Notes
Date Text
2007-04-16 15:28:032007-04-16 15:28:03
 *** NOTES ADDED.
  
 1) NOTE; PLEASE SEE NOTE #1 FROM REVIEW DATED 3/31/07
 HAS BEEN REMOVED AS THE ES-1 SHEET WAS LOCATED IN WITH
 THE CIVIL SHEETS.
 PLEASE BE SURE TO INSERT THE ES-1 SHEETS IN WITH THE
 ELECTRICAL PLANS. PLEASE SUBMIT STRUCTRUAL DETAIL FOR
 NEW CEILING HUNG TRANSFORMER.
 PLEASE CALRIFY THAT THE TRANSFORMER WILL NOT BE ABOVE
 ANY SUSPENDED CEILING ETC PER 450.13
2007-03-31 12:03:15 
  
 *** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FORM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING AND SOME NEW COMMENTS BASED
 ON CHANGES ON PLANS.
  
  
 1) NOTE:
  
 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT
 CORRELATE WITH THE ELECTRICAL PLANS SUBMITTED OR THE
 FIXTURES AS STATED ON LEGEND, WATTAGE ON FIXTURES, THE
 AMOUNT OF FIXTURES ETC.
 PLEASE COORDINATE THE USE, LIGHTING POWER DENSITIES AND
 METHOD OF CALCULATIONS BEING USED.
 PLEASE SEE THE INPUT DATA REPORT.
 PLEASE CLARIFY WHY PLANS CONTAIN NOTES FOR LIGHTING
 CONTROLS REQUIRED IF THE BUILDING IS OVER 5K SQ FT. IF
 THE BUILDING WHICH IS BEING SHOWN IS UNDER THE 5K,
 PLEASE DO NOT REFERENCE THESE CODE REQUIREMENTS UNLESS
 IT IS THE INTENTION AND DESIGN TO PROVIDE LIGHTING
 ENERGY EFFICIENT CONTROLS FOR AUTO-MATED SHUT OF
 LIGHTING.
 PLEASE SEE 13-415.1AB.1.1, 13-415.2
 PLEASE ALSO SEE 13-103.1.1.1 AS THE ENERGY CALCULATIONS
 SHALL BE SIGNED, DATED AND SEALED BY THE RESPONSIBLE
 DESIGNERS.
 PLEASE SEE THE CALCULATIONS SUBMITTED ARE PHOTOCOPIES
 OF SIGNED SHEETS.
  
 3) NOTE: PLEASE SEE THAT THE CODE SECTION REFLECTED FOR
 WIRING OF EMERGENCY/EXIT LIGHTS SHOULD BE 700.12E.
 PLEASE SEE THIS SEEMS TO HAVE BEEN A MISPRINT AND WOULD
 HAVE BEEN REDLINED IF THE PLANS WERE NOT COMING BACK
 FOR OTHER COMMENTS.
 PREVIOUS REVIEW NOTE:
  
 4) NOTE: PLEASE SEE THAT MINIMUM STROBES AND HORN
 LEVELS SHALL BE STATED ON PLANS FOR FBC 11-4.28.2,
 .3(4).
 THIS COMMENT WAS MADE ON PREVIOUS REVIEW AND NOT
 MINIMUM LEVELS ARE STATED FOR ADA COMPLIANCE. THIS CAN
 BE DONE ON THE SYMBOL LEGEND.
 ** PLEASE KNOW EVEN THOUGH THE FIRE ALARM WILL BE UNDER
 A SEPARATE PERMIT THIS IS REQUIRED ON THE PLANS AT THIS
 TIME.
 ** PLEASE ALSO KNOW THE SECURITY SYSTEM AS SHOWN WILL
 ALSO BE UNDER A SEPARATE PERMIT.
  
 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS IF
 THE SERVICE AS SHOWN IS BEING FED FROM AN EXISTING
 SERVICE.
 220, 215.3, 230.42
 PLEASE ALSO SEE THAT ALL CONTINUOUS LOADS SHALL BE
 SHOWN AT 125%. 215.3 AND 230.42.
  
 6) NOTE: PLEASE SEE *F*,*S* AND *WM* SHEETS CONTAIN A
 RAISED SEAL OVER A PHOTO-COPIED SIGNATURE FOR THE
 ENGINEER * MR. ALBERT KWAN*. THIS HAS BEEN DONE ON A
 REPETITIVE BASIS BY THE SAID DESIGNER ON SEVERAL
 PROJECTS WHICH HAVE BEEN SUBMITTED TO THIS JURISDICTION
 AND ON SEVERAL OCCASIONS THE NOTES HAVE BEEN ISSUED TO
 THIS ENGINEER THAT AN *ORIGINAL SIGNATURE* IS REQUIRED
 UNDER FLORIDA STATUTES 471.025 AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002.
 THE PREVIOUS SHEETS SUBMITTED WERE *PHOTO-COPIES* AND
 THE ONLY THING WHICH HAS CHANGED IS THE FACT THE
 PREVIOUS PLANS WITH THE PHOTO-COPIED SIGNATURE NOW HAS
 A RAISED SEAL OVER THE PHOTO-COPIED SIGNATURE.
 **PLEASE KNOW AT THIS TIME THESE SHEETS WILL BE
 RETAINED BY THIS OFFICE AND SENT TO THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS FOR REVIEW.
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]