Date |
Text |
2007-09-07 10:44:45 | ** DENIED 2ND REVIEW FOR REVISIONS ** |
| |
| ** PLEASE SEE NOTE(S) FROM PREVIOUS REVIEW. |
| |
| |
| 1) NOTE: PLEASE SUBMIT PLANS WHICH CORRELATE. PLEASE |
| SEE EACH SHEET CONTAINS TWO COMPLETELY DIFFERENT PANEL |
| SCHEDULES FOR CIRCUITING. |
| IF THE FRONT SHEET E-1 IS ONLY FOR THE EXISTING PANELS, |
| THEN WHY ARE THERE NEW CIRCUITS BEING SHOWN? |
| THE SECOND SHEET E-2 INDICATES THESE AS EXISTING WITH |
| NEW CIRCUITS SHOWN? |
| PLEASE SEE EACH SHEET FOR POWER AND LIGHTING ALSO |
| CONTAINS ITEMS WHICH ARE BEING FED FROM SEPARATE |
| CIRCUITS TO THE SAME ITEMS DEPENDING ON THE PANEL |
| SCHEDULE YOU LOOK AT. |
| 408.4, 310.16, 240.4 |
| FBC 106.1.3, 106.3.5.4 |
| |
| 2) NOTE: ** THE PREVIOUS REVIEW NOTE WITH RESPECT TO |
| THE OVEN. PLEASE KNOW THE PREVIOUS PLANS INDICATED A |
| *LOCK OFF* DEVICE WAS GOING TO BE USED. THIS LED TO AN |
| UNDERSTANDING THAT THE OVENWAS A *HARDWIRED* UNIT AND |
| NOT CORD AND PLUG CONNECTED FROM THE MANUFACTURE. THIS |
| RESPONSE LETTER AND PLANS NOW MENTIONS THE RECEPTACLE |
| WAS REMOVED? IS THIS UNIT *HARWIRED* OR CORD AND PLUG |
| CONNECTED*? |
| IF THIS UNIT IS LISTED TO BE CORD AND PLUG CONNECTED |
| AND COMES LISTEDR AND/OR WITH A CORD FOR PLUGGING IN, |
| THEN DISCONNECT IS NOT REQUIRED AND A STANDARD |
| RANGE/OVEN RECEPTACLES MAY BE SUED WITH OUT A |
| DISCONNECT BEING REQUIRED. |
| IF THIS UNIT IS LISTED TO BE HARDWIRED OR COMES WITH A |
| WHIP TO HARDWIRE THEN A DISCONNECTING MEANS IF NOT |
| WITHIN SITE OF THE PANEL IS REQUIRED. |
| |
| 3) NOTE: PLEASE SEE SHEET E-1 IS NOT SIGNED, DATED OR |
| SEALED BY THE ENGINEER OF RECORD. |
| FAC 61G15-23.002, FS 471.025 |
| |
| |
| ** AS STATED ON THE PREVIOUS REVIEW, IF THERE ARE |
| COMMENTS OR QUESTIONS WHICH CAN BE GONE OVER ON THE |
| PHONE, PLEASE CALL. |
| THIS WOULD ALLEVIATE THE BACK AND FORTH ON PLANS ON ANY |
| ITEMS NOT CLEAR AND PERHAPS NOT UNDERSTOOD OR NOT TYPED |
| IN ANY MANOR. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |