Plan Review Notes
Plan Review Notes For Permit 06120363
Permit Number 06120363
Review Stop E
Sequence Number 4
Notes
Date Text
2007-08-27 18:33:44 
 *** DENIED REVIEW ***
  
 1) NOTE: PLEASE SUBMIT PLANS WHICH CORRELATE. PLEASE
 SEE EACH SHEET CONTAINS TWO COMPLETELY DIFFERENT PANEL
 SCHEDULES FOR CIRCUITING.
 PLEASE SEE EACH SHEET FOR POWER AND LIGHTING ALSO
 CONTAINS ITEMS WHICH ARE BEING FED FROM SEPARATE
 CIRCUITS TO THE SAME ITEMS DEPENDING ON THE PANEL
 SCHEDULE YOU LOOK AT.
 408.4, 310.16, 240.4
 FBC 106.1.3, 106.3.5.4
  
 2) NOTE: PLEASE SEE THE RE-LOCATED OVEN MENTIONS THIS
 WILL HAVE A BREAKER LOCK OFF DEVICE. ** IMPORTANT,
 PLEAS KNOW THAT THE TYPE OF DEVICE MUST HAVE THE LOCK
 OFF MECHANISM PERMANENTLY A PART OF THE BREAKER. *SNAP
 OR CLIP ON TYPE DEVICES ARE NOT ACCEPTABLE AND A
 DISCONNECTING MEANS WILL BE REQUIRED.
 ** 110.3, 90.4, 422.30, 422.31
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]