Plan Review Notes
Plan Review Notes For Permit 06120363
Permit Number 06120363
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-27 19:13:40** UNSAT **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS AS THIS PERMIT APPLICATION HAS BEEN MADE UNDER
 THE NEW 2005 NEC.
 THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON
 ELECTRICAL SHEETS.
 2005 NFPA-2005
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE FBC R313, PLEASE SHOW ALL EXISTING
 OR NEW TO BE INSTALLED SMOKE ALARMS AS REQUIRED PER
 NFPA-72 11-5.1.1, 11.8.3
  
 3) NOTE: PLEASE VERIFY RECEPTACLE SPACING FOR NEW WALL
 AREAS IN ADDITION AREA OF KITCHEN/BREAKFAST AREA PER
 210.52. PLEASE SEE WALLS 2FT OR MORE.
  
 4) NOTE: PLEASE SEE 210.52B1 WHICH REQUIRES ALL
 RECEPTACLE CIRCUITS IN DINING, KITCHEN, BREAKFAST AREAS
 AND AREAS OF THE LIKE TO BE ON ONE OR MORE OF THE SMALL
 APPLIANCE CIRCUITS.
 PLEASE SEE PANEL SCHEDULES DO NOT INDICATE THESE. ?
 PLEASE SEE LOAD CALCULATIONS FOR SERVICE SEEM TO SHOW
 3- SMALL APPLIANCE CIRCUITS, HOWEVER THESE ARE NOT
 LISTED ON EITHER PANEL SCHEDULE?
 PLEASE KNOW IF THERE ARE MORE THAN 3, THEN THE LOADS
 SHALL BE FIGURED ACCORDINGLY.
 PLEASE SEE THE FOLLOWING SECTIONS. 210.52B1, 210.11B1,
 220.52A
  
 5) NOTE: PLEASE INDICATE A NEW OR EXISTING GFI RECEPT
 LOCATED AT THE NEW CONDENSING UNIT BEING ADDED AT THE
 SIDE OF DWELLING. PLEASE SEE 210.63 AND 210.8A3.
  
 6) NOTE: PLEASE SEE NEW LIVING ROOM WHICH WILL REQUIRE
 A LIGHT FIXTURE OF SOME KIND TO BE INSTALLED. PLEASE
 SEE OTHER EXCEPTIONS IN 210.70 WHICH WILL PERMIT THE
 SWITCHING OF ? SWITCHED RECEPT ? OR RECESSED LTS.
 PLEASE SEE LS 101 7.8
  
 7) NOTE: PLEASE SEE 220.83B FOR LOAD CALCULATIONS WHEN
 ADDING HEAT LOAD TO AN EXISTING DWELLING. PLEASE SEE
 THE HEAT LOADS FOR UNITS SHALL BE FIGURED AT 100% AS
 SHOWN ON PANEL B.
 THIS DOES PERMIT THE FIRST 8KVA AT 100% REMAINDER AT
 40%,INSTEAD OF THE FIRST 10KVA AT 100% ,THEN HEAT AT
 100%.
  
 8) NOTE: PLEASE SEE 220.14D WHICH IF THE AMOUNT OF
 RECESSED LIGHTS IN DWELLING ARE ABOVE 20, THEN THE
 TOTAL NUMBER SHALL BE BASED ON THE MAXIMUM WATTAGE PER
 FIXTURE TIMES THE AMOUNT OF FIXTURES ADDED TO THE 3VA
 PER SQ FT.
 PLEASE SEE THE 2002 NEC SECTION 220.3(B)(4)
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]