Plan Review Notes For Permit 06120388 |
Permit Number |
06120388 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-18 13:07:24 | *****DENIED****** | | | | | | 1.ON SHEET D-1, DEMOLITION NOTE #10, ADD THE WORD | | "EXIT" BETWEEN REQUIRED ---- COMPONENTS. | | | | 2.WHAT WILL BE THE INTERIOR FINISH CLASSIFICATION FOR | | THE WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS | | CORRIDORS, AND IN ALL OTHER AREAS? | | | | 3.ON SHEET M7.1, IT IS NOTED THATDUCT MOUNTED SMOKE | | DETECTOR EQUIPMENT WILL BE INSTALLED. IF THIS BUILDING | | IS NOT TIED INTO A FIRE ALARM SYSTEM, HOW WILL ALERT | | NOTIFICATION BE ACCOMPLISHED? | | | | 4.ON SHEET E1.1, AN ADDITIONAL EXIT LIGHT (AS | | RED-LINED) IS NEEDED. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | ITEM WAS ADDRESSED IN THE PLAN. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|