Plan Review Notes
Plan Review Notes For Permit 06120388
Permit Number 06120388
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-01-18 13:07:24*****DENIED******
  
  
 1.ON SHEET D-1, DEMOLITION NOTE #10, ADD THE WORD
 "EXIT" BETWEEN REQUIRED ---- COMPONENTS.
  
 2.WHAT WILL BE THE INTERIOR FINISH CLASSIFICATION FOR
 THE WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS
 CORRIDORS, AND IN ALL OTHER AREAS?
  
 3.ON SHEET M7.1, IT IS NOTED THATDUCT MOUNTED SMOKE
 DETECTOR EQUIPMENT WILL BE INSTALLED. IF THIS BUILDING
 IS NOT TIED INTO A FIRE ALARM SYSTEM, HOW WILL ALERT
 NOTIFICATION BE ACCOMPLISHED?
  
 4.ON SHEET E1.1, AN ADDITIONAL EXIT LIGHT (AS
 RED-LINED) IS NEEDED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED IN THE PLAN.
  
  