Plan Review Notes
Plan Review Notes For Permit 06120388
Permit Number 06120388
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-09 12:43:25 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 611 EXISTING BUILDING CODE, INDICATE COMPLIANCE
 WITH CHAPTER 13-101.1.3. SUBMIT PROPER FORMS FOR
 REVIEW.
  
 2} LOCATE THE CLOCKS ,SENSORS AND TIMERS ON THE PLAN.
 13-415.
  
 3} INDICATE FIXTURE TYPES THAT COMPLY WITH 13-415.
  
 4} THE "NEW PANEL " FEED ON SHEET E5.1 MUST INCLUDE
 CONDUCTOR NUMBER A, SIZES AND OVERCURRENT PROTECTION
 RATING STATED ON THE RISER DIAGRAM. SHOW EQUIPMENT
 GROUND SIZE AS WELL.
  
 5} THE EMERGENCY LIGHTS MUST COMPLY WITH 700.12(F)(4).
 IDENTIFY THE CIRCUIT NUMBER ON THE PLANS (SHEET E1.1),
 SO THE CONNECTING CIRCUIT WILL BE CLEAR IN THE FIELD.
  
 6} CIRCUIT THE EXIT LIGHTS ON SHEET E1.1. SHOW ON
 SCHEDULE.
  
 7} SHEET E0.1, NOTE 57 SHOULD INCLUDE EDITION(S) BEING
 REFERENCED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  