERHANG ABOVE ENTRY AREA. PROVIDE COMPLETE STRUCTURAL
 SECTION/DETAIL WITH COMPLETE SPECIFICATIONS,
 DIMENSIONS, HEIGHT, ETC.SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 E) WINDOW SCHEDULE DOESN'T MATCH FLOOR PLAN. REVISE
 AS REQUIRED.
  
 11- SHEET A-3:A) PROVIDE ONLY THE INFORMATION THAT IS
 RELEVANT TO THIS PROJECT. THERE ARE A LOT OF NOTES AND
 TABLES THAT DON'T APPLY TO THIS PROJECT.
  
 B) REVISE CODE INFORMATION.CODE THAT APPLIES TO
 THIS PROJECT IS 2004 FLORIDA RESIDENTIAL CODE. WHEN
 REFERENCINGASCE7,THEN, THE CORRECT EDITION IS
 2002, NOT 2005. REVISE AS REQUIRED.
  
 C) TRUSS CONNECTOR SCHEDULE AND CONNECTORS SPECIFIED
 ON ROOF FRAMING PLAN DON'T MATCH. REVISE AS REQUIRED.
  
 D) REVISE NUMBER AND TYPE OF FASTENERS SPECIFIED ON
 TRUSS CONNECTOR SCHEDULE. SEE CURRENT CATALOGUE FOR
 UPDATED INFORMATION. OTHERWISE, ENGINEER TO PROVIDE
 COMPLETE ENGINEERING ANALYSIS SHOWING WHY CONNECTORS
 ARE DIFFERENT THAN THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 E) MANUFACTURER FOR CONNECTORS SPECIFIED ON ROOF
 FRAMING PLAN IS OUT OF BUSINESS. REVISE AS REQUIRED.
  
 F) CLEARLY IDENTIFY TRUSSES FOR WHICH UPLIFT
 PRESSURES WERE CALCULATED.
  
 G) PROVIDE COMPLETE STRUCTURAL DETAILS/SPECS FOR
 ROOF ABOVE ENTRY DOORS. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 H) ENGINEER TO COORDINATE ALL NOTES AND CHARTS SHOWN
 ON THIS DRAWINGS. THERE IS A LOT OF MIXED INFORMATION
 THAT NEEDS TO BE COORDINATED.SEE 2004 FLORIDA
 RESIDENTIAL CODE AND ALLINFORMATION SUBMITTED IN THIS
 SHEET.PROVIDE ONLY THE REQUIRED INFORMATION.SEE
 SECTIONS . R301 2004 FLORIDA RESIDENTIAL CODE. ALSO,
 SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE
 FOR MINIMUM REQUIREMENTS FOR ROOF SHEATHING. REVISE AND
 COORDINATE ALL INFORMATION IN SHEET A-3 TO MATCH.
  
 I) PNEUMATIC FASTENING SCHEDULE: PROVIDE ONLY THE
 INFORMATION THAT APPLIES TO THIS PROJECT.CHECK/REVISE
 SPACING FOR BUCK DETAILS FASTENING. INFORMATION DOESN'T
 MATCH. ALSO, COORDINATE WITH PROVIDED BUCK DETAIL.
  
 J) ROOF FRAMING PLAN CALLS DWELLING SEPARATION WALL
 A "FIRE WALL".SEEFBC 2004 FOR CORRECT DEFINITION
 FOR "FIRE WALL" AND REVISE AS REQUIRED.
  
 K) PROVIDE COMPLETE SECTION TRUH DWELLING SEPARATION
 WALL TO SHOW COMPLIANCE WITH SEC. R317.1 2004 FLORIDA
 RESIDENTIAL CODE.
  
 L) REVISE ATTIC VENTILATION CALCULATIONS AND NOTES
 SEE SEC. R806 2004 FLORIDA RESIDENTIAL CODE FOR PROPER
 INFORMATION.
  
  
 12- PRIOR TO SUBMITTAL TO THIS OFFICE BRING PLANS FOR
 HISTORICAL APPROVAL AFTER CORRECTIONS ARE DONE TO THE
 PLANS.
  
 13- SHEET A-4:A) REVISE INTERIOR BEARING WALL TO
 MATCH FLOOR PLAN. REVISE SIZE OF FOOTING, WALL
 CONSTRUCTION, ETC.
  
 B) SPECIFY FIREBLOCKING ON INTERIOR BEARING WALL
 SECTION AS REQUIRED BY SEC. R602.8 2004 FLORIDA
 RESIDENTIAL CODE.
  
