Plan Review Notes
Plan Review Notes For Permit 06120363
Permit Number 06120363
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-26 18:02:40DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)BASED ON THE 2006 SUPPLEMENT TO THE 2004 FBC
 RESIDENTIAL EFFECTIVE DECEMBER 8, 2006, THE EXPOSURE
 CATEGORY FOR THIS PROJECT IS EXPOSURE C. PLEASE MAKE
 ALL NECESSARY CORRECTIONS.
  
 4)SUBMIT A SUBSURFACE SOIL REPORT. FBC 1802.2.1
 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 5)THE PROPERTY IS LOCATED IN AN A5 FLOOD ZONE. THE
 MINIMUM ELEVATION FOR THE FINISHED FLOOR IS 7' 6",
 WHICH INCLUDES THE 6" FREEBOARD REQUIRED BY THE CITY OF
 WEST PALM BEACH. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 6)PLEASE UPDATE THE STRUCTURAL NOTES ON SHEET A0. THE
 2006 AMENDMENTS TO THE 2004 FBC WILL APPLY TO THIS
 PROJECT. ALSO, THE 2002 EDITIONS OF ACI- 315, 318 AND
 530 APPLY PER THE REFERENCED STANDARDS OF THE FLORIDA
 BUILDING CODE.
  
 7)ROOF SHEATHING FASTENER SPACING IS REQUIRED TO
 COMPLY WITH FBC R803.2.3.1 (2006 AMENDMENTS) . WOOD
 STRUCTURAL PANELS SHALL BE FASTENED TO ROOF FRAMING
 WITH 8D RING- SHANK AT 6 INCHES ON CENTER AT EDGES AND
 6 INCHES ON CENTER AT INTERMEDIATE FRAMING. SPACING OF
 RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN
 NAILING ZONE 3FOR 130MPH OR GREATER DESIGN WIND
 SPEEDS. PLEASE REVISE NOTE ON A6.
  
 8) PLEASE SPECIFY THE NUMBER OF FASTENERS AND CORRECT
 THE FASTENER TYPE FOR THE SIMPSON HETAL 20 CONNECTORS
 IN THE TRUSS ANCHOR SCHEDULE ON A6.
  
 9) SHOW COMPLIANCE WITHR320.1.
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION
 (SEE SECTION 202 , REGISTERED TERMITICIDE). UPON
 COMPLETION OF THE APPLICATION OF THE TERMITE PROTECTIVE
 TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL BE ISSUED
 TO THE BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.?
  
 10) SUBMIT TRUSS DRAWINGS AS REQUIRED BY R802.10.1.
 TRUSS DESIGN DRAWINGS.
 TRUSS DESIGN DRAWINGS, PREPARED IN CONFORMANCE WITH
 SECTION R802.10.1 , SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO INSTALLATION. THE TRUSS
 LAYOUT AND TRUSS DRAWING ARE REQUIRED TO BE SIGNED,
 SEALED AND DATED BY THE TRUSS ENGINEER AND REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 PROJECT.
  
 11) SPECIFY THE TRUSS DEAD AND LIVE LOADS FOR THE TOP
 AND BOTTOM CORDS AND TOTAL LOADS ON THE PLANS.
  
 12)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 13) THE PRODUCT APPROVAL FOR THE POLYGLASS MODIFIED
 BITUMEN ROOF SYSTEM ON PAGE 37 OF NOA 06-0410.06 HAS A
 MAXIMUM DESIGN PRESSURE OF -45 WITH LIMITATION NUMBER
 9. THIS LIMITATION DOES NOT ALLOW ENHANCED FASTENING
 WHICH IS REQUIRED TO ACHIEVE THE UPLIFT PRESSURES OF
 ROOF ZONES 2 AND 3. PLEASE ALSO NOTE THAT LIMITATION
 NUMBER 7 OF THIS NOA REQUIRES SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING.
  
 14)SPECIFYTHE METHOD OF ATTACHMENT THAT WILL BE
 USED TO INSTALL THE MONIER CONCRETE ROOF TILE. PLEASE
 CIRCLE THE APPROPRIATE FASTENER OR ADHESIVE SYSTEM ON
 THE NOA. PLEASE BE SURE THAT THE ATTACHMENT SELECTED
 WILL PROVIDE ADEQUATE RESISTANCE FOR A MOMENT BASED
 SYSTEM.
  
 NOTE: SEE MARKS ON THE PLAN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714