2007-03-02 12:18:55 | *** UNSAT 2NDREVIEW *** |
| |
| 1) NOTE: PLEASE SEE ONLY THE 2005 NFPA-70 WAS ADDED TO |
| PLANS. |
| THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON |
| ELECTRICAL SHEETS. |
| 2005 NFPA-2005 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE SEE FBC R313, PLEASE SHOW ALL EXISTING |
| OR NEW TO BE INSTALLED *SMOKE ALARMS* AS REQUIRED PER |
| NFPA-72 11-5.1.1, 11.8.3 |
| PLEASE SEE THIS WAS NOT DONE, ONLY WHAT APPEARS TO BE |
| THREE VERY FAINT *SMOKE DETECTORS* WERE ADDED TO FIRST |
| FLOOR ONLY. PLEASE KNOW THIS COMMENT IS FOR ALL |
| EXISTING TO BE SHOWN MEETING THE CURRENT CODE OR NEW TO |
| BE INSTALLED. |
| * PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| ALARMS.THIS WAS MENTIONED IN PREVIOUS NOTE FOR SMOKE |
| ALARMS UNLESS THIS RESIDENCE DOES CONTAIN A FIRE ALARM |
| PANEL? |
| THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| FOR OTHER NEW HOMES. |
| ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE*. |
| PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| |
| 3) NOTE: PLEASE VERIFY RECEPTACLE SPACING FOR NEW WALL |
| AREAS IN ADDITION AREA OF KITCHEN/BREAKFAST AREA PER |
| 210.52. PLEASE SEE WALLS 2FT OR MORE. PLEASE SEE ONLY |
| ONE WAS ADDED. |
| |
| 4) NOTE: PLEASE CLARIFY THESE CIRCUITS. PANEL SCHEDULES |
| DO NOT DIFFERENTIATE THE NEW AND EXISTING CIRCUITS WITH |
| ANY DESIGNATION SO IT IS UNCLEAR IF THE NEW ADDITION |
| AREA FOR BREAKFAST/DINING MEETS THIS REQUIREMENT. |
| PLEASE SEE 210.52B1 WHICH REQUIRES ALL RECEPTACLE |
| CIRCUITS IN DINING, KITCHEN, BREAKFAST AREAS AND AREAS |
| OF THE LIKE TO BE ON ONE OR MORE OF THE SMALL APPLIANCE |
| CIRCUITS. |
| PLEASE KNOW IF THERE ARE MORE THAN 3, THEN THE LOADS |
| SHALL BE FIGURED ACCORDINGLY. |
| PLEASE SEE THE FOLLOWING SECTIONS. 210.52B1, 210.11B1, |
| 220.52A |
| |
| 5) NOTE: PLEASE SEE NEW RECEPTACLES BEING ADDED TO |
| VESTIBULE AREA WHICH ARE REQUIRED TO BE GFI /GFI |
| PROTECTED. PLEASE SEE THE PREVIOUS PLANS WERE REDLINED |
| FOR THE SINGLE RECEPTACLE WHICH WAS PREVIOUSLY SHOWN TO |
| BE GFI PER 210.8 AND THE SAME ONE AS PREVIOUSLY SHOWN |
| AND NOW THE NEW ONES ALSO NEED TO INDICATE THE GFI |
| PROTECTION. |
| 210.8A7 |
| |
| 6) NOTE: PLEASE CLARIFY LOAD CALCULATIONS AS NOTED IN |
| PREVIOUS REVIEW. PLEASE SEE THESE NOW INDICATE *SPACE |
| HEATERS*? PLEASE SEE THIS SECTIONS INDICATES *SPACE |
| HEATERS* AND *CENTRAL HEAT*, HOW DOES THE LOAD |
| CALCULATIONS SHOW ALL THESE ARE SPACE HEATERS AND AT |
| 65%. ? ARE THESE *SPACE HEATERS*? |
| SEE 220.83B FOR LOAD CALCULATIONS WHEN ADDING HEAT LOAD |
| TO AN EXISTING DWELLING. PLEASE SEE THE HEAT LOADS FOR |
| UNITS SHALL BE FIGURED AT 100% AS SHOWN ON PANEL B. |
| THIS DOES PERMIT THE FIRST 8KVA AT 100% REMAINDER AT |
| 40%,INSTEAD OF THE FIRST 10KVA AT 100% ,THEN HEAT AT |
| 100%. |
| |
| 8) NOTE:PLEASE SEE LOAD CALCULATIONS INDICATE THE NEW |
| RECESSED LIGHTS, HOWEVER RESPONSE DOES NOT MENTION IF |
| THERE ARE OTHER FIXTURES IN THE EXISTING DWELLING? ARE |
| THESE THE ONLY ONES? |
| PLEASE SEE 220.14D WHICH IF THE AMOUNT OF RECESSED |
| LIGHTS IN DWELLING ARE ABOVE 20, THEN THE TOTAL NUMBER |
| SHALL BE BASED ON THE MAXIMUM WATTAGE PER FIXTURE TIMES |
| THE AMOUNT OF FIXTURES ADDED TO THE 3VA PER SQ FT. |
| PLEASE SEE THE 2002 NEC SECTION 220.3(B)(4) |
| |
| 9) NOTE:PLEASE SEE THE CIRCUIT FOR THE AHU ON PLANS |
| SHOWS 28/30 YET PANEL SCHEDULE SHOWS THESE SAME |
| CIRCUITS FOR GENERAL LTS ETC. |
| PLEASE SEE 408.4 AND COMMENTARY FROM CODE WHICH IS |
| BEING SHOWN BELOW. PLEASE INDICATE NEW AND EXISTING |
| CIRCUITS. |
| |
| * SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO |
| REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND |
| CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| REQUIRED BY THIS SECTION.* |
| |
| 10) NOTE: PLEASE SEE AS SOME NOTES WERE REPEATED FOR |
| CODE COMPLIANCE ONLY A NOTICE FOR FS 553.80(2)(B) IS |
| BEING GIVEN AT THIS TIME. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |