Plan Review Notes
Plan Review Notes For Permit 06120355
Permit Number 06120355
Review Stop P
Sequence Number 3
Notes
Date Text
2007-06-18 16:57:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. COVER SHEET INDICATES ADDRESS AT 901 S FLAGLER DR.,
 BUT THE PERMIT NUMBER AND PROPERTY CONTROL NUMBER
 INDICATE THE ADDRESS AS 355 JEFFERSON RD. PLEASE
 CONTACT LILI URSA AT 822-1239 AND ASSURE THE CORRECT
 ADDRESS.
 ****RESPONSE NOTED, BUT THE ADDRESS HAS NOT CHANGED.
 THE ADDRESS ON THE APPLICATION IS NOT CORRECT PER THE
 REVIEW OF LILI URSA FROM ADDRESSING.
 ******NO RESPONSE/NOT ADDRESSED. NEW PREMIT APPLICATION
 NOW SHOWS 900 S. FLAGLER DR.
  
 2. OK
 3. OK
  
 4. SHT A-1 TYPICAL ACCESSIBLE RESTROOM DETAIL. SHOW THE
 FOLLOWING:
 A. 11-4.16.5 FLUSH CONTROLS
 ****NOT ADDRESSED
 ******NO RESPONSE/NOT ADDRESSED
 B. OK
 C. 11-4.19.5 FAUCETS
 ****NOT ADDRESSED
 ******NO RESPONSE/NOT ADDRESSED
  
 5. SUBMIT A DETAIL FOR THE SINKS IN ROOMS 103 & 104
 SHOWING COMPLIANCE WITH THE FOLLOWING.
 A. OK
 B. OK
 C. 11-4.24.4 SINK DEPTH
 ****NOT ADDRESSED
 ******NO RESPONSE/NOT ADDRESSED
 D. OK
 E. OK
 F. 11-4.24.7 FAUCETS
 ****NOT ADDRESSED
 ******NO RESPONSE/NOT ADDRESSED
  
 6. OK
 7. OK
 8. OK
 10. OK
 11. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 808-6731
 E-MAIL [email protected]