 B) PROVIDE DETAIL/SPECS FOR DWELLING SEPARATION AT
 ATTIC AREA. SEC. R317.1 2004 FLORIDA RESIDENTIAL CODE.
  
 C) PROVIDE ALL DESIGN CRITERIA, INCLUDING ALL WIND
 LOADS, AND LIVE AND DEAD LOADS. REFERENCE 2004 FLORIDA
 RESIDENTIAL CODE,WHICH IS THE CODE THAT REGULATES
 THIS BUILDING, NOT SECTIONS 1606 OF FBC 2004. SEE SEC.
 R301 AND TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE.
 REVISE AS REQUIRED.
  
 D) PLYWOOD NAILING NOTES TO MATCH INFORMATION ON
 SHEET A-3 AFTER APPROPRIATE REVISIONS ARE DONE.
  
 E) TYPICAL WALL SECTION:
 * WHAT IS D-30 INSULATION?
 ** WHAT IS 6 MIL JISQUEEN?
 *** WHAT IS 1/2" DRYWALL STRIPS AT 16"O.C.?
 **** WHAT IS 2"X4" STRIP?. IS IT FIREBLOCKING?. ALSO,
 VERIFY SIZE WITH SIZE OF FURRING STRIPS FOR DRYWALL
 INSTALLATION.
 ***** WHAT IS 325# SHINGLES?
 ****** ROOF SHEATHIG SIZE AND TYPE TO MATCH INFORMATION
 ON SHEET A-3 AFTER APPROPRIATE REVISIONS ARE DONE.
 ******* TRUSS CONNECTOR TO MATCH INFORMATION ON SHEET
 A-3 AFTER APPROPRIATE REVISIONS ARE DONE.
 ******** SPECIFY FOOTING MIN. DEPTH AS REQUIRED BY SEC.
 R 403.1.4 2004 FLORIDA RESIDENTIAL CODE.
 ********* SPECIFY MINIMUM FINISH FLOOR AS REQUIRED BY
 SEC. R404.1.6 2004 FLORIDA RESDIENTIAL CODE.
  
 14- ENERGY CALCULATIONS:A) PROVIDE COMPLETE
 INFORMATION ON TOP OF FORM.
  
 B) THIS IS A MULTIFAMILY BUILDING, NOT SINGLE
 FAMILY. SEE DEFINITIONS ON SUBCHAPTER13-2 OF 2004
 FBC. REVISE AS REQUIRED. THEREFORE SEPARATE ENERGY
 CALCULATIONS ARE REQUIRED. SEE SEC. 15-101.2.5.1 FBC
 2004.
  
 C) IF CALCULATIONS ARE NOT DONE FOR WORST CASE
 SCENARIO, THEN THEY SHALL BE DONE ON ACTUAL BUILDING
 ORIENTATION.ENERGY CALCULATIONS SUBMITTED ARE NOT FOR
 WORST CASE SCENARIO AND BUILDING ORIENTATION DON'T
 MATCH ACTUAL BUILDING ORIENTATION. SEE SURVEY AND
 REVISE AS REQUIRED.
  
 D) OVERHANG LENGTH AND HEIGHT ARE INCORRECT.THEY
 CAN'T BE ZERO. REVISE AS REQUIRED.
  
 16- ENERGY CALCULATIONS ARE TAKINGTHE CEILING FAN
 CREDIT. THEREFORE NEED TO SPECIFY CEILING FAN SIZE IN
 ALL ROOMS AS REQUIRED BY TABLE 13-607.1.A.1 FBC 2004.
  
 17- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) SINGLE HUNG WINDOWS.TWO DIFFERENT PRODUCT
 APPROVALS WERE SUBMITTED. ONLY THE ONE FOR LARGE
 MISSILE IMPACT CAN BE USED FOR OPENINGS BELOW 30'-0"
 HIGH. PROVIDE 2 COPIES.
  
 B) SHINGLES.
  
 C) BAHAMA SHUTTERS AND COLONIAL SHUTTERS SHOWN ON
 EXTERIOR ELEVATIONS. AND PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED INSTALLATION SCHEDULE SAMPLE.
 PROVIDE ALL REQUIRED INFORMATION.
  
 D) PRECAST LINTELS.
  
 E) ENTRY DOORS.
  
 F) REAR DOORS.
  
 G) ALL STRUCTURAL SIMPSON OR USP CONNECTORS
 SPECIFIED ON PLANS ANDDETAILS.
  
 H) WINDOW MULLIONS AND SPECIFY FASTENING.
  
 18- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712