2007-05-08 13:40:49 | BUILDING REVISION TO A4 AND A5 IS DENIED | | | | THE TECHNICAL INFORMATION ON THE REVISIONS APPEARS TO | | BE CORRECT. HOWEVER, IT CAN NOT BE APPROVED DUE TO THE | | FOLLOWING ITEMS. | | | | 1) SHEET A4 OF THE APPROVED PLAN WAS SIGNED AND SEALED | | BY THE ENGINEER AND THE REVISED A4 IS SIGNED AND SEALED | | BY THE ARCHITECT. ONLY THE PERSON THAT SIGNED AND | | SEALED THE APPROVED PLAN SHEET CAN REVISE IT. | | | | 2) THE SUPPLEMENTAL DRAWING A5 THAT WAS SUBMITTED CAN | | NOT BE ACCEPTED BECAUSE IT DOES NOT REVISE SHEET A5 OF | | THE APPROVED PLANS. FOR RECORD KEEPING PURPOSES AND TO | | AVOID CONFUSION, IT SHOULD BE NUMBER DIFFERENTLY FOR | | EXAMPLE A5.1. SEE CITY AMENDMENT FBC 106.1.3. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|