Plan Review Notes
Plan Review Notes For Permit 06120363
Permit Number 06120363
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-02 12:18:55*** UNSAT 2NDREVIEW ***
  
 1) NOTE: PLEASE SEE ONLY THE 2005 NFPA-70 WAS ADDED TO
 PLANS.
 THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON
 ELECTRICAL SHEETS.
 2005 NFPA-2005
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE FBC R313, PLEASE SHOW ALL EXISTING
 OR NEW TO BE INSTALLED *SMOKE ALARMS* AS REQUIRED PER
 NFPA-72 11-5.1.1, 11.8.3
 PLEASE SEE THIS WAS NOT DONE, ONLY WHAT APPEARS TO BE
 THREE VERY FAINT *SMOKE DETECTORS* WERE ADDED TO FIRST
 FLOOR ONLY. PLEASE KNOW THIS COMMENT IS FOR ALL
 EXISTING TO BE SHOWN MEETING THE CURRENT CODE OR NEW TO
 BE INSTALLED.
 * PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.THIS WAS MENTIONED IN PREVIOUS NOTE FOR SMOKE
 ALARMS UNLESS THIS RESIDENCE DOES CONTAIN A FIRE ALARM
 PANEL?
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 3) NOTE: PLEASE VERIFY RECEPTACLE SPACING FOR NEW WALL
 AREAS IN ADDITION AREA OF KITCHEN/BREAKFAST AREA PER
 210.52. PLEASE SEE WALLS 2FT OR MORE. PLEASE SEE ONLY
 ONE WAS ADDED.
  
 4) NOTE: PLEASE CLARIFY THESE CIRCUITS. PANEL SCHEDULES
 DO NOT DIFFERENTIATE THE NEW AND EXISTING CIRCUITS WITH
 ANY DESIGNATION SO IT IS UNCLEAR IF THE NEW ADDITION
 AREA FOR BREAKFAST/DINING MEETS THIS REQUIREMENT.
 PLEASE SEE 210.52B1 WHICH REQUIRES ALL RECEPTACLE
 CIRCUITS IN DINING, KITCHEN, BREAKFAST AREAS AND AREAS
 OF THE LIKE TO BE ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS.
 PLEASE KNOW IF THERE ARE MORE THAN 3, THEN THE LOADS
 SHALL BE FIGURED ACCORDINGLY.
 PLEASE SEE THE FOLLOWING SECTIONS. 210.52B1, 210.11B1,
 220.52A
  
 5) NOTE: PLEASE SEE NEW RECEPTACLES BEING ADDED TO
 VESTIBULE AREA WHICH ARE REQUIRED TO BE GFI /GFI
 PROTECTED. PLEASE SEE THE PREVIOUS PLANS WERE REDLINED
 FOR THE SINGLE RECEPTACLE WHICH WAS PREVIOUSLY SHOWN TO
 BE GFI PER 210.8 AND THE SAME ONE AS PREVIOUSLY SHOWN
 AND NOW THE NEW ONES ALSO NEED TO INDICATE THE GFI
 PROTECTION.
 210.8A7
  
 6) NOTE: PLEASE CLARIFY LOAD CALCULATIONS AS NOTED IN
 PREVIOUS REVIEW. PLEASE SEE THESE NOW INDICATE *SPACE
 HEATERS*? PLEASE SEE THIS SECTIONS INDICATES *SPACE
 HEATERS* AND *CENTRAL HEAT*, HOW DOES THE LOAD
 CALCULATIONS SHOW ALL THESE ARE SPACE HEATERS AND AT
 65%. ? ARE THESE *SPACE HEATERS*?
 SEE 220.83B FOR LOAD CALCULATIONS WHEN ADDING HEAT LOAD
 TO AN EXISTING DWELLING. PLEASE SEE THE HEAT LOADS FOR
 UNITS SHALL BE FIGURED AT 100% AS SHOWN ON PANEL B.
 THIS DOES PERMIT THE FIRST 8KVA AT 100% REMAINDER AT
 40%,INSTEAD OF THE FIRST 10KVA AT 100% ,THEN HEAT AT
 100%.
  
 8) NOTE:PLEASE SEE LOAD CALCULATIONS INDICATE THE NEW
 RECESSED LIGHTS, HOWEVER RESPONSE DOES NOT MENTION IF
 THERE ARE OTHER FIXTURES IN THE EXISTING DWELLING? ARE
 THESE THE ONLY ONES?
 PLEASE SEE 220.14D WHICH IF THE AMOUNT OF RECESSED
 LIGHTS IN DWELLING ARE ABOVE 20, THEN THE TOTAL NUMBER
 SHALL BE BASED ON THE MAXIMUM WATTAGE PER FIXTURE TIMES
 THE AMOUNT OF FIXTURES ADDED TO THE 3VA PER SQ FT.
 PLEASE SEE THE 2002 NEC SECTION 220.3(B)(4)
  
 9) NOTE:PLEASE SEE THE CIRCUIT FOR THE AHU ON PLANS
 SHOWS 28/30 YET PANEL SCHEDULE SHOWS THESE SAME
 CIRCUITS FOR GENERAL LTS ETC.
 PLEASE SEE 408.4 AND COMMENTARY FROM CODE WHICH IS
 BEING SHOWN BELOW. PLEASE INDICATE NEW AND EXISTING
 CIRCUITS.
  
 * SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
  
 10) NOTE: PLEASE SEE AS SOME NOTES WERE REPEATED FOR
 CODE COMPLIANCE ONLY A NOTICE FOR FS 553.80(2)(B) IS
 BEING GIVEN AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH