2007-06-08 12:46:52 | |
| ** UNSAT 3RD REVIEW** |
| |
| ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ALONG |
| WITH A NEW NOTE BASED ON REVISED NOTES ON PLANS NEED TO |
| BE ADDRESSED. |
| |
| 1) NOTE:PLEASE SEE PREVIOUS NOTES WHICH REQUESTED THE |
| MINIMUM LEVELS FOR FBC ADA LEVELS TO BE STATED ON |
| PLANS. AS NOTED PREVIOUSLY THIS COULD BE SHOWN ON PLANS |
| AND LEGEND. IT IS KNOWN THESE FIRE ALARM AND ANY FIRE |
| SPRINKLERS WILL BE UNDER SEPARATE PERMITS, HOWEVER THE |
| BASE PLANS ARE REQUIRED TO SHOW THE *MINIMUM* |
| REQUIREMENTS FOR THIS. |
| PLEASE SEE 11-4.28.1 FOR LOCATIONS, 11-4.28.2 AND .3(4) |
| FOR LEVELS. |
| |
| 2) NOTE: PLEASE SEE THE PREVIOUS SUBMITTED ENERGY |
| CALCULATIONS HAD COMMENTS AS THEY NEEDED SOME |
| COORDINATION WITH PLANS, HOWEVER THIS SUBMITTED PACKAGE |
| DOES NOT CONTAIN ANY SUBMITTED ENERGY CALCULATIONS FOR |
| REVIEW OF METHOD, COORDINATION ETC AS REQUIRED PER FBC |
| 13-415.AB.1.1. |
| PLEASE KNOW AS THESE WERE NOT SUBMITTED, NO REVIEW OF |
| THESE ITEMS CAN BE DONE. |
| |
| 3) NOTE: PLEASE SEE THE REVISED NOTES ON E-1 NOW STATES |
| IN *SPECIAL ENERGY EFFICIENT NOTES* , NOTE #5 THAT ALL |
| INTERIOR LIGHTING IS GOING TO MEET 13-415.1.ABC.1.1, |
| HOWEVER THE PLANS DO NOT SHOW THIS. THERE IS NOT SUCH |
| DEVICES ON PLANS, NO CONTROLS, NO SCHEDULING, NO OVER |
| RIDE TIMES ETC. |
| PLEASE SEE CHAPTER 13 THIS SECTION AS STATED AND SEE |
| PREVIOUS SUBMITTED PLANS FOR THIS SAME ITEM. |
| |
| ** EVEN IF PLANS ARE STAMPED BY THE STATE, IF THE PLANS |
| DO NOT CORRELATE FOR CODE COMPLIANCE THEY CAN NOT BE |
| ISSUED AND STAMPED. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |