2007-03-07 16:14:35DENIED BY BUILDING
  
 1) IN REGUARD TO THE SUBSURFACE SOIL REPORT REQUIRED BY
 FBC 1802.2.1. THE REPORT CAN BE SUBMITTED AFTER THE
 DEMO WORK BUT BEFORE COMMENCING THE NEW CONSTRUCTION.
 IT WILL BE A PROVISO.
  
 2) ON SHEET A6 A SIMPSON LTH 1 WAS ADDED TO THE ANCHOR
 SCHEDULE. THERE IS NO SIMPSON CONNECTOR THAT
 CORRESPONDS WITH THIS. DID YOU INTEND TO SPECIFY A
 SIMPSON LTA 1?
  
 3) SPECIFY ON THE PLANS THE METHOD OF TERMITE TREATMENT
 WILL BE EMPLOYED TO SATISFY THE REQUIREMENTS OF
 R320.1.
  
 4)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5) RAS 117 CALCULATIONS ARE REQUIRED FOR THE GAF
 RUBEROID MODIFIED ROOF SYSTEM SPECIFING THE ENHANCED
 FASTENER SPACING IN THE SAMPLE SUBMITTED DOES NOT
 CORRESPOND TO THE SYSTEM SPECIFIED IN THE NOA. THE RAS
 117 CALCULATIONS CAN BE SUBMITTED AS A PROVISO WHEN THE
 ROOFING CONTRACTOR APPLIES FOR PERMIT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  