2007-01-09 07:59:20 | BUILDING PLAN REVIEW |
| PERMIT: 06120388 |
| ADD: 440 COLUMBIA DR SUITE 500 |
| |
| CONT: SISCA CONST |
| TEL: (561)228-7517 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2 ) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3A) SHEET D-1 INDICATES WORK TO BE COMPLETED IN |
| THE EXISTING MENS AND WOMENS RESTROOM AND |
| EXISTING CLOSET (111). |
| THE DOORS TO THE EXISTING RESTROOM SWING IN TO |
| THE CLEAR FLOOR SPACE REQUIRED FOR FIXTURES. |
| 11-4.22.2 DOORS. ALL DOORS TO |
| ACCESSIBLE TOLIET ROOMS SHALL COMPLY |
| WITH 11-4.13. DOORS SHALL NOT SWING INTO |
| CLEAR FLOOR SPACE REQUIRED FOR ANY |
| FIXTURE. |
| |
| 3B) SHEET D-1CLOSET (111)INDICATES DOOR AND |
| FRAME TO BE REMOVED: |
| 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARANCES SHALL BE |
| CLEAR & LEVEL. |
| |
| 11-4.1.6(2) DUTY TO PROVIDE AN |
| ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| AREAS SHALL BE DEEMED DISPROPORTIONATE |
| TO THE OVERALL ALTERATION WHEN THE COST |
| EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| TION TO THE PRIMARY FUNCTION AREA. |
| (A)(I) AN ACCESSIBLE ENTRANCE |
| (II) AN ACCESSIBLE ROUTE |
| (III) AT LEAST ONE ACCESSIBLE REST- |
| ROOM FOR EACH SEX OR A SINGLE |
| UNISEX RESTROOM |
| (IIII) ACCESSIBLE TELEPHONE |
| (IV) ELEMENTS SUCH AS PARKING, STOR- |
| AGE OR ALARMS. |
| |
| 4) SHEET E1.1 DOESN'T INDICATE ANY EXIT LIGHTS, |
| PLANS DO INDICATE DIRECTIONALS. 1006.3.1 EXITS |
| SHALL BE MARKED BY AN APPROVED SIGN READILY |
| VISIBLE FROM ANY DIRECTION OF RXIT ACCESS. EVERY |
| EXIT SIGN SHALL BE SUITABLY ILLUMINATED BY A RELIABLE |
| LIGHT SOURCE. EXTERNALLY AND INTERNALLY ILLUMINATED |
| SIGNS SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY |
| LIGHTING. |
| |