2007-04-16 15:28:03 | 2007-04-16 15:28:03 |
| *** NOTES ADDED. |
| |
| 1) NOTE; PLEASE SEE NOTE #1 FROM REVIEW DATED 3/31/07 |
| HAS BEEN REMOVED AS THE ES-1 SHEET WAS LOCATED IN WITH |
| THE CIVIL SHEETS. |
| PLEASE BE SURE TO INSERT THE ES-1 SHEETS IN WITH THE |
| ELECTRICAL PLANS. PLEASE SUBMIT STRUCTRUAL DETAIL FOR |
| NEW CEILING HUNG TRANSFORMER. |
| PLEASE CALRIFY THAT THE TRANSFORMER WILL NOT BE ABOVE |
| ANY SUSPENDED CEILING ETC PER 450.13 |
2007-03-31 12:03:15 | |
| |
| *** UNSAT 2ND REVIEW ** |
| |
| ** PLEASE SEE SOME COMMENTS FORM PREVIOUS REVIEW ARE |
| STILL IN NEED OF ADDRESSING AND SOME NEW COMMENTS BASED |
| ON CHANGES ON PLANS. |
| |
| |
| 1) NOTE: |
| |
| 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT |
| CORRELATE WITH THE ELECTRICAL PLANS SUBMITTED OR THE |
| FIXTURES AS STATED ON LEGEND, WATTAGE ON FIXTURES, THE |
| AMOUNT OF FIXTURES ETC. |
| PLEASE COORDINATE THE USE, LIGHTING POWER DENSITIES AND |
| METHOD OF CALCULATIONS BEING USED. |
| PLEASE SEE THE INPUT DATA REPORT. |
| PLEASE CLARIFY WHY PLANS CONTAIN NOTES FOR LIGHTING |
| CONTROLS REQUIRED IF THE BUILDING IS OVER 5K SQ FT. IF |
| THE BUILDING WHICH IS BEING SHOWN IS UNDER THE 5K, |
| PLEASE DO NOT REFERENCE THESE CODE REQUIREMENTS UNLESS |
| IT IS THE INTENTION AND DESIGN TO PROVIDE LIGHTING |
| ENERGY EFFICIENT CONTROLS FOR AUTO-MATED SHUT OF |
| LIGHTING. |
| PLEASE SEE 13-415.1AB.1.1, 13-415.2 |
| PLEASE ALSO SEE 13-103.1.1.1 AS THE ENERGY CALCULATIONS |
| SHALL BE SIGNED, DATED AND SEALED BY THE RESPONSIBLE |
| DESIGNERS. |
| PLEASE SEE THE CALCULATIONS SUBMITTED ARE PHOTOCOPIES |
| OF SIGNED SHEETS. |
| |
| 3) NOTE: PLEASE SEE THAT THE CODE SECTION REFLECTED FOR |
| WIRING OF EMERGENCY/EXIT LIGHTS SHOULD BE 700.12E. |
| PLEASE SEE THIS SEEMS TO HAVE BEEN A MISPRINT AND WOULD |
| HAVE BEEN REDLINED IF THE PLANS WERE NOT COMING BACK |
| FOR OTHER COMMENTS. |
| PREVIOUS REVIEW NOTE: |
| |
| 4) NOTE: PLEASE SEE THAT MINIMUM STROBES AND HORN |
| LEVELS SHALL BE STATED ON PLANS FOR FBC 11-4.28.2, |
| .3(4). |
| THIS COMMENT WAS MADE ON PREVIOUS REVIEW AND NOT |
| MINIMUM LEVELS ARE STATED FOR ADA COMPLIANCE. THIS CAN |
| BE DONE ON THE SYMBOL LEGEND. |
| ** PLEASE KNOW EVEN THOUGH THE FIRE ALARM WILL BE UNDER |
| A SEPARATE PERMIT THIS IS REQUIRED ON THE PLANS AT THIS |
| TIME. |
| ** PLEASE ALSO KNOW THE SECURITY SYSTEM AS SHOWN WILL |
| ALSO BE UNDER A SEPARATE PERMIT. |
| |
| 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS IF |
| THE SERVICE AS SHOWN IS BEING FED FROM AN EXISTING |
| SERVICE. |
| 220, 215.3, 230.42 |
| PLEASE ALSO SEE THAT ALL CONTINUOUS LOADS SHALL BE |
| SHOWN AT 125%. 215.3 AND 230.42. |
| |
| 6) NOTE: PLEASE SEE *F*,*S* AND *WM* SHEETS CONTAIN A |
| RAISED SEAL OVER A PHOTO-COPIED SIGNATURE FOR THE |
| ENGINEER * MR. ALBERT KWAN*. THIS HAS BEEN DONE ON A |
| REPETITIVE BASIS BY THE SAID DESIGNER ON SEVERAL |
| PROJECTS WHICH HAVE BEEN SUBMITTED TO THIS JURISDICTION |
| AND ON SEVERAL OCCASIONS THE NOTES HAVE BEEN ISSUED TO |
| THIS ENGINEER THAT AN *ORIGINAL SIGNATURE* IS REQUIRED |
| UNDER FLORIDA STATUTES 471.025 AND FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.002. |
| THE PREVIOUS SHEETS SUBMITTED WERE *PHOTO-COPIES* AND |
| THE ONLY THING WHICH HAS CHANGED IS THE FACT THE |
| PREVIOUS PLANS WITH THE PHOTO-COPIED SIGNATURE NOW HAS |
| A RAISED SEAL OVER THE PHOTO-COPIED SIGNATURE. |
| **PLEASE KNOW AT THIS TIME THESE SHEETS WILL BE |
| RETAINED BY THIS OFFICE AND SENT TO THE FLORIDA BOARD |
| OF PROFESSIONAL ENGINEERS FOR REVIEW. |
| |
| 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| NOTICE AT THIS TIME. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |