2007-03-07 16:14:35 | DENIED BY BUILDING | | | | 1) IN REGUARD TO THE SUBSURFACE SOIL REPORT REQUIRED BY | | FBC 1802.2.1. THE REPORT CAN BE SUBMITTED AFTER THE | | DEMO WORK BUT BEFORE COMMENCING THE NEW CONSTRUCTION. | | IT WILL BE A PROVISO. | | | | 2) ON SHEET A6 A SIMPSON LTH 1 WAS ADDED TO THE ANCHOR | | SCHEDULE. THERE IS NO SIMPSON CONNECTOR THAT | | CORRESPONDS WITH THIS. DID YOU INTEND TO SPECIFY A | | SIMPSON LTA 1? | | | | 3) SPECIFY ON THE PLANS THE METHOD OF TERMITE TREATMENT | | WILL BE EMPLOYED TO SATISFY THE REQUIREMENTS OF | | R320.1. | | | | 4)WPB ADMIN CODE 106.3* PRODUCT | | APPROVALS. THOSE PRODUCTS WHICH ARE | | REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL. | | | | 5) RAS 117 CALCULATIONS ARE REQUIRED FOR THE GAF | | RUBEROID MODIFIED ROOF SYSTEM SPECIFING THE ENHANCED | | FASTENER SPACING IN THE SAMPLE SUBMITTED DOES NOT | | CORRESPOND TO THE SYSTEM SPECIFIED IN THE NOA. THE RAS | | 117 CALCULATIONS CAN BE SUBMITTED AS A PROVISO WHEN THE | | ROOFING CONTRACTOR APPLIES FOR PERMIT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|