Plan Review Notes For Permit 06120355 |
Permit Number |
06120355 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-05-07 11:38:13 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 11 | | FBC-2004 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW: | | | | 1. COVER SHEET INDICATES ADDRESS AT 901 S FLAGLER DR., | | BUT THE PERMIT NUMBER AND PROPERTY CONTROL NUMBER | | INDICATE THE ADDRESS AS 355 JEFFERSON RD. PLEASE | | CONTACT LILI URSA AT 822-1239 AND ASSURE THE CORRECT | | ADDRESS. | | ****RESPONSE NOTED, BUT THE ADDRESS HAS NOT CHANGED. | | THE ADDRESS ON THE APPLICATION IS NOT CORRECT PER THE | | REVIEW OF LILI URSA FROM ADDRESSING. | | | | 2. CIVIL SHT 1 OF 2 STATES 1" BACKFLOW PREVENTOR. PER | | TABLE 603(D) THE BACKFLOW PREVENTOR ASSEMBLIES SHALL BE | | AT LEAST THE SAME SIZE AS THE LINE IN WHICH THEY ARE | | INSTALLED. THE WASTER SERVICE IS SHOWN AT 1-1/2". | | PLEASE PROVIDE THE APPROVED SIZE RPZV BACKFLOW. | | ****SHEETS HAVE BEEN DELETED. COMMENT WILL BE TAKEN | | CARE OF AT THE TIME OF INSPECTION. | | | | 3. OK | | | | 4. SHT A-1 TYPICAL ACCESSIBLE RESTROOM DETAIL. SHOW THE | | FOLLOWING: | | A. 11-4.16.5 FLUSH CONTROLS | | ****NOT ADDRESSED | | B. OK | | C. 11-4.19.5 FAUCETS | | ****NOT ADDRESSED | | | | 5. SUBMIT A DETAIL FOR THE SINKS IN ROOMS 103 & 104 | | SHOWING COMPLIANCE WITH THE FOLLOWING. | | A. OK | | B. OK | | C. 11-4.24.4 SINK DEPTH | | ****NOT ADDRESSED | | D. OK | | E. OK | | F. 11-4.24.7 FAUCETS | | ****NOT ADDRESSED | | | | 6. OK | | 7. OK | | 8. OK | | 10. OK | | 11. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 808-6731 | | E-MAIL [email protected] |
|