Plan Review Notes
Plan Review Notes For Permit 06120388
Permit Number 06120388
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-09 07:59:20BUILDING PLAN REVIEW
 PERMIT: 06120388
 ADD: 440 COLUMBIA DR SUITE 500
  
 CONT: SISCA CONST
 TEL: (561)228-7517
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3A) SHEET D-1 INDICATES WORK TO BE COMPLETED IN
 THE EXISTING MENS AND WOMENS RESTROOM AND
 EXISTING CLOSET (111).
 THE DOORS TO THE EXISTING RESTROOM SWING IN TO
 THE CLEAR FLOOR SPACE REQUIRED FOR FIXTURES.
 11-4.22.2 DOORS. ALL DOORS TO
 ACCESSIBLE TOLIET ROOMS SHALL COMPLY
 WITH 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
  
 3B) SHEET D-1CLOSET (111)INDICATES DOOR AND
 FRAME TO BE REMOVED:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 4) SHEET E1.1 DOESN'T INDICATE ANY EXIT LIGHTS,
 PLANS DO INDICATE DIRECTIONALS. 1006.3.1 EXITS
 SHALL BE MARKED BY AN APPROVED SIGN READILY
 VISIBLE FROM ANY DIRECTION OF RXIT ACCESS. EVERY
 EXIT SIGN SHALL BE SUITABLY ILLUMINATED BY A RELIABLE
 LIGHT SOURCE. EXTERNALLY AND INTERNALLY ILLUMINATED
 SIGNS SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY
 LIGHTING.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  