Date |
Text |
2007-02-03 18:03:17 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 11 |
| FBC-2004 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. COVER SHEET INDICATES ADDRESS AT 901 S FLAGLER DR., |
| BUT THE PERMIT NUMBER AND PROPERTY CONTROL NUMBER |
| INDICATE THE ADDRESS AS 355 JEFFERSON RD. PLEASE |
| CONTACT LILI URSA AT 822-1239 AND ASSURE THE CORRECT |
| ADDRESS. |
| |
| 2. CIVIL SHT 1 OF 2 STATES 1" BACKFLOW PREVENTOR. PER |
| TABLE 603(D) THE BACKFLOW PREVENTOR ASSEMBLIES SHALL BE |
| AT LEAST THE SAME SIZE AS THE LINE IN WHICH THEY ARE |
| INSTALLED. THE WASTER SERVICE IS SHOWN AT 1-1/2". |
| PLEASE PROVIDE THE APPROVED SIZE RPZV BACKFLOW. |
| |
| 3. THE BRUH-HOSEIN-RUPP PARTNERSHIP REQUIRES A |
| CERTIFICATE OF AUTHORIZATION ON EACH SHEET THAT THE |
| FIRM NAME IS SHOWN ON THE TITLE BLOCK. PLEASE PROVIDE |
| ON EACH SHEET AS WELL AS ALL OTHER REQUIREMENTS OF FAC |
| 61G1-16.004 & FS 481.219, 481.2055. |
| |
| 4. SHT A-1 TYPICAL ACCESSIBLE RESTROOM DETAIL. SHOW THE |
| FOLLOWING: |
| A. 11-4.16.5 FLUSH CONTROLS |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| C. 11-4.19.5 FAUCETS |
| |
| 5. SUBMIT A DETAIL FOR THE SINKS IN ROOMS 103 & 104 |
| SHOWING COMPLIANCE WITH THE FOLLOWING. |
| A. 11-4.24.2 HEIGHT |
| B. 11-4.24.3 KNEE CLEARANCE |
| C. 11-4.24.4 SINK DEPTH |
| D. 11-4.24.5 CLEAR FLOOR SPACE - SHALL EXTEND A |
| MAXIMUM OF 19" UNDERNEATH THE SINK. (FIG 32). - CABINET |
| DOORS NOT APPROVED IN THE CLEAR FLOOR SPACE. |
| E. 11-4.24.6 EXPOSED PIPES & SURFACES |
| F. 11-4.24.7 FAUCETS |
| |
| 6. A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1. |
| PLEASE INDICATE THE LOCATION AND SUBMIT A DETAIL |
| SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| SUBSECTIONS AND SECTION 11-4.1.3(10)(A) PROVISIONS FOR |
| THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING IS THE |
| UNIT IS NOT A HI/LOW UNIT. |
| |
| 7. SHT A-1 FINISH SCHEDULE FOR RESTROOMS 110 & 111. |
| REMARKS INDICATE CERAMIC TILE TO 42" AFF. THE |
| REQUIREMENT PER SECTION 1210.2 IS FOR THE SMOOTH, HARD, |
| NONABSORBENT SURFACE TO BE INSTALLED UP TO 48". PLEASE |
| CORRECT THE REMARKS. |
| |
| 8. SHT M-1 SHOW THE FLOOR PLAN FOR THE SINK IN ROOM 104 |
| AS WELL AS THE SANITARY AND WATER RISER DIAGRAMS.-- |
| THE RISER DIAGRAM FOR THE SINK IN ROOM 103 DOES NOT |
| MEET THE CODE REQUIREMENT THAT STATES THE WASH MACHINE |
| SHALL CONNECT TO A BRANCH DRAIN OR STACK A MINIMUM OF |
| 3" IN DIAMETER. SHOW THE FUTURE STUB UP ON THE RISER. |
| THE W/M WILL ALSO REQUIRE A VENT CONNECTION WHEN THE |
| SANITARY IS CONNECTED IN THE FUTURE. SECTIONS 406.3 & |
| 901.2.1. |
| |
| 10. SHT M-1, ALL WATER RISER DIAGRAMS. THE WATER HAMMER |
| ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| "EFFECTIVE RANGE" NOT IN THE CEILING AS INDICATED. |
| PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| |
| 11. A SEPARATE IRRIGATION PERMIT WILL BE REQUIRED. |
| PLANS MAY BE SUBMITTED AT THE TIME OF APPLICATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 808-6731 |
| E-MAIL [email protected] |