Plan Review Notes
Plan Review Notes For Permit 06120355
Permit Number 06120355
Review Stop P
Sequence Number 2
Notes
Date Text
2007-05-07 11:38:13DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. COVER SHEET INDICATES ADDRESS AT 901 S FLAGLER DR.,
 BUT THE PERMIT NUMBER AND PROPERTY CONTROL NUMBER
 INDICATE THE ADDRESS AS 355 JEFFERSON RD. PLEASE
 CONTACT LILI URSA AT 822-1239 AND ASSURE THE CORRECT
 ADDRESS.
 ****RESPONSE NOTED, BUT THE ADDRESS HAS NOT CHANGED.
 THE ADDRESS ON THE APPLICATION IS NOT CORRECT PER THE
 REVIEW OF LILI URSA FROM ADDRESSING.
  
 2. CIVIL SHT 1 OF 2 STATES 1" BACKFLOW PREVENTOR. PER
 TABLE 603(D) THE BACKFLOW PREVENTOR ASSEMBLIES SHALL BE
 AT LEAST THE SAME SIZE AS THE LINE IN WHICH THEY ARE
 INSTALLED. THE WASTER SERVICE IS SHOWN AT 1-1/2".
 PLEASE PROVIDE THE APPROVED SIZE RPZV BACKFLOW.
 ****SHEETS HAVE BEEN DELETED. COMMENT WILL BE TAKEN
 CARE OF AT THE TIME OF INSPECTION.
  
 3. OK
  
 4. SHT A-1 TYPICAL ACCESSIBLE RESTROOM DETAIL. SHOW THE
 FOLLOWING:
 A. 11-4.16.5 FLUSH CONTROLS
 ****NOT ADDRESSED
 B. OK
 C. 11-4.19.5 FAUCETS
 ****NOT ADDRESSED
  
 5. SUBMIT A DETAIL FOR THE SINKS IN ROOMS 103 & 104
 SHOWING COMPLIANCE WITH THE FOLLOWING.
 A. OK
 B. OK
 C. 11-4.24.4 SINK DEPTH
 ****NOT ADDRESSED
 D. OK
 E. OK
 F. 11-4.24.7 FAUCETS
 ****NOT ADDRESSED
  
 6. OK
 7. OK
 8. OK
 10. OK
 11. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 808-6731
 E-MAIL [email protected]